Adjustment
Note:
Remove lockplate before adjustment.
Replace lockplate after adjustment (if desired).
1.
Adjust range spindle
to desired CUT-IN value.
2.
Adjust differential spindle to desired
DIFFERENTIAL (DIFF.) value.
CUT-IN minus DIFFERENTIAL
equals CUT-OUT
Example:
Example:
Example:
CUT-IN equals CUT-OUT plus
DIFFERENTIAL
CUT-OUT minus DIFFERENTIAL
equals CUT-IN
1.
Adjust range spindle
to desired CUT-IN value.
2.
DIFFRENTIAL (DIFF.) is fixed.
Value printed on scale plate.
1.
Adjust range spindle
to desired CUT-OUT value.
2.
DIFFRENTIAL (DIFF.) is fixed.
Value printed on scale plate.
CUT-IN – DIFF. = CUT-OUT
30 psig – 10 psi = 20 psig
(2.1 bar)
(0.7 bar)
(1.4 bar)
CUT-OUT + DIFF. = CUT-IN
12 psig + 10 psi = 22 psig
(0.8 bar)
(0.7 bar)
(1.5 bar)
CUT-OUT – DIFF. = CUT-IN
203 psig – 58 psi = 145 psig
(14 bar)
(4 bar)
(10 bar)
LP range
LP differential
HP range
Increase
360
°
Decrease
360
°
Increase
360
°
Decrease
360
°
Decrease
360
°
Increase
360
°
10 psi
(0.7 bar)
/rev.
2 psi
(0.15 bar)
/rev.
33 psi
(2.3 bar)
/rev.
15
/
64
in.
(6 mm)
Low pressure (LP) side setting
High pressure (HP) side setting
Setting
KP 15A with LP auto. reset only
KP 15 A with HP auto./man. reset
KP 15A with LP man. reset only
KP 15A with convertible LP auto./man. reset
LP scale
LP scale
HP scale
Lockplate