Danfoss OPTYMA Control AK-RC 101 Operation And Maintenance Manual Download Page 11

OPTYMA

TM

 Control single-phase  AK-RC 101 

RS8FD402 

©

 Danfoss A/S 2014/11

 

 

11

Level 2 - Programming (Installer Level)

To access the second programming level press the 

UP (

) and DOWN (

) keys and the LIGHT key 

simultaneously for a few seconds.

When the first programming variable appears the 

system automatically goes to stand-by.

1.  Select the variable to be modified by pressing the  

  UP (

) and DOWN (

) keys.

  When the parameter has been selected it is  

  possible to:

2.  View the setting by pressing the SET key.

3.  Modify the setting by holding the SET key down  

  and pressing the (

) or (

) key.

4.  When configuration settings have been 

completed you can exit the menu by pressing the 

(

) and (

) keys simultaneously and keep them 

pressed until the room temperature reappears.

5.  Changes are saved automatically when you exit  

  the configuration menu.

6.  Press the STAND-BY key to enable electronic  

 control.

List of Level 2 variables (Installer Level)

Variables Explanation

Value

Default

AC 

Door switch status

0  =  normally open

1  =  normally closed

0

F3

Fan status with compressor off

0  =  fans run continuously

1  =  fans only run when  

 

    compressor is working

1

F4

Fan pause during defrost

0  =  fans run during defrost

1  =  fans do not run during defrost

1

dE   

Sensor presence

If the evaporator sensor is disabled defrosts are 

carried out cyclically with period d0: defrosting 

ends when an external device trips and closes the 

remote defrost contact or when time d3 expires.

0  =  evaporator sensor present

1  =  no evaporator sensor

0

d1 

Defrost type

, cycle inversion (hot gas) or with 

heater elements

1  =  hot gas

0  =  electric

0

bdr

Modbus baudrate

(Danfoss System unit =19200 baud)

0=300. 1=600. 2=1200. 3=2400. 

4=4800. 5=9600. 6=14400.

7=19200

. 8=38400 baud.

7

Ad

Modbus address

1 ... 247 

(+ setting: AU must be set to 7)

(+ move jumper: see page 14)

0

Ald

Minimum and maximum temperature 

Signalling and alarm display delay

1…240 min

120 min

C1

Minimum time between shutdown and 

subsequent switching on of the compressor

0…15 min

0 min

CAL

Correction of sensor signal

-10…+10

0

Pc

Compressor protection contact status

0 = NO

1 = NC

0 = NO

doC

Compressor safety time for door switch

: when 

the door is opened the evaporator fans shut down 

and the compressor will continue working for time 

doC, after which it will shut down.

0…5 minutes

0

tdo

Restart time, if the door remains open

0... 240 min. (0=no function)

0

Fst

FAN shutdown TEMPERATURE

The fans will stop if the temperature value read by 

the evaporator sensor exceeds  this value.

-45…+45°C

+45°C

Summary of Contents for OPTYMA Control AK-RC 101

Page 1: ...OPTYMATM Control Single phase AK RC 101 MAKING MODERN LIVING POSSIBLE Operation and Maintenance Guide...

Page 2: ...anel 8 Front keypad 8 LED Display 9 General 9 Symbols used 9 Setting and displaying the set points 9 Level 1 Programming User Level 10 List of Level 1 variables User Level 10 Level 2 Programming Insta...

Page 3: ...off cycle or electrical defrosting and with direct or pump down compressor stop Control of single phase evaporator unit only with solenoid valve or remote condensing unit Main characteristics Direct...

Page 4: ...the length of connector wires so that wiring does not twist into a spiral shape as this could have a detrimental effect on the electronics Installation 5 Fit a general protection fuse before the elect...

Page 5: ...ver on the right hand side of the housing Installing the unit 2 Undo the 4 fixing screws at the front of the housing 3 Open the front of the housing lift it and slide the two hinges out as far as they...

Page 6: ...le be especially careful to keep power wires away from signal wires Use clips to hold wires in place 7 Close the front panel making sure that all the wires are inside the housing and that the housing...

Page 7: ...ower supply Voltage 230 V 10 50Hz 60Hz Power consumption electronics only 7 VA Cold room conditions Operating temperature 5 to 50 C Storage temperature 10 to 70 C Relative humidity Less than 90 Not co...

Page 8: ...101 Control Panel Front keypad AUXILIARY RELAY CONTROL on the version with alarm relay controls the relay manual if parameter AU 1 UP MUTE WARNING BUZZER STAND BY The LED flashes if the system shuts d...

Page 9: ...rameters The second programming level Level 2 is for general parameter programming of the various controller work modes It is not possible to access the Level 2 programming directly from Level 1 you m...

Page 10: ...oint Defrosting will not take place if the temperature detected by the defrost sensor is greater than d2 If the sensor is faulty defrosting is timed 35 45 C 15 C d3 Max defrost duration minutes 1 240...

Page 11: ...ing defrost 0 fans run during defrost 1 fans do not run during defrost 1 dE Sensor presence If the evaporator sensor is disabled defrosts are carried out cyclically with period d0 defrosting ends when...

Page 12: ...Password type of protection active when PA does not equal 0 0 display set point only 1 display set point AUX light access 2 access to programming not permitted 3 access to second level programming not...

Page 13: ...st relay control Pump down function Pump down function is activated when parameter AU 4 for version with AUX Alarm relay only Connect pump down pressostat on the digital input INP 1 The compressor is...

Page 14: ...oard Alarm relay 2 Undo the 6 CPU board fixing screws remove the board from the front part of the housing in ABS 3 Remove the jumper from JUMPER JP2 4 Insert the jumper in JUMPER JP2 in position 3 2 t...

Page 15: ...alarm An EEPROM memory alarm has been detected All outputs except the alarm one are deactivated Switch unit off and then back on again E8 Man in room alarm Reset the alarm input inside the cold room...

Page 16: ...rol single phase AK RC 101 Connection diagram Comp Protection Door Limit Switch Common dig input Defrost probe Ambient probe Common probe Power Supply 230Vac Common 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 17: ...Supply 230Vac 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Modbus Danfoss 80Z681 10 A B A B 1 2 N L P Connect Compr Relay output to room thermostat input terminals of OptymaPlus SlimPack remove br...

Page 18: ...1 Housing back panel in ABS 2 Housing front panel in ABS 3 Front cover in transparent polycabonate 4 Front panel opening hinge 5 Front panel closure screws 6 Board fixing screws 7 Automatic fuse Cut o...

Page 19: ...OPTYMATM Control single phase AK RC 101 RS8FD402 Danfoss A S 2014 11 19 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3200 Sensor EKS 221 spare part 084N3210...

Page 20: ...20 RS8FD402 Danfoss A S 2014 11 OPTYMATM Control single phase AK RC 101 Notes...

Reviews: