0-12 This Set-up Linked to
Option:
Function:
To enable conflict-free changes from one set-up
to another during operation, link set-ups
containing parameters that are not changeable
during operation. The link will ensure the proper
synchronization of the ‘not changeable during
operation’ parameter values when moving from
one set-up to another during operation. ‘Not
changeable during operation’ parameters can be
identified by the label FALSE in the parameter
lists in the section
Parameter Lists
.
is used by Multi set-up
in
. Multi set-up is used to move
from one set-up to another during operation (i.e.,
while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up
2 while the motor is running. Program in Set-up 1
first, then ensure that Set-up 1 and Set-up 2 are
synchronized (or ‘linked’). Synchronization can be
performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in
to
Set-up 1
[1]. This will start the linking (synchro-
nizing) process.
0-12 This Set-up Linked to
Option:
Function:
130BP075.10
OR
2. While still in Set-up 1, copy Set-up 1 to Set-up
2. Then set
Set-up 2
[2]. This will start the linking process.
130BP076.10
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a "not changeable during
in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between Set-
up 1 and Set-up 2 during operation is now
possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
Parameter Descriptions