Inputs – Sensor Power

The status of sensor power input on the connector and pin C1p06 is described.

Signal

Type

Direction

Range

Description

C1p06_SnsrPwr

Bus

——

——

AnIn U16

Input

0 – 32767

Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.

Volt U16

Input

0 – 10000

Analog input voltage
100 is 100 mV.

Updated BOOL

Input

——

True when the AnIn and Volt signals are refreshed.

Inputs – Multifunction Inputs

The status of multifunction inputs on the connectors and pins C1p08, C1p09, and C1p10 is described.

Signal

Type

Direction

Range

Description

Pin _MFIn

Bus

——

——

Config

Bus

——

——

PinConfig0 U16

Output

0 – 3

Determines how the input pin is internally connected.
0: Activated with 5 V or Supply Voltage. The internal Pull Down and Pull Up
resistors are disabled.
1: Activated with Ground. The internal Pull Up resistor is connected to an internal
5 V. The internal Pull Down resistor is disabled.
2: Activated with 5 V or Supply Voltage. The internal Pull Up resistor is disabled.
The internal Pull Down resistor is connected to Ground.
3: Activated with Supply Voltage. The internal Pull Up resistor is connected to an
internal 5 V. The internal Pull Down resistor is connected to Ground.

PinConfig1 U16

Output

0 – 3

Sets the maximum input voltage to allow maximum possible input resolution.
0: 0 – 5.753 V
1: 0 – 0.448 V
2: 0 – 37.4 V
3: 0 – ~2.918 V (not recommended)

PinConfig1 U16

Output

0 – 3

Sets the maximum input voltage to allow maximum possible input resolution.
0: 0 – 5.26 V
1: 0 – 0.3675 V
2: 0 – 35.3 V
3: 0 – ~2.465 V (not recommended)

DigInConfigHigh

U16

Output

0 – 65535

DigInConfigHigh is the voltage level required for DigIn to transition from false to
true.
100 is 100 mV.

DigInConfigLow U16

Output

0 – 65535

DigInConfigLow is the voltage level required for DigIn to transition from true to
false.
100 is 100 mV.

DigIn

BOOL

Input

——

Digital input state according to PinConfig0DigInConfigHigh and
DigInConfigLow.

AnIn

U16

Input

0 – 32767

Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.

Volt

U16

Input

0 – 37400

Analog input voltage.
The actual maximum value is determined by PinConfig1.
100 is 100 mV.

Freq

U16

Input

0 – 35300

Input Signal Frequency
100 is 100 Hz.

User Manual

PLUS+1® Compliant IX012-010 Function Block

IX012-010 Function Block

 

6 | 

©

 Danfoss | July 2018

11063398 | AQ00000107en-US0101

Summary of Contents for IX012-010

Page 1: ...User Manual PLUS 1 Compliant IX012 010 Function Block www danfoss com...

Page 2: ...Revision history Table of revisions Date Changed Rev July 2018 Rebranding 0101 June 2009 AA User Manual PLUS 1 Compliant IX012 010 Function Block 2 Danfoss July 2018 11063398 AQ00000107en US0101...

Page 3: ...s and Signal Overview 8 Configuring Communications 9 Variable Addressing Mode 9 Predefined Addressing Mode 9 Fixed Addressing Mode 9 Volatile Parameters 9 Non Volatile Parameters 10 Timing Configurati...

Page 4: ...e The CAN messages use 11 bit identifiers in this mode 2 Fixed ID addressing mode The I O module Tx and Rx message identifiers are determined directly by setting Tx ID and Rx ID The CAN messages use e...

Page 5: ...ines how often the Power Sensor Power and CAN Shield input values are transmitted from the I O module 1000 is 1 ms RepTime_DigAn_In U16 0 65535 Determines how often the DigIn and AnIn values are trans...

Page 6: ...h Supply Voltage The internal Pull Up resistor is connected to an internal 5 V The internal Pull Down resistor is connected to Ground PinConfig1 U16 Output 0 3 Sets the maximum input voltage to allow...

Page 7: ...ear in both the Input and Output buses Signal Type Direction Range Description CAN Bus CommStatus U16 Input 1 8 255 Current status of communication with the I O module 0 CAN message transmission is di...

Page 8: ...on block requires I O module hardware using protocol version 2 00 to 2 99 ProtocolVersion U16 Input 0 65535 I O communication protocol version used by the I O module hardware 200 is version 2 00 Conne...

Page 9: ...module In this mode the I O module reads the N1 value stored in non volatile memory EEPROM Because the function block and the I O module use different default addressing modes as long as the N1 value...

Page 10: ...ion on a CAN bus Use the PLUS 1 CG150 USB CAN gateway and CANKing software to view CAN bus loads PLUS 1 I O modules communicate with their associated controllers over a CAN bus System developers can a...

Page 11: ...nfigured but a second I O module has a similar configuration Review configuration and make changes to the other I O modules Incompat_Protocl is true The firmware on the I O module uses a version of th...

Page 12: ...lutions ApS Nordborgvej 81 DK 6430 Nordborg Denmark Phone 45 7488 2222 Danfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading S...

Reviews: