background image

H1F output speed

Start and low speed stability. The motor produces maximum starting torque at maximum
displacement. Stable operation can be achieved at 15–34 rpm, ± 5 %, depending on system pressure, in
applications that require low speed stability. Motor output speed becomes more stable as speed
increases.
Rated speed is the highest output speed recommended at full power condition. Operating at, or below
this speed will yield satisfactory product life. Do not exceed rated speed in open circuit applications.
Maximum speed is the highest operating speed permitted. Exceeding maximum speed reduces the
product life and can cause loss of hydrostatic power and dynamic braking capacity. Never exceed the
maximum speed limit under any operating conditions.

Operation between rated and maximum speed is reserved for intermittent operation (see

H1F Operating

Parameters

 on page 11 ) not to exceed 10 minutes durations, 2% of duty cycle based load-life, and 310

bar system delta pressure. Speed above rated are anticipated to occur during downhill braking (negative
power). Contact factory for any operation above Rated speed when negative power is not involved.

During hydraulic braking and downhill conditions, the prime mover must be capable of providing
sufficient braking torque in order to avoid pump over speed. This is especially important to consider for
turbocharged and Tier 4 engines.

W

Warning

Unintended vehicle or machine movement hazard.
Exceeding maximum speed may cause a loss of hydrostatic drive line power and braking capacity. You
must provide a braking system, redundant to the hydrostatic transmission, sufficient to stop and hold the
vehicle or machine in the event of hydrostatic drive power loss. The braking system must also be
sufficient to hold the machine in place when full power is applied.

H1F system pressure

System pressure is the differential pressure between high pressure system ports. It is the dominant
operating variable affecting hydraulic unit life. High system pressure, which results from high load,
reduces expected life. Hydraulic unit life depends on the speed and normal operating, or weighted
average, pressure that can only be determined from a duty cycle analysis.
Application pressure is the high pressure relief or pressure limiter setting normally defined within the
order code of the pump. This is the applied system pressure at which the driveline generates the
maximum calculated pull or torque in the application.
Maximum working pressure is the highest recommended application pressure. Maximum working
pressure is not intended to be a continuous pressure. Propel systems with application pressures at, or
below, this pressure should yield satisfactory unit life given proper component sizing.
Maximum pressure is the highest allowable application pressure under any circumstance. For
applications which are above the maximum working pressure, please contact Danfoss
Minimum pressure must be maintained under all operating conditions to avoid cavitation.

All pressure limits are differential pressures referenced to low loop (charge) pressure. Subtract the low

loop gauge pressure from the high loop gauge pressure readings to compute the differential.

Summing pressure is the sum of both the low and high loop pressures. Summing pressure above 30 bar
[435 psi] guarantees reliable use within the rated speed.

Case pressure

Under normal operating conditions, the rated case pressure must not be exceeded. During cold start,
case pressure must be kept below maximum intermittent case pressure. Size drain plumbing accordingly.

Service Manual

H1F Bent Axis Fixed Displacement Motors, Size 080

Operating parameters

 

©

 Danfoss | December 2023

AX465363259664en-000102 | 17

Summary of Contents for H1F 080

Page 1: ...Service Manual H1F 080 H1F Bent Axis Fixed Displacement Motor www danfoss com...

Page 2: ...visions Date Changed Rev December 2023 Updated title 0102 November 2023 First edition and next various changes 0101 Service Manual H1F Bent Axis Fixed Displacement Motors Size 080 2 Danfoss December 2...

Page 3: ...arameters H1F output speed 17 H1F system pressure 17 Case pressure 17 External shaft seal pressure 18 Temperature 18 Fluid and filter maintenance Fluid and filter recommendations 19 Pressure measureme...

Page 4: ...bly 29 H1F Loop Flushing Charge Relief Removal 29 Torque chart H1F Fasteners plugs with torque chart 30 Service Manual H1F Bent Axis Fixed Displacement Motors Size 080 Contents 4 Danfoss December 2023...

Page 5: ...ware that hydraulic fluid may be under high pressure and or hot Inspect the outside of the motor and fittings for damage Cap hoses after removal to prevent contamination Keep it clean Cleanliness is a...

Page 6: ...re in the system before removing hoses fittings gauges or components Never use your hand or any other body part to check for leaks in a pressurized line Seek medical attention immediately if you are c...

Page 7: ...and transport modes i e wheel loader mobile crane drill rigs winches harvestors SAE Cartridge and DIN flange with radial or axial high pressure port configurations are available Loop flushing is also...

Page 8: ...EDC 4 Charge Pump 5 Charge Check High Pressure Relief Valve 6 Loop Flushing Valve 7 Pressure Limiter Valve 8 Charge Pressure Relief Valve 9 Servo Cylinder 10 Charge Pressure Filter 11 Heat Exchanger 1...

Page 9: ...schematic above shows the function of a hydrostatic transmission using an H1 axial variable displacement pump with electric proportional displacement control EDC and an H1 fixed displacement motor wit...

Page 10: ...l at rated speed l min US gal min 320 84 5 at max speed 400 105 7 Theoretical torque at max displacement N m bar lb in 1000 psi 1 27 777 Theor corner power at rated speed and max working pressure p 45...

Page 11: ...psi Max delta 480 bar 6962 psi Max abs 510 bar 7397 psi Min low loop 7 5 bar 109 psi Case pressure Rated 3 bar 44 psi Maximum 5 bar 73 psi Minimum 0 3 bar 4 psi Ambient temperature1 Maximum 70 C 158...

Page 12: ...the oil to drain down and be replaced with air in the rotating group The minimum pressure in the inlet port and the outlet port must be equal or higher as shown in the tables H1F Required inlet press...

Page 13: ...g n 1000 v Qe Vg p mh 20 Me Qe p t 600 Me n 9550 Pe n Qe 1000 v Vg Vg n 231 v Qe Vg p mh 2 Me Vg n p t 396 000 P e n Qe 231 v Vg Where Qe Input flow l min Me Output torque N m Pe Output power kW n Spe...

Page 14: ...e system pressure to flow to the loop flushing relief valve Legend A System loop A B System loop B LFRV to loop flushing relief valve P003 437 A B L2 W Warning Unintended vehicle or machine movement h...

Page 15: ...ith a cracking pressure of 16 bar 232 psi Valves are available with several orifice sizes to meet the flushing flow requirements of all system operating conditions A loop flushing defeat option is ava...

Page 16: ...al Information BC152886482203 H1F speed sensor position Sensor position in cartridge housing Cartridge housing H1F Target Ring Speed target rings vary according to the diameter of the cylinder block o...

Page 17: ...nt to hold the machine in place when full power is applied H1F system pressure System pressure is the differential pressure between high pressure system ports It is the dominant operating variable aff...

Page 18: ...ttest point in the transmission which is normally the motor case drain The system should generally be run at or below the published rated temperature The maximum intermittent temperature is based on m...

Page 19: ...st fluid change occur at 500 hours of operation Change the fluid more frequently if it becomes contaminated with foreign matter dirt water grease etc or if the fluid is subjected to temperature levels...

Page 20: ...ap System split flange boss ports A B Code 62 per ISO 6162 Type 1 Port Size 080 A B 1 in Thread M12 x 1 75 min 24 mm 0 94 in Ports and gauge Information Port Size 080 Pressure obtained L1 L2 M22 x 1 5...

Page 21: ...ar 0 1000 psi pressure gauge in the charge pressure gauge port of the pump to monitor the charge pressure during start up For open circuit systems use gauges in system ports 8 Disconnect any external...

Page 22: ...cycle slowly between forward and reverse for at least five minutes 18 Shut down prime mover 19 Remove gauges Replace plugs at the gauge ports 20 Check reservoir level Add filtered fluid if needed The...

Page 23: ...hing flow Restricted orifice in loop flushing cartridge reduces flow Measure case drain flow Clean or replace orifice cartridge 4 Loop flushing shuttle Loop flushing shuttle may be sticking in one dir...

Page 24: ...leakage Excess internal leakage may cause lower charge pressure and affect motor performance including output speed Install loop flushing defeat option and measure case flow If case flow is excessive...

Page 25: ...and grime 2 If removing the motor tag each hydraulic line connected to the motor If you disconnect hydraulic lines plug each open port to keep dirt and contamination out of the motor 3 Inspect the sys...

Page 26: ...4 Cover the shaft splines with shaft cover or packing tape to avoid damaging the seal during installation 5 Install front cover G0025 into housing G0010 6 Using snap pliers install retaining ring G00...

Page 27: ...mm 0 2 in 45 5 15 mm 100 mm 3 94 in 69 mm 2 6 in 58 mm 2 3 in 0 10 0 0 0 20 in 0 004 0 0 150 mm 5 90 in 70 mm 2 76 in 5 mm 0 2 in 45 5 4 mm 100 mm 3 94 in 56 mm 2 2 in 48 mm 1 9 in 0 10 0 0 0 21 in 0...

Page 28: ...H1F speed sensor reassembly Speed sensor assembly J0020 J0010 J0041 1 Lubricate and install new O ring J0041 2 Install speed sensor J0010 3 Install screw J0020 using a 5 mm internal hex wrench with t...

Page 29: ...hing reassembly K0040 QK040 K0010 K0050 QK050 1 Lubricate and install spool K0010 2 Lubricate and install springs K0020 3 Lubricate and install new O rings QK040 QK050 4 Install plugs K0040 K0050 usin...

Page 30: ...nd torque chart Options Frame size Description Wrench size Torque J0020 80 Speed sensor screw 5 mm internal hex 8 N m 6 lbf ft F0120 80 Endcap screw 10 mm internal hex 111 N m 82 lbf ft Plug size and...

Page 31: ...foss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading Shanghai Co Ltd Building 22 No 1000 Jin Hai Rd Jin Qiao Pudong New District...

Reviews: