Input
Type
Range
Description
Enbl_RecheckCRC
BOOL
——
Determines if the I/O module CRC is periodically checked to ensure the device’s
configuration matches the function block’s configuration.
T: The CRC is requested from the I/O module and compared every 5 seconds.
F: The CRC is only requested from the I/O module during initialization.
Enbl_ResetTest
BOOL
——
Determines if the I/O module volatile memory is periodically checked to ensure
the device has not lost volatile configuration information due to temporary loss
of power.
T: Volatile information is requested from the I/O module and compared every 1
second.
F: Volatile memory is not checked after initialization and temporary loss of
power to the I/O module may go undetected.
BusRecvryTm
U16
0–65535
BusRecvryTm sets the time the I/O module CAN port waits after going into a
“bus off” condition before attempting to go back on the bus.
1000 is 1 ms.
DriverRecvryTm
U16
0–65535
DriverRecvryTm sets the time the I/O module CAN port waits after a CAN error
causes the driver to reset before attempting to go back on the bus.
1000 is 1 ms.
RepTime_Supply
U16
0–65535
Determines how often the Power, Sensor Power, and CAN Shield input values
are transmitted from the I/O module.
1000 is 1 ms.
RepTime_DigAn_In
U16
0–65535
Determines how often the DigIn and AnIn values are transmitted from the I/O
module.
1000 is 1 ms.
RepTime_MF_In
U16
0–65535
Determines how often the MFIn values are transmitted from the I/O module.
1000 is 1 ms.
Inputs – Power Supply
The status of power supply input on the connector and pin C1p02 is described.
Signal
Type
Direction
Range
Description
C1p02_Pwr
Bus
——
——
AnIn U16
Input
0 – 32767
Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.
Volt U16
Input
0 – 55015
Analog input voltage
100 is 100 mV.
Updated BOOL
Input
——
True when the AnIn and Volt signals are refreshed.
Inputs – CAN Shield
The status of analog and CAN0 shield inputs on the connector and pin C1p05 is described.
Signal
Type
Direction
Range
Description
C1p05_AnIn
Bus
——
——
AnIn U16
Input
0 – 32767
Analog input AD count.
Due to CAN message optimization, this value is approximated by scaling the Volt
signal.
Volt U16
Input
0 – 5753
Analog input voltage
100 is 100 mV.
Updated BOOL
Input
——
True when the AnIn and Volt signals are refreshed.