Table 03
Procedure to isolate IPS for servicing
Multipoint
Single point purging from receiver
1
Close all supply lines from the purge points of the ammonia
system.
Do not close any stop valve between IPS 8 and float valve
Restart the controller to force pump-down
2
Restart the controller to force pump-down
Wait 20 minutes
3
Wait 20 minutes
4
Stop the compressor by turning the compressor switch QM1 to
the off position
Stop the compressor by turning the compressor switch QM1 to
the off position
5
Close the SVA shut-off valve in the drain line (located under
the IPS 8)
Close the SVA shut-off valve in the drain line (located under
the IPS 8)
6
Release the remaining system pressure to atmosphere
by opening the SNV drain valve. This can also be done by
attaching a permanent magnet on the AKVA 10 valve for forced
opening
Release the remaining system pressure to atmosphere
by opening the SNV drain valve. This can also be done by
attaching a permanent magnet on the AKVA 10 valve for forced
opening
Disposal of the IPS 8
If an IPS 8 unit is worn out and has to be replaced,
the disposal must be done in accordance with
national legislation and only done by competent
personnel.
Table 04
ALARMS
Description
Troubleshooting
A01
General alarm
Missing feedback on DI3. Leads to shut down of IPS 8
No feedback from the relays; Compressor, air fan or condenser fan
E10
System is OFF
Indicates status o the main switch
-
E14
Liquid alarm
Signal from the LLS that there is liquid in the evaporator
LLS 4000 feedback
E13
Compressor EROR
Indicates no status is being received from KL01
We are missing status feedback of compressor from KL1 relay, for
example we have PHS switch so if pressure is high (24 bar's).
E01
Temp Sensor Fault
Indicates no signal from temperature sensor
Cable is cut, or sensor is missing. Check connection.
E16
Discharge sensor error
Indicates no signal from temperature sensor
Cable is cut, or sensor is missing. Check connection.
E17
Suction sensor error
Indicates no signal from temperature sensor
Cable is cut, or sensor is missing. Check connection.
E02
BPL Sensor Fault
Indicates no signal from pressure sensor (R452a)
Cable is cut, or sensor is missing. Check connection.
E03
BPH Sensor Fault
Indicates no signal from pressure sensor (R717)
Cable is cut, or sensor is missing. Check connection.
E04
Low temperature
Indicates too low ambient temperature (<-50°C)
Readings are out from working limits of sensor
E05
Hi temperature
Indicates too high ambient temperature (>120°C)
Discharge line is too hot, check that condensing fun is working.
E06
Low pressure BPL
Indicates too low R452a pressure
Factory setting 0.3 bar, we can have several problems: a) Restrictor
is blocked (clean it). b) Wrong piping and as addition ammonia is
draining, so check piping's. c) Check SV float.
E07
Hi pressure BPL
Indicates too high R452a pressure
a) Expansion valve is not working
b) to high ambient temperature (24 bar's /54 C)
E08
Low pressure BPH
Indicates too low R717 pressure
Purge points are blocked, or flange is blocked with rubber plug.
E09
Hi pressure BPH
Indicates too high R717 pressure
Pressure is 24 bars.
E11
Memory is full
A memory reset is required
Need to restart IPS, and clean memory
E15
Memory wrong!
Wrong counter values. The unit will automatically repair itself
If you change timers CST or PLT, you need to stop IPS by using M/S,
else one of timers will fail and count wrong
E12
Total purge time error
This occurs when PLT is activated. System will automatically restart
when CST has expired
If IPS is running on one point more than PLT (24 hours F.S.), IPS
will be pushed to next point, Alarm will be active for CSTM (CST /
n-points). For example if we have 8 points, then CSTM is 135 min, so
after 135-minute IPS will start compressor.