background image

 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

 Under all circumstances, the EN378 (or  

other applicable local safety regulation) 

requirements must be fulfilled.
The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation» 

section for further details. 
The condensing unit must be handled with cau-

tion in the vertical position (maximum offset 

from the vertical : 15°)

A

B

C

D

E

F

G

K

H

I
J

Installation and servicing of the 
condensing units by qualified 

personnel only. Follow these instructions 
and sound refrigeration engineering practice 
relating to installation, commissioning, 
maintenance and service.

A:   Model

B:   Code  number 

C:   Application,  Protection

D:   Refrigerant 

E:   Housing Service Pressure

F:  

Supply voltage, Locked Rotor Ampere, 

 

Maximum Current Consumption

G:   Serial Number and bar code

H:   Cable entry ports

I:   Suction  port

J:   Liquid  port

K:   Microchannel heat exchanger

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Picture 2 

Picture 3 

Mounting bolts 

1 – Introduction

These instructions pertain to Optyma™ High 

Ambient 52 Pack condensing units OP-LPHE/

MPZE (R404A, R134a) used for refrigeration sys-

tems. They provide necessary information regar-

ding safety and proper usage of this product.

The condensing unit includes following:

  •  Reciprocating  compressor

 •  Microchannel heat exchanger

 •  Dual pressure switches

 •  Service valves suction/liquid

 •  Weather proof housing

  •  Filter  drier

 •  Receiver with stop valve

  •  Sight  glass

  •  Solenoid  valve

 •  Oil separator (LBP only)

 •  Discharge thermostat (LBP Only)

2 – Handling and storage

 •  It is recommended not to open the packaging 

before the unit is at the final place for installation.

 •  Handle the unit with care. The packaging al-

lows for the use of a forklift or pallet jack. Use 

appropriate and safe lifting equipment. 

 •  Store and transport the unit in an upright position.

 •  Store the unit between -35°C and 60°C.

 •  Don’t expose the packaging to rain or corrosive 

atmosphere.

 •  After unpacking, check that the unit is com-

plete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 

 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.

 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture1 

for minimal values of distance to walls.

 •  Avoid installing the unit in locations which are daily 

exposed to direct sunshine for longer periods.

 •  Avoid installing the unit in aggressive and dus-

ty environments.

 •  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable enough 

to carry the entire unit weight and to eliminate 

vibrations and interference.

 •  The unit ambient temperature may not exceed 

52°C during off-cycle.

 •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

 •  When installing units for HFC refrigerants, use 

equipment specifically reserved for HFC refri-

gerants which was never used for CFC or HCFC 

refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 •  The suction piping connected to the compres-

sor must be flexible in 3 dimensions to dampen 

vibrations. Furthermore piping has to be done 

in such a way that oil return for the compres-

sor is ensured and the risk of liquid slug over in 

compressor is eliminated.

•  

For all units factory setting of fan speed 

controller to be 15 ±1 bar.

•  For refrigerant R134a, adjust the factory pres-

sure setting of XGE-2C (code no: 061H3144) 

from 15 ±1 bar to recommended setting 8 bar 

by rotating the screw by 9 turns in counter 

clockwise direction.

Instructions

Optyma™ High Ambient 52 Pack 

OP-LPHE/MPZE

1 | © Danfoss | DCS (CC)| 2017.12

FRCC.PI.056.A2.02

Summary of Contents for Optyma OP-LPHE Series

Page 1: ...use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between 35 C and 60 C Don t expose the packaging to rain or corrosive atmosphere After unpacking check that the unit is com plete and undamaged 3 Installation precautions Do not braze as long the condensing unit is under pressure Neverplacetheunitinaflammableatmosp...

Page 2: ...essure Low Pressure Energize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence phase 11 Check with running unit Check the fan rotation direction Air must flow from the condenser towards the fan Check current draw and voltage Check suction superheat to reduce risk of slug ging When a sight glass is provided observe the oil lev...

Page 3: ...PZE086MTW07V OP MPZE086MTW07N OP MPZE086MTW07Q H3 H3 H3 380V 3N 60Hz 230V 1N 60Hz 230V 3 60Hz OP MPZE060 068 086 OP LPHE108 136 2SW PD LJK PELHQW 3DFN 114X7140 LBP LBP LBP LBP LBP LBP MBP MBP MBP MBP MBP APP UNIT DESCRIPTION CHASSIS POWER SUPPLY COMP 114X7150 114X7153 114X7120 114X7141 114X7151 114X7146 114X7156 114X7117 114X7123 114X7157 NTZ048 NTZ048 NTZ048 NTZ068 NTZ068 NTZ068 MTZ018 MTZ018 MTZ...

Page 4: ... MTZ072 MTZ100 MTZ100 OP LPHE215NTW07Q OP LPHE215NTW07V OP LPHE271NTW07V OP LPHE271NTW07Q OP MPZE108MTW07N OP MPZE108MTW07V OP MPZE108MTW07Q OP MPZE0121MTW07V OP MPZE121MTW07Q OP MPZE171MTW07V OP MPZE171MTW07Q H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 230V 3 60Hz 380V 3N 60Hz 380V 3N 60Hz 230V 3 60Hz 230V 1N 60Hz 380V 3N 60Hz 230V 3 60Hz 380V 3N 60Hz 230V 3 60Hz 380V 3N 60Hz 230V 3 60Hz OP MPZE108 121 171 ...

Page 5: ...o LP auto LP man HP man HP man HP auto HP auto P H t e s e r n a m P L t e s e r t u a P L AC1 16 A DC 11 LR 112A AC3 16 A 400 V 12 W AC1110 A 220 V When used acc to UL regulations 1 bar Pe 30in Hg Convertible reset KP 15 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Instructions Danfoss DCS CC 2017 12 5 FRCC PI 056 A2 02 ...

Page 6: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions 6 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 ...

Page 7: ...tor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions Danfoss DCS CC 2017 12 7 FRCC PI 056 A2 02 ...

Page 8: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions 8 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 ...

Page 9: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions Danfoss DCS CC 2017 12 9 FRCC PI 056 A2 02 ...

Page 10: ...der Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white 10 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made wit...

Reviews: