ICAD 600/900/1200 - Analog I/O 

for modulating control

Fig. 6

Fig. 7

Reference Color

Description

A

Black 

– Common Alarm

B

Brown 

– ICM fully open

C

Red

– ICM fully closed

D

Orange

– GND ground

E

Yellow 

+ 0/4 - 20 mA Input

F

Green 

+ 0/2 - 10 V Input

G

Blue 

+ 0/4 - 20 mA Output

I

Black 

+ Fail safe supply

Battery / UPS* 19 V d.c.

II

White 

+

Supply voltage 24 V d.c.

III

Brown 

}

Digital Ouput

Analog In/Output

ICAD 600/900/1200

 Uninterruptible Power Supply 

}

Terminal box

Control cable

Supply cable

Only possible with EKC 347

Terminal box

ICAD 600/900/1200 - Digital I/O for 

ON/OFF valve operation

Auxiliary relays

Terminal box

Fig. 8

III

I

II

C

D

E

B

A

G

F

4 pin male connector

8 pin male connector

External

voltage

24 V d.c.

(+)
(–)

K

1

K

2

K

1

K

2

II III

Supply

D         F         G                 E

DI1

DI2

Control

ICAD

Danfoss

M27H0163_1

Neutral zone / 3 point control

Fig. 9

Summary of Contents for Old ICAD 1200 series

Page 1: ...027R9796 Fig 1 Fig 2 Fig 3 Fig 4 ICAD 600 ICAD 900 ICAD 600 ICAD 900 ICAD 1200 Fig 5a ICM ICAD 600 Fig 5b ICM ICAD 900 mm in H 45 1 77 L3 25 1 Instruction Actuator ICAD 600 ICAD 900 ICAD 1200 ICAD 1200 Fig 5c ICM ICAD 1200 Note When mounting the ICAD make sure to push ICAD down to mechanical stop ...

Page 2: ...safe supply Battery UPS 19 V d c II White Supply voltage 24 V d c III Brown Digital Ouput Analog In Output ICAD 600 900 1200 Uninterruptible Power Supply Terminal box Control cable Supply cable Only possible with EKC 347 Terminal box ICAD 600 900 1200 Digital I O for ON OFF valve operation Auxiliary relays Terminal box Fig 8 III I II C D E B A G F 4 pin male connector 8 pin male connector External...

Page 3: ...d Orange GND are used for current mA output optional not mandatory Fig 6 Digital operation 7 wired cable A G ON OFF ICM solenoid valve operation ICM valve to be controlled by means of a digital voltfree contact Connect digital input signals fig 8 See Parameter list for configuration of digital input signals Green and Orange GND are connected to a voltfree contact Digital output signals are optiona...

Page 4: ...lve with low speed according to a digital input signal Med represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal High represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with high speed according to a digital input signal Like below Alarms ICAD can handle and display different alarms Description...

Page 5: ...ve 2 Open Valve 3 Maintain valve position 4 Go to OD given by 12 Fail safe supply 08 0 1 0 Yes Fail safe supply connected and enable of A4 alarm 0 No 1 Yes DI function 09 1 2 1 No Define function when DI is ON short circuited DI terminals when 02 2 1 Open ICM valve DI OFF Close ICM valve 2 Close ICM valve DI OFF Open ICM valve Password 10 0 199 0 Enter number to access password protected parameter...

Page 6: ... DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Close 55 0 1 DO Closed status ON when OD 3 DO Open 56 0 1 DO Open status ON when OD 97 DO Alarm 57 0 1 DO alarm status ON when a Alarm is detected Display mP SW ver 58 0 100 Software version for display microprocessor Motor mP SW ver 59 0 100 Software version for motor microprocessor Reset to factory setting 1 Remove the power supply 2 Activate down a...

Page 7: ......

Page 8: ... Danfoss A S AC SMC MWA 08 2011 DKRCI PI HV0 E6 02 520H3832 8 www danfoss com icv ...

Reviews: