4
Installation Guide
GreenCon RC-T2/T4
GB
VIE2D22P
Danfoss Heating Solutions
3. Error codes
Display
Description
E1
Alarming for short circuit of
sensor
EE
EEPROM chip error
Lo
Indicating temperature lower
than 0°C
Hi
Indicating temperature
higher than 50°C
4. Notes
1. Correct wiring is essential; using instrument to con-
firm L and N before wiring is recommended.
2. Don’t remove too much of the insulation cover from
the wire to avoid short circuit caused by the naked
wire touching the metal 86 size mounting wall box.
3. Don’t let the screw press or touch the wire when
using screw to fix room thermostat in wall box. A
short-circuit risk exists if the wire insulation cover is
damaged by the screw, and if the naked wire con-
nects with the screw.
4. If walls must be painted, mount the room thermostat
after painting, to avoid dust or paint material pen-
etrating the room thermostat and thus damaging
the PCB.
5. The max load of relay is 3 A (resistive) or 1 A (induc-
Summary of Contents for GreenCon RC-T2