background image

Instructions

2 | AN382129347378en-000101 - 8510306P01AB

© Danfoss | Climate Solutions | 2021.08

1 – Introduction

These instructions pertain to the LLZ scroll 
compressors used for refrigeration systems. They 
provide necessary information regarding safety 
and proper usage of this product.

2 – Handling and storage

 • 

 

Handle the compressor with care. Use the 
dedicated handles in the packaging. Use the 
compressor lifting lug and use appropriate and 
safe lifting equipment.

 •  Store and transport the compressor in an upright 

position.

 •  Store the compressor between -35°C and 70°C / 

-31°F and 158°F.

 •  Don’t expose the compressor and the packaging 

to rain or corrosive atmosphere.

3 – Safety measures before assembly

 Never use the compressor in a flammable 

atmosphere.
 •  Mount the compressor on a horizontal flat surface 

with less than 7° slope.

 •  Verify that the power supply corresponds to the 

compressor motor characteristics (see nameplate).

 •  When installing a compressor for R452A, R404A/

R507, R448A/R449A, use equipment specifically 
reserved for HFC refrigerants which was never 
used for CFC or HCFC refrigerants.

 •  

Use clean and dehydrated refrigeration-grade 
copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.
 •  The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

 •  The compressor must always be mounted with the 

rubber grommets supplied with the compressor.

4 – Assembly

 • 

 

Slowly release the nitrogen holding charge 
through discharge and suction ports.

 •  Connect the compressor to the system as soon as 

possible to avoid oil contamination from ambient 
moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Do not exceed the maximum tightening torque 

for rotolock connections

Rotolock connections

Tightening torque

1” Rotolock

80 Nm±10Nm

1” 1/4 Rotolock

90 Nm±10Nm

1” 3/4 Rotolock

110 Nm±10Nm

•  Connect the required safety and control devices. 

When the schrader port, if any, is used for this, 
remove the internal valve.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.
 •  Do not use leak detection dye.
 •  Perform a leak detection test on the complete 

system.

 •  The low side test pressure must not exceed 31 bar 

/450 psi.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.
 •  Connect a vacuum pump to both the LP & HP 

sides.

 • 

 

Pull down the system under a vacuum of 

 

500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.

 •  Do not use a megohmmeter nor apply power to 

the compressor while it is under vacuum as this 
may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.
 •  All electrical components must be selected as per 

local standards and compressor requirements.

 •  Refer to page 1 for electrical connections details. 

For three phase applications, the terminals are 
labeled T1, T2, and T3.

 •  Danfoss scroll compressors will only compress gas 

while rotating counter-clockwise (when viewed 
from the compressor top). Three-phase motors, 
however, will start and run in either direction, 
depending on the phase angles of the supplied 
power. Care must be taken during installation 
to ensure that the compressor operates in the 
correct direction.

 •  Use ø 4.8 mm / #10 - 32 screws and ¼” ring 

terminals for the power connection with ring 
connect screw terminal (C type). Fasten with 3 Nm 
torque.

 

• 

 

Use a self tapping screw to connect the 
compressor to earth.

8 – Filling the system

 •  Keep the compressor switched off.
 •  Keep the refrigerant charge below the indicated 

charge limits if possible. Above this limit; protect 
the compressor against liquid flood-back with a 
pump-down cycle or suction line accumulator.

 •  Never leave the filling cylinder connected to the 

circuit.

Compressor models

Refrigerant charge limit 

LLZ013-015-018

4.5 kg / 10 lb

LLZ024-034

7.2 kg / 16 lb

M

DGT

HPs

180 s

TH

LP

CONTROL CIRCUIT

F1

F1

KM

KM

KM

KA

KA

A1

A2

A3

KA

KA

KS

KS

KS

L1

L3

L2

Q1

T1

T3

T2

LLSV

KS

PM

Three phase (Wiring diagram with pump-down cycle)

Reviews: