280

Adjustment spindle(s) location

Auto reset

Manual reset

KP 1A, 2A, 5A

KP 1A, 5A

Manual tripping

(Electrical contacts/wiring test)

TRIP (main lever)
use FINGERS ONLY!
(Do NOT use screwdriver)

Note:
KP 1A and KP 5A w/man. reset:
Push manual reset knob during manual
tripping.

Wiring

CAUTION: Disconnect power supply before
wiring connections are made to avoid
possible electrical shock or damage to
equipment.
All wiring should conform to the National
Electrical Code and local regulations.

Terminal block

CAUTION: Use terminal screws furnished
in the contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.

Contact load ratings

Load Option A

CUT-OUT on pressure drop
Wire terminals 1-4:
CUT-IN = High Set Point (HSP)
see “Setting”
CUT-OUT = Low Set Point (LSP)
see “Setting”

Terms 1-4 close on pressure rise
Terms 1-4 open on pressure drop

Example:

CUT-IN

= 30 psig

CUT-OUT = 10 psig

This means CUT-IN

= HSP = 30 psig

and

CUT-OUT = LSP = 10 psig

Note:



= Bellows movement on pressure rise

Ø

= Bellows movement on pressure drop

The free terminal can be used for signal
purpose.

Load Option B

CUT-OUT on pressure rise
Wire terminals 1-2:
CUT-IN = Low Set Point (LSP)
see “Setting”
CUT-OUT = High Set Point (HSP)
see “Setting”

Terms 1-2 close on pressure drop
Terms 1-2 open on pressure rise

Example:

CUT-IN

= 250 psig

CUT-OUT = 350 psig

This means CUT-IN

= LSP = 250 psig

and

CUT-OUT = HSP = 350 psig

120 V a.c.

16 FLA, 96 LRA

240 V a.c.

  8 FLA, 48 LRA

240 V d.c.

12 W pilot duty

Manual reset

To resume control operation after safety
cutout, push reset knob as indicated.

Note:
KP 1A, man. reset is possible only after a
pressure rise of 10 psi (0.7 bar).
KP 5A, man. reset is possible only after a
pressure drop of 43 psi (3.0 bar).

Bellows

Bellows

Diff.

(fixed)

KP 1A:

10 psi (0.7 bar

KP 5A:

43 psi (3 bar)