background image

Installation and service

Start-up

Vacuum pump-down and 
dehydration procedure

Leak detection

Before initial start-up or after a prolonged shut-
down period, energise the crankcase heater 12 
hours prior to start-up. If the crankcase heater 
cannot be energised long enough before start-
up, the compressor shall be heated in another 

way (for example with an electric heater or 
flood light) to boil off refrigerant from the oil. 
This is particulary important when ambient 
temperature is low at commissioning.

Moisture obstructs proper operation of the 
compressor and the rest of the refrigeration 
system. Air and moisture reduce service life, 
increase condensing pressure and cause 
excessively high discharge temperatures, 
which are capable of destroying the lubricating 
properties of the oil. Air and moisture also 
increase the risk of acid formation, thus giving 
rise to copper plating. All these phenomena 
can ultimately induce mechanical and electrical 
compressor failure. To eliminate these risks, it is 
recommended to perform the following vacuum 
pull-down procedure:
1. To the extent possible (i.e. if valves are 
present), the compressor must be kept isolated 
from the system.
2. After leak detection, the system must be 
pulled-down under a vacuum of 500 microns 
(0.67 mbar). A two-stage vacuum pump shall be 
used with a capacity appropriate for the system 
volume. It is recommended to use connection 
lines with a large diameter and to connect these 
lines to the service valves and not to the schrader 
connection, so as to avoid excessive pressure 
losses.
3. Once the vacuum level of 500 microns is 
reached, the system must be isolated from the 

vacuum pump. Wait 30 minutes during which 
time the system pressure should not rise. When 
the pressure rapidly increases, the system is 
not leak tight. Bring the system pressure up 
to atmospheric pressure with dry nitrogen or 
another suitable inert gas in order to reform 
a new leak detection. After repairing all leaks 
the vacuum pull-down procedure should be 
restarted from Step 1. When the pressure slowly 
increases, this indicates the presence of moisture. 
In this case Steps 2 and 3 should be repeated.
4. Connect the compressor to the system by 
means of opening the valves. Repeat Steps 2 & 3.
5. Break the vacuum with either nitrogen or the 
ultimate refrigerant.
6. Repeat Steps 2 and 3 on the total system.
Upon commissioning, the system moisture 
content may be as high as 100 ppm. During 
compressor operation, the filter drier must 
reduce this content to a level of 20 to 50 ppm.

 Do not use a megohmmeter or apply power 

to the compressor while it is under vacuum as 
this may cause motor winding damage, and 
never run the compressor under vacuum as this 
may cause the compressor motor to burnout.

Whenever possible the compressor must be kept 
isolated from the system during leak detection 
by closing the suction and discharge valves. Use 
a mixture of nitrogen and the final refrigerant 
(eg. R404A or R507A) and use a leak detector 
for the applied refrigerant. A spectrometric 
detection system using helium can also be 
applied. Note that leak detection with refrigerant 
may not be allowed in some countries. Do 
not use other gasses such as oxygen, dry 

air or acetylene as these gasses can form an 
inflammable mixture with the compressor oil. 
Never use CFC or HCFC refrigerants for leak 
detection of HFC systems. Leak detecting 
additives shall not be used as they may affect the 
lubricant properties. Warranty may be voided if 
leak detection additives have been used.

Eventual leaks shall be repaired respecting the 
instructions written above.

Refrigerant charging

It is recommended that charging be done to the 
high side of the system. Charge refrigerant as 
close as possible to the nominal system charge 
before starting the compressor. Then slowly 
add refrigerant on the low pressure side as far 
away as possible from the compressor suction 
connection. The refrigerant charge quantity 

must be suitable for both winter and summer 
operation. All zeotropic mixtures must be 
charged in the liquid phase. 

R

 When a liquid line solenoid valve is used, the 

vacuum in the low pressure side must be broken 
before applying power to the system.

AB245486497018en-000601

28

Application Guidelines

Summary of Contents for Maneurop NTZ

Page 1: ...Maneurop reciprocating compressors NTZ 50 60 Hz Group 2 R404A R507A R452A Group 1 R454C R455A Application guidelines http cc danfoss com...

Page 2: ......

Page 3: ...certificates 17 Pressure equipment directive 2014 68 EU 17 Low voltage directive 2014 35 EU 17 Machinery directive 2014 30 EU 17 Internal free volume 17 Operating conditions 18 Refrigerants and lubri...

Page 4: ...to avoid safety risk This icon indicates instructions to avoid reliability risk The purpose of this guideline is informational with the intent to educate customers as to how the compressors should pr...

Page 5: ...be operated at a return gas temperature suction gas temperature of 20 C even at low evaporating temperatures A liquid injection system is not required All components are of high quality and precision...

Page 6: ...conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K For full NTZ data details and capacity tables refer to selection software Coolselector 2 NT Z 4 L 048 A R1 B Motor voltage code Z Polyole...

Page 7: ...52 1 19 NTZ271 4 7090 6 64 9 65 1 07 8210 6 64 9 65 1 24 R452A Refrigeration Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K RGT 20 C Co...

Page 8: ...16 3 41 0 89 1177 1 25 3 11 0 94 Compressor model 50 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K 60 Hz EN12900 ratings To 35 C Tc 40 C SC 0K SH 10K Cooling capacity W Power input kW Current input...

Page 9: ...se heater 25 98 Schrader 1 4 263 333 353 NTZ068 1 Suction rotolock 1 1 4 Discharge rotolock 1 68 82 109 118 35 33 68 Suction 147 Discharge 142 159 17 17 123 39 Threaded oil sight glass 141 224 68 HM8...

