background image

9

521B0881   DKCFN.PI.020.F1.02

12. Trouble Shooting

Motor does not start:

•  Check power supply

•  Check start permission from control system

•  FCM 300: 

 

o  Check programming

 

o  Is a start signal applied to terminal 4?

 

o  Is the supply pressure sufficient?

 

o  Is the water temperature below 50°C/122°F

 

o  Is line 2 blinking when using an LCP? If so, press START

 

o  Reset the FCM after a fault or trip condition

Pump does not generate pressure:

•  Check water supply:

 

o  Ball valve open?

 

o  Supply pressure OK?

 

o  Filter OK, not clogged?

•  Repeat bleeding procedure

 

o  Bleed the filter

 

o  Bleed the pump

•  Check application:

 

o  Is any dump valve open?

 

o  Are all nozzles properly installed and tight?

 

o  Is there still any air in pipes and hoses?

•  After pump replacement:

 

o  Have the installation instructions for the pump been observed?

 

o  Has the flexible coupling between motor and pump been  

 

installed properly? No axial load is tolerated! 

Pump generates too low pressure:

•  Is the pressure relief valve properly adjusted?

•  Is the FCM 300 pressure set point programmed correctly?

•  Are there any leakages in the system?

•  Do all nozzles spray as expected?

•  Is the Plug&Spray

TM

 unit properly sized in relation to the nozzles?

Pump is noisy:

•  A noisy pump is often a sign of cavitation.

 

o  Is the system properly bleeded? 

 

o  Is the supply pressure sufficient?

 

o  In case of a mechanical failure, stop the pump immediately and  

 

return it for inspection.

Pressure decreases over time:

•  The pump is providing less and less pressure over time.

 

o  Has the resistance of the nozzles changed?

 

o  Are there any leakages in the system?

 

o  Is the pressure relief valve still adjusted correctly?

 

o  The pump may have reached its service life and requires a  

 

refurbishment.

11. Maintenance

11.1 Filter replacement:

The supply pressure manometer allows to check the supply pressure 

and to monitor it for preventative maintenance, e.g. changing filter. 

When the pressure drop across the filter increases over time as the 

filter becomes dirty, the pressure will decrease. To avoid an unforeseen 

system stop, replace the filter cartridge before reaching the cut-off 

pressure level of 1.6 bar (23 psi).

•  Use only original Danfoss spare part 

•  Shut the ball valve

•  Relief pressure from the system by pressing the red button

•  Remove the filter housing and the used cartridge

•  Attach the gaskets on both ends (thin type) to the new cartridge

•  Insert the new cartridge 

•  Please be careful with the O-ring in the filter housing

•  Turn the filter house carefully when reapplying

•  Make sure that the gasket stays in proper position

•  Only hand tighten the filter house, do not use a tool!

 

Never run the system without filter cartridge! Improper filtration 

may result in severe damage or reduced lifetime. Danfoss will not 

accept warranty claims due to contamination.  

11.2 Pump replacement

Nessie pumps are maintenance-free. Under normal operation conditi-

ons and with sufficient filtration, the pump service life is at least 8000 

operating hours. Only when the pump performance is decreasing or 

the noise level increasing, the pump should be replaced immediately.

In systems with high availability demands, Danfoss recommends a 

preventive pump replacement after 8000 operating hours.

The replacement must only be made by an authorized Danfoss service 

partner.   

11.3 Decommissioning

Humidification and adiabatic cooling systems are often seasonally 

operated. This may result in longer periods of no operation and the 

following problems:

•  Hygiene problems due to bacteria growth (bio film)

•  Corrosion of vital parts (if air accumulates in the system over time)

The best way to avoid both problems is to run the system - although 

not needed - for a couple of minutes every day to entirely replace the 

water in the system. An optional drain valve may be installed to drain 

the system to the sewer. If this is not feasible, the system should be 

preserved as described in the following chapter about frost protection.

11.4 Frost protection:

If the Plug&Spray

TM

 unit is exposed to temperatures below freezing, 

the system must be frost protected with a glycol mixture (minimum 

35% of monopropylene glycol). 

Follow this procedure:

•  Disconnect the water supply; connect the supply to a canister with 

glycol mixture

•  Drain the system as much as possible, remove the filter housing to 

drain it

•  Connect the high-pressure discharge to the same canister with 

glycol mixture

•  Briefly run the pump pressure-less to entirely fill the system with 

glycol mixture

•  To re-commission, flush the system as described above

•  It is recommended to renew the filter cartridge shortly after re-com-

missioning!

  

 

Never just drain the system! Remaining water will result in corrosion 

and damage! Always refill the system with water or glycol mixture. 

Summary of Contents for Nessie Plug&Spray NPS 1CS

Page 1: ...e Ionized Reverse Osmosis Danfoss defines clean tap water as water filtered to 10 m absolute value than 5000 This means that the water is filtered to a level where 99 995 of all particles larger than1...

Page 2: ...The units come in a constant speed version with IEC or Nema electric motor as well as in a version with constant pressure regulation using a Danfoss FCM 300 variable speed drive motor The Plug SprayT...

Page 3: ...The upper support part is inserted into the bottom part during instal lation and joined together with the supplied screws NB The mounting plate must be fixed to the floor with 4 bolts to secure the sy...

Page 4: ...directions must be followed under any circumstance 8 1 Basic unit without electrical connecting box Constant speed version CS Electric motor The electric motor is a standard IEC or Nema AC motor and...

Page 5: ...ired and prepared for direct power supply connection The following connections must be made 3 phase power supply 3 400 V Start signal through external potential free contact Fault relay Please refer t...

Page 6: ...alve preventing return flow into the supply The water temperature must be kept between 3 and 50 C respec tively 37 and 122 F The supply pressure must not exceed 2 and 4 bar In case of unstable or peak...

Page 7: ...nd check again With units with drive motor FCM 300 please check the programming see section on programming of the FCM 300 below Flushing the system The Plug SprayTM units are protected from factory ag...

Page 8: ...als 1000 rpm 33 Hz for NPS 10 12 5 VS equals 1000 rpm 202 max output frequency 50 Hz equals 3000 rpm 85 Hz for NPS 10 12 5 equals 2400 rpm 215 Preset reference 1 Depends on application see description...

Page 9: ...ter housing and the used cartridge Attach the gaskets on both ends thin type to the new cartridge Insert the new cartridge Please be careful with the O ring in the filter housing Turn the filter house...

Page 10: ...l h 75 l h 100 l h Maxi mum flow at 100 bar 75 l h 100 l h 200 l h 300 l h 500 l h 750 l h 1000 l h 300 l h 450 l h 600 l h 1000 l h 1350 l h 1750 l h Motor type 0 55 kW 6 pole 0 75 kW 4 pole 1 5 kW 4...

Page 11: ...0 55 kW NPS 1 CS IEC 180N0671 Electric motor 0 75 kW NPS 2 CS IEC 180N0371 Electric motor 1 5 kW NPS 3 2 4 CS IEC 180N0021 Electric motor 2 2 kW NPS 6 3 CS IEC 180N0280 Electric motor 3 kW NPS 10 CS...

Page 12: ...12 521B0881 DKCFN PI 020 F1 02 Produced by Danfoss A S Danfoss Industri Service G1 Advertising 06 08 LN BPV E...

Reviews: