Parameter list - Valid from: (i58:9, i59:18)) and onwards

Description

ICAD 

parameter

Min Max Factory 

Setting

Stored Unit Pass 

word

Comments

OD (Opening degree)

-

0

100

%

-

ICM valve Opening Degree is displayed during normal operation. 

Running display value (see 

¡01

¡05

).

Main Switch

¡01

1

2

1

-

No

Internal main switch 

1: Normal operation 

2: Manual operation. Valve Opening Degree will be flashing. With the down  

  arrow and the up arrow push buttons the OD can be entered manually.

Mode

¡02

1

2

1

-

No

Operation mode 

1:   Modulating – ICM positioning according to Analog Input (see

 ¡03

2:   ON/OFF - operating the ICM valve like an ON/OFF solenoid valve  

 

  controlled via Digital Input. See also 

¡09

.

3:   Neutralzone / 3 point control. Increase/Decrease Opening Degree by    

  Digital Input. See fig. 9

AI signal

¡03

1

4

2

-

No

Type of AI signal from external controller 

1: 0-20 mA 

2: 4-20 mA 

3: 0-10 V 

4: 2-10 V

Speed 

In 

Modulating Mode

 

Opening/closing speed 

 

In 

ON/OFF Mode

 

Opening speed

¡04

1

100

50/ 100

-

No

Speed can be decreased. Max. speed is 100 % - Not active in manual operation (

¡01

 = 

2) 

 

If 

¡26

= 1 - 3 then factory setting =100 

If 

¡26

= 4 - 9 then factory setting =50 

 

If ICM is opening and (

¡04

 < = 33) or ICM is closing and (

¡14

 < = 33) 

=> Low is displayed. 

 

If ICM is opening and (33 < If 

¡04

 < = 66) or ICM is closing and (33 < If 

¡14

 < = 66) 

=> Med is displayed. 

 

If ICM is opening and (

¡04

 > = 67) or ICM is closing and (

¡14

 > = 67)  

=>  High is displayed"

Automatic calibration

¡05

0

2

0

-

No

Not active before 

¡26

 has been operated. 

Always auto reset to 0. 

CA will flash in the display during calibration, 

if Enter push button has been activated for two seconds 

0: No Calibration 

1: Normal forced calibration -  CA flashing slowly 

2: Extended calibration – CA flashing rapidly"

AO signal

¡06

0

2

2

-

No

Type of A0 signal for ICV valve position 

0: No signal 

1: 0-20 mA 

2: 4-20 mA

Failsafe

¡07

1

4

1

-

No

Define condition at power cut and fail safe supply is installed. 

1: Close valve 

2: Open Valve 

3: Maintain valve position 

4: Go to OD given by 

¡12

"

Fail safe supply

¡08

0

1

0

Yes

Fail safe supply connected and enable of A4 alarm: 

0: No 

1: Yes 

DI function

¡09

1

2

1

No

Define function when DI is ON (short circuited DI terminals) when 

¡02

 = 2 

1: Open ICM valve (DI = OFF = > Close ICM valve) 

2: Close ICM valve (DI = OFF = > Open ICM valve)

Password

¡10

0

199

0

-

-

Enter number to access password protected parameters: 

¡26

 

Password = 11

Old Alarms

¡11

A1

A99

-

-

No

Old alarms will be listed with the latest shown first. Alarm list can be reset by means  

of activating down arrow and up arrow at the same time for 2 seconds.

OD at power cut.

¡12

0

100

50

No

Only active if 

¡07

 = 4 

If fail safe supply is connected and power cut occurs, the ICM will go to the specified OD.

Inverse operation

¡13

0

1

0

No

When 

¡02

 = 1

0:   Increasing Analog Input signal => Increasing ICM Opening Degree 

1:   Increasing Analog Input signal => Decreasing ICM Opening Degree   

When 

¡02

 = 3

0:   DI1 = ON, DI2 = OFF => Increasing ICM Opening Degree.

     DI1 = OFF, DI2 = ON  => Decreasing ICM Opening Degree

  DI1 = DI2 = OFF  

=> ICAD/ICM maintain current position

  DI1 = DI2 = ON  

=> ICAD/ICM maintain current position

1:   DI1 = ON, DI2 = OFF  => Decreasing ICM Opening Degree 

  DI1 = OFF, DI2 = ON  => Increasing ICM Opening Degree

  DI1 = DI2 = OFF  

=> ICAD/ICM maintain current position

  DI1 = DI2 = ON  

=> ICAD/ICM maintain current position

In 

ON/OFF Mode

 

 

Closing speed

¡14

0

100

50/ 100

-

No

See 

¡04

.  

If 

¡26

= 1 - 3 then factory settin qg = 100 

If 

¡26

= 4 - 9 then factory setting = 50

Manual set point

¡15

0

100

0

No

When 

¡01

= 2, 

¡15

 determine the start up value.

Encoder operation

¡16

0

1

0/1

Yes

NB: 

Password protected. Password = 7 

If 

¡26

 = 1 - 3 then factory setting = 0 

If 

¡26

 = 4 - 6 then factory setting = 0 (1 if ICAD1200) 

If 

¡26

 = 7 - 9 then factory setting = 1 

0: Encoder disabled. Means ICAD operation as ICAD 600/900 

1: Encoder enabled

ICM configuration

¡26

0

9

0

Yes

NB: 

Password protected. Password = 11 

0: No valve selected. Alarm A1 will become active. 

1: ICM 20 with ICAD 600 

2: ICM 25 with ICAD 600 

3: ICM 32 with ICAD 600 

4: ICM 40 with ICAD 900/1200 

5: ICM 50 with ICAD 900/1200 

6: ICM 65 with ICAD 900/1200 

7: ICM 100 with ICAD 1200 

8: ICM 125 with ICAD 1200 

9: ICM 150 with ICAD 1200

Summary of Contents for Old ICAD 1200 series

Page 1: ...027R9796 Fig 1 Fig 2 Fig 3 Fig 4 ICAD 600 ICAD 900 ICAD 600 ICAD 900 ICAD 1200 Fig 5a ICM ICAD 600 Fig 5b ICM ICAD 900 mm in H 45 1 77 L3 25 1 Instruction Actuator ICAD 600 ICAD 900 ICAD 1200 ICAD 1200 Fig 5c ICM ICAD 1200 Note When mounting the ICAD make sure to push ICAD down to mechanical stop ...

Page 2: ...safe supply Battery UPS 19 V d c II White Supply voltage 24 V d c III Brown Digital Ouput Analog In Output ICAD 600 900 1200 Uninterruptible Power Supply Terminal box Control cable Supply cable Only possible with EKC 347 Terminal box ICAD 600 900 1200 Digital I O for ON OFF valve operation Auxiliary relays Terminal box Fig 8 III I II C D E B A G F 4 pin male connector 8 pin male connector External...

Page 3: ...d Orange GND are used for current mA output optional not mandatory Fig 6 Digital operation 7 wired cable A G ON OFF ICM solenoid valve operation ICM valve to be controlled by means of a digital voltfree contact Connect digital input signals fig 8 See Parameter list for configuration of digital input signals Green and Orange GND are connected to a voltfree contact Digital output signals are optiona...

Page 4: ...lve with low speed according to a digital input signal Med represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal High represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with high speed according to a digital input signal Like below Alarms ICAD can handle and display different alarms Description...

Page 5: ...ve 2 Open Valve 3 Maintain valve position 4 Go to OD given by 12 Fail safe supply 08 0 1 0 Yes Fail safe supply connected and enable of A4 alarm 0 No 1 Yes DI function 09 1 2 1 No Define function when DI is ON short circuited DI terminals when 02 2 1 Open ICM valve DI OFF Close ICM valve 2 Close ICM valve DI OFF Open ICM valve Password 10 0 199 0 Enter number to access password protected parameter...

Page 6: ... DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Close 55 0 1 DO Closed status ON when OD 3 DO Open 56 0 1 DO Open status ON when OD 97 DO Alarm 57 0 1 DO alarm status ON when a Alarm is detected Display mP SW ver 58 0 100 Software version for display microprocessor Motor mP SW ver 59 0 100 Software version for motor microprocessor Reset to factory setting 1 Remove the power supply 2 Activate down a...

Page 7: ......

Page 8: ... Danfoss A S AC SMC MWA 08 2011 DKRCI PI HV0 E6 02 520H3832 8 www danfoss com icv ...

Reviews: