ESBE 3-WAY VALVE

INSTALLATION INSTRUCTIONS

Pipe the Valve into the System

•  ESBE 3-way valves can be piped for either 3-way Mixing or 3-way Diverting applications
•  3-way Mixing:  2 inputs, 1 output   •  3-way Diverting:  1 input, 2 outputs
•  The System port, or the port on the valve which will deliver the mixed water to the    
  system, must never be the center port.
•  Install the valve so the actuator (if so equipped) will not be below the valve (ie. 
facing the floor).

Orient the Valve Face Plate

•  The face plate can be turned over and rotated to match your piping configuration.

For technical support or additional product information, contact:

Danfoss Inc.

7941 Corporate Drive 
Baltimore, MD USA 21236 
Telephone: (433) 512 - 0266 
Fax: (443) 512 - 0270 
E-mail: [email protected] 
www.na.heating.danfoss.com

Danfoss Inc.

6711 Mississauga Road · Suite 410 
Mississauga, ON, L5N 2W3 Canada 
Telephone: (905) 285 - 2050 
Fax: (905) 285 - 2055 
E-mail: [email protected] 
www.na.heating.danfoss.com

3-WAY MIXING – 

Two temperature inputs, one blended output

A)

B)

C)

D)

Art.nr. 98140081   Ritn.nr 3285   Utg PC6

Wiring:

 91M, 92M, 92-2M and 93M for “Floating” Signals (see 

). For ESBE 

92P and 92K2 actuators, refer to the actuator’s installation instructions.

Warning: Always turn off all electrical power before removing or servicing 
the actuator.

–  The actuator is powered using a 24VAC transformer, 3VA minimum.
–  Remove the four cover screws and lift the cover off the actuator.
–  Remove one (or two) of the wiring knockouts and install one (or two) of the 
“conduit fittings”. All wires must go through these fittings.
–  Attach the “common” from the control (or transformer) to terminal “N”.
–  Connect the control output for clockwise rotation to “Upper terminal L1”, and 
connect the control output for counterclockwise rotation to “Lower terminal L1”

Auxiliary Switch

–  ESBE 91M, 92M, 92-2M and 93M actuators include one fully adjustable  
auxiliary switch. The wiring should be connected as shown in 

. To set the 

switching position, turn the cam (see 

).

Reinstall the cover and secure it, before turning on the power.

Adjusting the Degree of Rotation

–  ESBE 90 series actuators do not require adjustment when used with ESBE 
valves. However if the actuator is used for an application that requires a differ-
ent degree of rotation, the middle and lower cams can be adjusted to provide 
between 30° and 180° of rotation. For access to the cams, the cam operating the 
aux switch must be removed. See 

Always turn off all power before adjust-

ments are made.

Test:

 Test the valve rotation to ensure the valve is allowed to fully open and

fully close. Rotations of 30° to 180° are possible via middle and lower cams for 
applications that require them. For access, aux. switch cam must be removed.

10

0

10

0

0

10

0

10

M

L1

L1

N

1

2 3

4