ESBE 4-WAY VALVE
INSTALLATION INSTRUCTIONS
Pipe the Valve into the System
• Pipe the valve in either one of the configurations shown below.
• Install the valve so the actuator (if so equipped) will not be below the valve (ie.
facing the floor).
Orient the Valve Face Plate
• The dial face plate is printed on both sides.
• If the 0 through 10 scale is facing correctly for your piping arrangement (A or B) as
shown below, proceed with mounting the actuator.
• Otherwise, remove the face plate with the 0 through 10 scale, and turn it over.
Then replace the face plate on the valve so it matches your piping configuration.
INSTALLATION INSTRUCTIONS (Continued)
3-WAY DIVERTING –
Configurations shown below are suitable
for boiler return water control
E)
F)
A)
B)
ESBE Series 90 Actuator
INSTALLATION INSTRUCTIONS
(For Series 60 actuator mounting instructions, refer to installation instructions
included with actuator).
Place drive sleeve
onto shaft and secure with screw
. Rotate the sleeve
and valve shaft until the pointer is aligned to position 5 on scale plate.
Mount threaded stud
in the lower left threaded hole. For 1½ and 2" valves
replace one of the cover bolts with the threaded stud. Tighten mounting piece
onto threaded stud.
Mount handle
over drive sleeve. Handle must be mounted opposite to the
pointer of the drive sleeve, & facing away from
.
Mount actuator onto sleeve so that mounting piece
fits into the locking
piece
. Push locking piece
to lock in place. Labels are supplied to indicate
the direction of rotation. Determine the direction of rotation and mount the correct
label under the plastic front cover of actuator.
Note:
Always test rotation of the valve in manual position mode to ensure that
the handle does not interfere with the actuator mounting stud and mounting
piece.
Manual Operation:
Always disconnect power before operating by hand.
Note position of drive sleeve pointer to be returned to. Depress the gray button,
“A”, on the side to release the handle. The valve can now be operated manually.
Never manually operate when gears are engaged
.
5
5
5
5
5 5
5
5
3F
3G
3MG
5
A
5
10
0
0
10
0
10
0
10
2
3
”CLICK”