1.4.2 Installing the Gland Plate
1.
Remove the existing gland plate and gasket from the
bottom of the frequency converter by removing 6
screws (T25) from the D1h or 8 screws (T25) from the
D2h. See
Illustration 1.3
.
2.
Make sure that the flange on the frequency converter
is smooth and clean in preparation for the new
gasket.
3.
Place the new gland plate over the opening, with the
gasket side facing the opening. See
Illustration 1.4
.
4.
Secure the new gland plate to the frequency
converter using the provided screws with captive
washers (6) for D1h or (8) for the D2h. Torque to 2.3
Nm (20 in/lbs).
1
Gasket
2
Screw with captive washer
3
Gland plate
Illustration 1.3 Removing Gland Plate
1
Gasket
2
Screw with captive washer
3
Gland plate
Illustration 1.4 Installing NEMA 3R Gland Plate
Installation Instructions
NEMA-3R Cover Kit for D1h–D2h
VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
MI70I102
Danfoss A/S © 06/2015 All rights reserved.
3