Page 10: ...179 Discharge 176 252 288 413 32 Threaded oil sight glass Schrader 1 4 PTC crankcase heater 96 21 145 125 188 171 8 38 82 1 98 2 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisat...

Page 11: ...02 V04 352 518 117 155 232 99 Oil equalisation 3 8 Mounting hole for PTC crankcase heater 15 15 15 246 205 155 246 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 233 210 125 209 98 95 Threaded oil si...

Page 12: ...ral hours to reset and restart the compressor The trickle circuit provides the facility of heating the compressor crankcase by feeding a small current to the auxiliary winding and the run capacitor Se...

Page 13: ...ickle circuit IOL Motor protector A C Run capacitors B Start capacitor C Common S Start winding auxiliary R Run winding main IOL Motor protector A C Run capacitors B Start capacitor C Common S Start w...

Page 14: ...1 20 5 03 NTZ108 72 45 57 21 4 12 1 11 1 20 4 00 2 54 NTZ136 97 2 51 64 29 14 3 15 0 98 3 80 2 54 NTZ215 147 7 74 110 42 3 22 3 23 0 57 2 23 1 26 NTZ271 198 96 150 56 5 27 0 30 0 41 1 61 0 84 Three ph...

Page 15: ...Vavg V2 3 2 xVavg voltage unbalance x 100 Internal motor protection Voltage unbalance Motor protection Three phase compressors are internally protected by a temperature current sensing bimetallic pro...

Page 16: ...ts the settings must ensure that the compressor start up time is always less than 0 5 seconds In case of use with R454C or R455A make sure that the softstarter selected is compatible with A2L refriger...

Page 17: ...CC China Compulsory Product Certification Models with motor voltage code 4 5 NTZ271 4 is out of CCC scope EAC Eurasian conformity mark Models with motor voltage code 4 5 Approvals and certificates Pre...

Page 18: ...tions Danfoss recommends the use of these refrigerants with NTZ compressors Note that R404A has a small temperature glide It must therefore be charged in the liquid phase For most other aspects howeve...

Page 19: ...HFO Blend with similar thermodynamic properties to R404A R455A is a zeotropic refrigerant with a temperature glide of about 12K and must therefore be charged in liquid phase R455A is classified A2L wi...

Page 20: ...ollowing table A high pressure HP safety switch is required to shut down the compressor should the discharge pressure exceed the values shown in the table below This switch can be set at lower values...

Page 21: ...il in a refrigeration circuit is required to lubricate moving parts in the compressor During normal system operation small oil quantities will continuously leave the compressor with the discharge gas...

Page 22: ...condensing temperature and condensing pressure in air cooled condensors will decrease This low pressure may be insufficient to supply enough liquid refrigerant to the evaporator As a result the evapor...

Page 23: ...standstill and after pressure equalisation refrigerant will condensate in the coldest part of the system which may be the compressor when it is placed in a cold environment Ultimately the full system...

Page 24: ...e migration of refrigerant and proves effective if oil temperature is maintained 10 K above the saturated LP temperature of the refrigerant Tests must thereby be conducted to ensure that the appropria...

Page 25: ...y mounted to the base frame otherwise high vibration transmission would occur and the service life reduced Suction and discharge lines must have adequate flexibility in 3 planes Eventually vibration a...

Page 26: ...mpressor in an upright position during all handling tasks manipulating transport storage The angle off the vertical must not exceed 15 degrees System contamination is one of the main factors that affe...

Page 27: ...rge connection and the risk of an oil mist blow out via the suction connection will be minimal Whenever possible the compressor must be the last component to be integrated in the system It is advisabl...

Page 28: ...rom Step 1 When the pressure slowly increases this indicates the presence of moisture In this case Steps 2 and 3 should be repeated 4 Connect the compressor to the system by means of opening the valve...

Page 29: ...sulated on the discharge tube 10 cm far from the compressor body The maximum allowed discharge temperature is 135 C Power and current consumption shall be compared with the table values at measured ev...

Page 30: ...120F0291 120F0241 NTZ271 120F0292 120F0243 Compressor model Single pack Multi pack Industrial pack Weight kg Dimensions mm Qty Weight kg Dimensions mm Static stacking Qty Weight kg Dimensions mm Stat...

Page 31: ...8153122 Rotolock nut 1 Models with 1 rotolock connection Multipack 10 8153123 Rotolock nut 1 1 4 Models with 1 1 4 rotolock connection Multipack 10 8153124 Rotolock nut 1 3 4 Models with 1 3 4 rotoloc...

Page 32: ...PTC heater 27W All models Multipack 10 PTC27W 120Z0460 PTC heater 27W All models Industry pack 50 Type Code n Description Application Packaging Pack size CSR 7701021 Relay Capacitors run 15 10 F start...

Page 33: ...ting kit 2 cyl NTZ 096 108 Single pack 1 120Z0764 Mounting kit 2 cyl HP NTZ 136 3 4 9 Single pack 1 8156007 Mounting kit 4 cyl NTZ215 271 Single pack 1 Type Code n Description Application Packaging Pa...

Page 34: ...document The safety and reliability risk icons are added Page 8 Nominal performance data for R454C is added Page 16 Pressure equipment directive Refrigerant Group 1 is added Page 18 Operating conditi...

Page 35: ......

Page 36: ...d us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spread across three continents AB245486497018en 000601 Danfoss DCS CC 2021 06 Our...

Reviews: