5

If no signal is received from one or more thermostats, the corresponding 
LEDs on the indicator panel remain lit. 
When the required number of thermostats have been checked, press and 
hold “MODE” for 3 seconds to return the system to normal mode. 

Note: 

The system returns automatically to normal mode if no buttons are 

pressed during a 15-minute period. 

5.3 Thermostat test mode 

This mode is used to test thermostat transmission. 
Using the point of a pencil or similar, press and hold the transmission button 
on the front of the thermostat for 3 seconds. 
This  forces  the  thermostat  to  transmit  a  signal  every  7  seconds  for  5-6 
minutes. 

Then check whether a signal from the thermostat is received by the base 
unit at 7 second intervals (the LED indicator for the assigned channel flashes 
on receiving a signal). 
The test can be terminated by again pressing the thermostat transmission 
button. 

Note: 

The system returns automatically to normal mode if no buttons are 

pressed during a 5-minute period.
 

5.4 Thermal actuator output testing 

Thermal actuator output testing is used to check the functioning of the base 
unit output relays. 
Press and hold the “MODE” button for 3 seconds (all LED indicators flash).
 
The first indicator then begins flashing. 
Press “OK” to test the first channel. The LED indicator now flashes rapidly 
(on/off at half-second intervals) and a small click can be heard after about 5 
seconds indicating that the output has been activated. Press “OK” again to 
de-activate the output. 
Press “MODE” to select the next output to be tested, and repeat the process 
described above. 
The test can be terminated by pressing and holding the “MODE” button for 
3 seconds. 

Note: 

The system returns automatically to normal mode if no buttons are 

pressed during a 10-minute period. 

5.5 Alarm function 

This function is initiated automatically in case of communication failure. 
If the base unit does not receive a signal from a registered thermostat for 2 
hours, the corresponding LED indicator starts flashing. Simultaneously, the 
thermal actuator output begins a continuous cycle of 7 minutes’ activation 
and 14 minutes’ de-activation. 

If after a further 8 hours the base unit has still not received a signal from the 
thermostat, an acoustic alarm begins buzzing. The buzzer can be de-activated 
by selecting the alarm “OFF” setting on the base unit (see Fig. 9). The alarm 
is reset when a button on the control panel is pressed or when the base unit 
receives a signal from the thermostat. 

5.6 Thermal actuator & pump exercise 

This  function  prevents  the  manifold  valve  and  circulating  pump  from 
sticking. 
It  is  activated  once  yearly.  First,  all  assigned  outputs  are  activated  for  5 
minutes, and the pump output is then activated for 5 minutes (only if pump 
output is installed). 
The function can be turned off by switching the EXERCISE switch to the OFF 
position. (See Fig. 10). 

5.7 NO/NC thermal actuator settings 

This function allows “Normally Closed’ (N/C) or “Normally Open” (N/O) thermal 
actuators to be used. 
Type is selected on the ACTUATOR switch (see Fig. 10). 

5.8 “Cooling” mode 

This mode allows thermostat signals to be inverted so that outputs are opened 
when the temperature is above the desired temperature and closed when 
below and is intended for use in cooling systems. 

6.0  Boiler and pump interlock setting

As standard, outputs 7 and 8 are set to control thermal actuators. 
However, output 7 can also be used to control a boiler via an ON/OFF signal, 
and output 8 can be used to control a pump. 
To enable a boiler or pump to be controlled, the system must be configured 
as shown in Figs 8 and 9 respectively. 

Note: 

If outputs 7 and 8 are not used for thermal actuators, the following 

applies: 
- LED indicators 7 and 8 light up when any other channel requires heat.

Fig. 7. Switches

Fig. 9. Step 2. Bend left-hand jumper as illustrated. 