Danfoss KP 15A Installation Manual Download Page 1

060-007866

Installation Guide

Pressure Control

Type KP 15A

© Danfoss A/S (AC-MCI / jmn), 2012-11 

DKRCI.PI.C00.C1.22 / 520H6064 

1

06

0R

975

2

06

0R

975

2

Refrigerants 

CAUTION:

Do not mount the control in a position where 

dirt, sediment or oil will affect the operation of the control.

t

1

 min .:  -40 °F (-40 °C)

t

1

 max.:    65 °C (149 °F)

Ambient temperatures / Mounting requirements

Test pressure (P

test

)

Connections

Mounting

R717, HCFC and non-flammable HFC

Cutting ring

p

test 

max.  

20 bar (285 psig)

PS/MWP

p

test 

max. 

35 bar (510 psig)

PS/MWP

Summary of Contents for KP 15A

Page 1: ...nts CAUTION Do not mount the control in a position where dirt sediment or oil will affect the operation of the control t1 min 40 F 40 C t1 max 65 C 149 F Ambient temperatures Mounting requirements Test pressure Ptest Connections Mounting R717 HCFC and non flammable HFC Cutting ring ptest max 20 bar 285 psig PS MWP ptest max 35 bar 510 psig PS MWP ...

Page 2: ...ee label for current wiring inside cover CAUTION Use terminal screws furnished in the contact block Use tightening torque 20 lb in 2 3 Nm Use copper wire only Low pressure LP side A C close on LP rise A C open on LP drop High pressure HP side A C open on HP rise A C close on HP drop LP signal option A B close on LP drop HP signal option A D close on HP rise Contact load ratings See label inside co...

Page 3: ... LP man reset is possible only after system pressure has risen above cut in value HP man reset is possible only after system pressure has dropped below cut out value Manual reset Convertible reset Note Do not select automatic reset if safety of the system requires manual reset Note Selected reset configuration may be protected against unauthorized actions applying a seal Insert a screwdriver into ...

Page 4: ... plate 1 Adjust range spindle to desired CUT OUT value 2 DIFFRENTIAL DIFF is fixed Value printed on scale plate CUT IN DIFF CUT OUT 30 psig 10 psi 20 psig 2 1 bar 0 7 bar 1 4 bar CUT OUT DIFF CUT IN 12 psig 10 psi 22 psig 0 8 bar 0 7 bar 1 5 bar CUT OUT DIFF CUT IN 203 psig 58 psi 145 psig 14 bar 4 bar 10 bar LP range LP differential HP range Increase 360 Decrease 360 Increase 360 Decrease 360 Dec...