6-46 Term. X30/12 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10.000
s]
A 1
st
order digital low pass filter time
constant for suppressing electrical noise
on terminal X30/12.
6-46 Term. X30/12 Filter Time Constant
cannot be changed while the motor is
running.
3.8.6 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog
output 1, i.e., Terminal 42. Analog outputs are current
outputs: 0/4 – 20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection. Resolution
on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog
current output. Depending on the selection
the output is either a 0–20 mA or 4–20 mA
output. The current value can be read out in
[0]
*
No
operation
When no signal on the analog output.
[52]
MCO
0-20mA
[53]
MCO
4-20mA
[100] Output
frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference
[Min - Max] 0% = 0 mA;
100% = 20 mA
mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback
[103] Motor
current
Value is taken from
Inverter max. current (160% current) is equal to
20 mA.
Example: Inverter norm current (15 hp [11 kW])
= 24 A. 160% = 38.4 A. Motor norm current =
22 A Readout 11.46 mA.
20
mA x 22 A
38.4
A
= 11.46
mA
If the norm motor current is equal to 20 mA,
the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
6-50 Terminal 42 Output
Option:
Function:
[104] Torque rel
to limit
The torque setting is related to setting in
[105] Torq relate
to rated
The torque is related to the motor torque
setting.
[106] Power
Taken from
[107] Speed
Taken from
. 20 mA =
value in
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
Freq
[113] PID
Clamped
Output
[119] Torque %
lim
[130] Output
freq.
4-20mA
0 Hz = 4 mA, 100 Hz = 20 mA
[131] Reference
4-20mA
[Min-Max] 0% = 4 mA;
100% = 20 mA
[-Max-Max] -100% = 4mA;
0% = 12 mA; +100% = 20 mA
[132] Feedback
4-20mA
[133] Motor cur.
4-20mA
.
Inverter max. current (160% current) is equal to
20 mA.
Example: Inverter norm current (15 hp [11 kW])
= 24 A. 160% = 38.4 A. Motor norm current =
22 A Readout 11.46 mA.
16
mA x 22 A
38.4
A
+ 4
mA = 13.17 mA
If the norm motor current is equal to 20 mA,
the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[134] Torq.% lim
4-20 mA
The torque setting is related to setting in
[135] Torq.%
nom 4-20
mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
Taken from
[137] Speed
4-20mA
Taken from
. 20 mA =
Value in
[138] Torque
4-20mA
Torque reference related to 160% torque.
Parameter Descriptions
FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3-69