Adjustment

See instruction printed on top of control

Note:
Remove lockplate before adjustment.
Replace lockplate after adjustment (if desired).

Setting

(se also “Wiring”)

KP 1A (auto. reset), KP 2A and KP 5A

KP 1A (manual reset ONLY)

Scale plate

Scale plate

1. Adjust range spindle to desired

1. Adjust range spindle to desired

HIGH SET POINT (HSP)

LOW SET POINT (LSP)

2. Adjust differential spindle to

2. DIFFERENTIAL is fixed.

desired DIFFERENTIAL (DIFF.)

Value printed on scale plate

Note:
KP 5A (manual reset) has fixed diff.
Value printed on scale plate.

HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT

LOW SET POINT plus DIFFERENTIAL equals HIGH SET POINT

Example:

Example:

HSP

DIFF.

=

LSP

LSP

+

DIFF.

=

HSP

30 psig

20 psi

=

10 psig

12 psig

+

10 psi

=

22 psig

(2.1 bar)

(1.4 bar)

(0.7 bar)

(0.8 bar)

(0.7 bar)

(1.5 bar)

10 psi (0.7 bar) / rev KP 1
7 psi (0.5 bar) / rev. KP 2

3 psi (0.2 bar) /  rev KP 1
1.5 psi (0.1 bar) /  rev. KP 2
4 psi (0.3 bar) / rev. KP 5