background image

1.4.3 Installing the NEMA 3R Cover

1.

Set the NEMA 3R cover over the top of the frequency
converter. Align the NEMA 3R cover with the screw
holes on the top mounting plate and the screw holes
on the side of the unit.

2.

Using the 6 screws provided in the bag, loosely
secure the cover to the frequency converter.

3.

Torque all 6 screws to 2.3 Nm (20 in/lbs).

4.

Apply adhesive label to the cover. See 

Illustration 1.5

.

NOTICE

REMOVING COVER

To remove the NEMA 3R cover after it has been installed,
remove the front 2 screws on the bottom of the unit. The
cover can be removed after the other 4 screws are loosened
since the cover has slotted screw openings.

1

Screw without captive washer

2

NEMA  3R  sticker

3

NEMA  3R  cover

4

Screws to remove for taking off the NEMA 3R cover

Illustration 1.5 Installing NEMA 3R Cover

1.4.4 Calculating Nominal Current when Using

a NEMA 3R Cover

The nominal current of a frequency converter with the NEMA
3R cover is 90% of its current rating. For example, in a
FC-302N250T5 standard IP54 frequency converter, the nominal
output current in normal overload mode is 588 A. With the
NEMA 3R cover, the normal overload current is 0.90 x 588 =
529.2 A. The same calculation is used to calculate the nominal
current for the high overload mode.

1.4.5 Derating for Ambient Temperature when

Using a NEMA 3R Cover

Using the NEMA 3R cover kit requires derating due to higher
ambient temperatures within the enclosure. Using SFAVM
(stator flux asynchronous vector modulation) gives greater
switching control, but generates more heat than using 60°
AVM (asynchronous vector modulation). SFAVM switches
throughout the entire cycle, where 60° AVM only switches 2/3
of the time.

The maximum switching frequency is 16 kHz for 60° AVM and
10 kHz for SFAVM. The discrete switching frequencies are
shown in 

Illustration 1.6

.

Installation Instructions

NEMA-3R Cover Kit for D1h–D2h
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

4

Danfoss A/S © 06/2015 All rights reserved.

MI70I102

Summary of Contents for NEMA-3R

Page 1: ...washers For NEMA 3R cover screws 6 without captive washers 1 2 Kit Part Numbers Part number Kit description 176F6302 NEMA 3R cover kit for D1h enclosures 176F6303 NEMA 3R cover kit for D2h enclosures...

Page 2: ...s are fully discharged Voltage V Frequency converter model Minimum waiting time minutes 3x400 N110 N315 20 N90K N250 20 3x690 N75K N400 20 N55K N315 20 Table 1 2 Discharge Time 1 4 Installation 1 4 1...

Page 3: ...g with the gasket side facing the opening See Illustration 1 4 4 Secure the new gland plate to the frequency converter using the provided screws with captive washers 6 for D1h or 8 for the D2h Torque...

Page 4: ...urrent of a frequency converter with the NEMA 3R cover is 90 of its current rating For example in a FC 302N250T5 standard IP54 frequency converter the nominal output current in normal overload mode is...

Page 5: ...llustration 1 6 Derating for Ambient Temperature Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 MI70I102 Danfoss A S 06 2015 All rights reserved...

Page 6: ...Illustration 1 7 Exterior Dimensions for D1h with NEMA 3R Kit Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 6 Danfoss A S 06 2015 All rights re...

Page 7: ...ation 1 8 Exterior Dimensions for D2h with NEMA 3R Kit Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 MI70I102 Danfoss A S 06 2015 All rights res...

Page 8: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Reviews: