background image

Instructions

AN293820378892en-000101 | 7

© Danfoss | DCS (CC) | 2019.01

• Check that all safety devices are operational 

and properly set (safety pressure switch set 

point, mechanical relief valve if necessary, etc.). 

Make sure that these devices comply with both 

generally - and locally - applicable regulations 

and standards (e.g. EN 378-2:2012).

• When using high-pressure switches or relief 

valves, the setting must not exceed maximum 

service pressure of any system component. Re-

fer to the Application Guidelines for relevant 

condensing unit pressure safety limits.

• A low-pressure switch is recommended to 

prevent operation under vacuum. Use a mini-

mum setting of 1.2 bar (absolute).

• Verify that all electrical connections are proper-

ly fastened and in compliance with local safety 

regulations.

• A compressor crankcase heater is factory ins-

talled, ensure that it has been energized for a 

minimum of 12 hours before initial start-up and/

or during prolonged shutdown periods.

10 - Start up

 Never start the compressor in the absence of 

a refrigerant charge. 

• Do not bypass the LP or any other safety swit-

ches during start-up

• Check current draw and voltage levels.

• Monitor the oil sight glass to ensure proper oil 

return to the compressor.After 2 to 4 hours of 

operations under established conditions, check 

the oil level and add oil if necessary (refer to TI 

bulletin 3-025).

If oil return continues to perform poorly, further 

investigation of the piping design is required. 

• In all cases, the application limits of the compressor 

must be respected; moreover, high superheat values 

lead to high discharge temperatures and decrease 

compressor capacity. The maximum discharge tem-

perature is 130°C: operating ata higher temperature 

may result in refrigerant decomposition.

• Under steady-state operating conditions, check 

refrigerant piping or capillary tubes for abnor-

mal vibrations (refrigeration line movement in 

excess of 1.5 mm necessitates corrective actions, 

pipe brackets, etc.).

• Ensure that refrigerant flow through the liquid 

line sight glass (when mounted) is adequate and 

that operating temperatures correspond with 

system specifications.

• When needed, refrigerant may be added in the 

liquid phase, carefully throttling the refrigerant 

on the low-pressure side and as far as possible 

from the compressor.The compressor must be 

operating during this process.

 Do not overcharge the system.

11 - Troubleshooting

• 

Compressor failure to start:

 verify that the 

compressor is hooked up to the power supply; 

check the power lead connections and all sui-

table capacitors on single-phase models. If these 

verifications reveal no abnormality, control the 

motor windings with an ohmmeter. 

Note: when the internal motor protector has 

tripped out, it may take up to several hours to 

reset and restart the compressor.

• Compressor failure to build up pressure:

 

check to make sure that all bypass valves in the 

system have not been opened. Also check that 

all solenoid valves are in their proper position. 

If the internal pressure relief valve is open, the 

compressor sump will be warm and the com-

pressor will trip out on the motor protector. If 

this happens, it may take up to 2 or 3 hours to 

reset and automatically restart the compressor.

• Abnormal running noise on the system: 

  - Ensure the absence of any liquid flood-back 

to the compressor by means of measuring the 

return gas superheat and compressor sump 

temperature. The sump should be at least 10K 

above the saturated suction temperature under 

steady-state operating conditions.

  - Check that the fans are running free and wit-

hout vibration.

• The high-pressure switch trips out:

 check 

condenser operations (condenser cleanliness, 

fan operations, etc.). If above check out OK, the 

problem may be due to either refrigerant over-

charging or the presence of a non-condensable 

(e.g. air, moisture) in the circuit. 

• The low-pressure switch trips out:

 check eva-

porator operations (coil cleanliness, fan opera-

tions, water flow, water filter, etc.), liquid refrige-

rant flow and pressure drops (solenoid valve, filter 

dryer, expansion valve, etc.), refrigerant charge.

• Low refrigerant charge:

 the correct refrige-

rant charge is given by the liquid sight glass 

indication, the condenser delta T in relation to 

the refrigerant pressure tables (pressure-tempe-

rature), the superheat and the sub-cooling, etc. 

(if additional charge is deemed necessary, refer 

to the 

«Filling the system»

 section). 

• Compressor maximum short cycling: 

there 

must be a minimum delay of five minutes 

between two compressor starts. DCC recom-

mends the compressor should run at least two 

minutes after each start, and between each stop 

and start must be three minutes standstill. Only 

during pump down cycle, the compressor may 

run much shorter until the pumpdown pressure 

has been reached or when safety devices will 

prohibit compressor further operation.

12 - Maintenance

• Proper operations and maintenance of the 

condensing units serve to prevent against sys-

tem-related problems.The following preventive 

maintenance checks, to be performed at regular 

intervals, are highly recommended:

  - Control operating conditions (evaporating 

temperature, condensing temperature, com-

pressor discharge temperature, temperature 

difference on heat exchangers, superheat, 

sub-cooling). These conditions must always re-

main within compressor operation limits.

  - Verify that safety devices are operational and 

properly set.

  - Check the compressor oil level and quality; 

this step may include an acid test, humidity 

check, spectrometer analysis, etc. whenever the 

oil becomes discolored.
  - Ensure that the circuit is leak tight.

  - Verify the proper operation of heat exchan-

gers and, if necessary, clean them.

  - Check that the fans are running free (without 

vibration) and current draw on the compressor 

motor as well as proper voltage balance between 

phases.

  - Change the filter dryer when necessary.

  - Check that all electrical connections are still 

adequately fastened. 

  - Make sure the condensing unit is clean and 

in good working order; verify the absence of rust 

or corrosion on components under pressure and 

electrical connections. 

  - Make sure the refrigerant charge is suitable 

for both winter and summer operation.

• Ensure that periodic in-service inspections re-

quired by local regulations are performed. 

13 - Replacement

 Precaution must be taken when disconnec-

ting any components, cutting or drilling holes in 

the tubing to ensure that no refrigerant under 

pressure is present in the system.

 The refrigerant shall not be discharged direc-

tly into the atmosphere; rather, it must be remo-

ved using approved reclamation techniques and 

equipment and then safely stored, inaccordance 

with applicable legislation.

 The presence of refrigerant vapor can displace 

air and lead to suffocation. Proper ventilation is 

mandatory at all times when servicing the equip-

ment.

 A condensing unit component change must be 

carried out in compliance with local regulations.

• Make sure that the main power supply has 

been switched off.

• Before replacement, it is necessary to deter-

mine the cause of failure and implement reme-

dial action. If such analysis and repair are not 

performed, repetitive failure may occur. Note 

that an oil acidity test always proves helpful in-

diagnosis when undertaking compressor repla-

cement.

• Check that the replacement component has 

the same electrical and refrigeration perfor-

mance characteristics as the original one.

• Whenever piping needs to be modified, please 

refer to the 

«Safety measures prior to assem-

bly»

 section.

• For further details on replacement steps,refer 

to the previous sections of this manual.

Note:

 

In the event of compressor motor failure, 

flush and clean the entire circuit before repla-

cing the compressor in order to remove acids and 

contaminants. Systematically install a new filter 

dryer on the liquid line. Prior to this step (if ne-

cessary), run the system for at least 2 hours with 

anti-acid cartridges (in such instances, the instal-

lation of a suction filter might also be required). Af-

ter an operating period of approximately 2 weeks, 

check the level of oil acidity. If the oil acid test pro-

ves positive, drain and replace the oil, replace the 

anti-acid liquid line filter dryer cartridges and the 

suction filter previously installed. Repeat oil and 

Summary of Contents for Optyma Blue OP-LGHE068NTA07D

Page 1: ...TA07D 114X8060 OP LGHE215NTA07D 114X8048 OP LGHE271NTA07D 114X8061 OP MGZE038MTA07G R404A R507 R134a 114X8062 OP MGZE048MTA07D 114X8063 OP MGZE060MTA07D 114X8064 OP MGZE086MTA07D 114X8065 OP MGZE108MT...

Page 2: ...temperature C MGZE MTZ MBP Models R134a SH10K Wiring Diagram WD1 MGZE MTZ MBP Models R404A 507 SH10K 15 25 20 35 30 45 40 50 55 35 30 25 20 15 10 5 0 5 40 45 15 25 20 35 30 45 40 50 55 25 20 15 10 5 0...

Page 3: ...3P 50Hz D 50Hz Voltage range 3 Phases 342V 440V G 220V 240V 1P 50 Hz Compressor 230V 1P 50Hz Fan 230V 1P 50Hz G 50Hz Voltage range 1 Phase 200V 264V D 380V 415V 3P 50 HZ Compressor 415V 3P 50Hz Fan 4...

Page 4: ...Instructions 4 AN293820378892en 000101 Danfoss DCS CC 2019 01 For R404A models HP bar LP bar MBP 28 8 LBP 28 3 Factory setting...

Page 5: ...rosive flammable atmosphere 3 Safety measures prior to assembly All installation and servicing is to be performed by qualified personnel in compliance with all pertinent practices and safety procedure...

Page 6: ...r than to the Schrader connec tion This recommendation allows avoiding excessive pressure losses Moisture level At the time of commissioning system moisture content may be as high as 100 ppm During op...

Page 7: ...filter dryer expansion valve etc refrigerant charge Low refrigerant charge the correct refrige rant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrig...

Page 8: ...cut the compressor shell and adjacent tubing release of liquid refrigerant can cause flash freezing on exposed skin Even though fans are fitted with safety guard it is recommended not to work on conde...

Reviews: