background image

3

3.0 Installation instructions 

The system should be installed by a competent person in the following 
sequence. 

3.1 Base unit 

Install the base unit first. Mount the base unit above the distribution manifold 
either direct on the wall or inside a wooden or metal distribution cabinet. 
Ensure that the base unit is mounted horizontally, that there is easy access 
to the control panel and thermal actuator connections, and that the base 
unit cover can be easily removed. Fix the base unit to the wall using two 
screws. 

The base unit must be connected to a 230 volt supply via a double pole switch 
socket outlet. If it is installed in a metal distribution cabinet, an aerial should 
be installed outside the cabinet in order to improve radio communication. 

3.2 Thermostat installation

Thermostats should be mounted on an internal wall at a height of 1.2-1.5 
metres above the floor, using screws and fixings.  
Thermostats must not be placed on an external wall or near heat sources 
such as television and stereo sets, ovens or similar. Thermostats should not 
normally be placed where they can be affected by direct sunshine. In rooms 
that are very humid or damp, e.g. bathrooms, thermostats must be placed 
as far from moisture sources as possible. 

3.3 Pre-installation 

Thermostats must be registered in the base unit before being placed in 
individual rooms. 
When registering thermostats, it is important that the room in which they are 
to be placed is written or marked on the rear of the thermostat. Thermostats 
can then be registered in turn. 
The channels to be used for individual rooms must therefore be decided 
in advance. 

Note: 

refer to section 4.3 for registration instructions

Fig. 2a. Thermostat location 

Fig. 2b. Thermostat installation 

4.0  Operating instructions

4.1  Thermal actuator installation 

1.

 

Ensure that the power supply to the base unit is disconnected. 

2. 

Lift base unit cover after loosening front screws. 

3. 

Remove internal aerial. 

4. 

Remove blue thermal actuator terminals from printed circuit  
 board. 

5. 

Connect thermal actuator cables. 

6. 

Reattach thermal actuator terminals in assigned order to printed circuit 
board. 

7. 

Position cables in strain-relief cable glands (see Fig 3). 

8. 

Replace internal aerial. 

9. 

Close base unit and tighten front screws 

Fig. 3. Push cable through cable gland. 

4.2 Base unit installation 

Once the base unit has been mounted on the wall, all thermal actuators 
have been connected and any connections for pump and boiler control 
have been made, the thermostats can be registered. First, power up the 
base unit. The green ‘Power’ LED lights up. 

Fig. 4. Control panel. LED indicators 1-8 and ‘Power’ LED. 

Ca. 1,5m 

Power

1 2 3 4 5 6 7 8

Mode

OK

Reviews: