Danfoss OPTYMA Control AK-RC 101 Operation And Maintenance Manual Download Page 12

12   

RS8FD402 

©

 Danfoss A/S 2014/11

 

 

OPTYMA

TM

 Control single-phase AK-RC 101

Variables Explanation

Value

Default

Fd

Fan differential below Fst

0…+10K

2K

LSE

Min. limit of set point setting

-45...HSE

-45°C

HSE

Max. limit of set point setting

45... LSE

45°C

tA

NO – NC 

alarm relay switching

0  =  activates when alarm is on 

1  =  deactivates when alarm is on

1

AU

Auxiliary/alarm relay control

 

0  =  alarm relay

1  =  manual auxiliary relay  

 

    controlled via AUX key

2  =  automatic auxiliary relay  

 

    managed by StA temp. setting  

    with 2°C differential

3  =  not used 

4  =  pump-down function (see 5.15)

5  =  free voltage contact for  

 

    condensing unit (AUX relay and  

    compressor relay in parallel)

6 =  Relay used to control a heating 

element in the crankcase. 

The relay is on when the 

compressor is stopped.

7 = The relay function is cancelled 

and data communication is 

permitted

0

StA

Temp. setting for aux. relay

-45…+45°C

0

In1

Man in cold room alarm

Select input INP1 on the board as compressor 

protection alarm or as man-in-room alarm  

(contact NC).

0  =  compressor protection

1  =  man-in-room alarm

0

P1

Password type of protection

( active when PA does not equal 0)

0  =  display set point only

1  =  display set point, AUX, light    

   access

2  =  access to programming not    

   permitted

3  =  access to second level  

 

    programming not permitted

3

PA

Password

(see P1 for the type of protection)

0...999

0  =  not active

0

reL

Software release

The version can be read

-

Continued...

Switching on the OPTYMA

TM

 Control single-phase

After wiring the electronic controller correctly, 

connect 230 V a.c.; the display panel will 

immediately emit a beep and all the LEDs will come 

on simultaneously for a few seconds.

Compressor activation/deactivation conditions

The OPTYMA

TM

 Control single-phase activates the 

compressor when cold room temperature exceeds 

differential (r0); it deactivates the 

compressor when the cold room temperature is 

lower than the setting.

Manual defrosting

To defrost just press the dedicated key (see page 8) 

to activate the elements relay. Defrosting will not 

take place if the end-of-defrost temperature setting 

(d2) is lower than the temperature detected by the 

evaporator sensor. Defrosting ends when the end-

of-defrost temperature (d2) or maximum defrost 

time (d3) is reached.

When using data communication, the defrost cycle 

can be started from the system unit.

Summary of Contents for OPTYMA Control AK-RC 101

Page 1: ...OPTYMATM Control Single phase AK RC 101 MAKING MODERN LIVING POSSIBLE Operation and Maintenance Guide...

Page 2: ...anel 8 Front keypad 8 LED Display 9 General 9 Symbols used 9 Setting and displaying the set points 9 Level 1 Programming User Level 10 List of Level 1 variables User Level 10 Level 2 Programming Insta...

Page 3: ...off cycle or electrical defrosting and with direct or pump down compressor stop Control of single phase evaporator unit only with solenoid valve or remote condensing unit Main characteristics Direct...

Page 4: ...the length of connector wires so that wiring does not twist into a spiral shape as this could have a detrimental effect on the electronics Installation 5 Fit a general protection fuse before the elect...

Page 5: ...ver on the right hand side of the housing Installing the unit 2 Undo the 4 fixing screws at the front of the housing 3 Open the front of the housing lift it and slide the two hinges out as far as they...

Page 6: ...le be especially careful to keep power wires away from signal wires Use clips to hold wires in place 7 Close the front panel making sure that all the wires are inside the housing and that the housing...

Page 7: ...ower supply Voltage 230 V 10 50Hz 60Hz Power consumption electronics only 7 VA Cold room conditions Operating temperature 5 to 50 C Storage temperature 10 to 70 C Relative humidity Less than 90 Not co...

Page 8: ...101 Control Panel Front keypad AUXILIARY RELAY CONTROL on the version with alarm relay controls the relay manual if parameter AU 1 UP MUTE WARNING BUZZER STAND BY The LED flashes if the system shuts d...

Page 9: ...rameters The second programming level Level 2 is for general parameter programming of the various controller work modes It is not possible to access the Level 2 programming directly from Level 1 you m...

Page 10: ...oint Defrosting will not take place if the temperature detected by the defrost sensor is greater than d2 If the sensor is faulty defrosting is timed 35 45 C 15 C d3 Max defrost duration minutes 1 240...

Page 11: ...ing defrost 0 fans run during defrost 1 fans do not run during defrost 1 dE Sensor presence If the evaporator sensor is disabled defrosts are carried out cyclically with period d0 defrosting ends when...

Page 12: ...Password type of protection active when PA does not equal 0 0 display set point only 1 display set point AUX light access 2 access to programming not permitted 3 access to second level programming not...

Page 13: ...st relay control Pump down function Pump down function is activated when parameter AU 4 for version with AUX Alarm relay only Connect pump down pressostat on the digital input INP 1 The compressor is...

Page 14: ...oard Alarm relay 2 Undo the 6 CPU board fixing screws remove the board from the front part of the housing in ABS 3 Remove the jumper from JUMPER JP2 4 Insert the jumper in JUMPER JP2 in position 3 2 t...

Page 15: ...alarm An EEPROM memory alarm has been detected All outputs except the alarm one are deactivated Switch unit off and then back on again E8 Man in room alarm Reset the alarm input inside the cold room...

Page 16: ...rol single phase AK RC 101 Connection diagram Comp Protection Door Limit Switch Common dig input Defrost probe Ambient probe Common probe Power Supply 230Vac Common 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 17: ...Supply 230Vac 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Modbus Danfoss 80Z681 10 A B A B 1 2 N L P Connect Compr Relay output to room thermostat input terminals of OptymaPlus SlimPack remove br...

Page 18: ...1 Housing back panel in ABS 2 Housing front panel in ABS 3 Front cover in transparent polycabonate 4 Front panel opening hinge 5 Front panel closure screws 6 Board fixing screws 7 Automatic fuse Cut o...

Page 19: ...OPTYMATM Control single phase AK RC 101 RS8FD402 Danfoss A S 2014 11 19 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3200 Sensor EKS 221 spare part 084N3210...

Page 20: ...20 RS8FD402 Danfoss A S 2014 11 OPTYMATM Control single phase AK RC 101 Notes...

Reviews: