Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Cooling/Heating (rE=Cooling, Ht= Heating)
o07
rE
Ht
rE
rE
(1)
rE
rE
rE
Ht
Sensor type (n5=NTC 5K, n10=NTC10K, ptc=PTC,
pt1=PT1000)
o06
n5
ptc
n10
n10
n10
n10
n10
n10
n10
n10
DO2 config (dEF=Defrost; ALA=alarm; Lig=Light)
o71
dEF
Lig
dEF
ALA
dEF
dEF
ALA
(1)
This option is a default setting in the controller and cannot be changed.
(2)
This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
(1)
This option is a default setting in the controller and cannot be changed.
(2)
This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Reference
Table 22: Reference
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Reference
r--
Setpoint
r00
-100.0
200.0
°C
2.0
4.0
2.0
-20.0
2.0
-24.0
2.0
50.0
Differential
r01
0.1
20.0
K
2.0
2.0
2.0
2.0
2.0
2.0
2.0
4.0
Maximum set point limitation
r02
-100.0
200.0
°C
50.0
6.0
4.0
-18.0
4.0
-20.0
50.0
70.0
Minimum set point limitation
r03
-100.0
200.0
°C
-35.0
2.0
0.0
-24.0
0.0
-26.0
-35.0
30.0
Display offset
r04
-10.0
10.0
K
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Display Unit (°C/ °F)
r05
-C
-F
-C
-C
-C
-C
-C
-C
-C
-C
Calibration of Sair
r09
-20.0
20.0
K
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Main switch ( -1=Service, 0=OFF, 1=ON,)
r12
-1
1
1
1
1
1
1
1
1
1
Night Set back
r13
-50.0
50.0
K
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Reference displacement offset temperature
r40
-50.0
20.0
°C
0.0
0.0
0.0
0.0
0.0
0.0
-
0.0
Pull down duration
r96
0
960
min
0
0
0
0
0
0
-
-
Pull down limit temperature
r97
-100.0
200.0
°C
0.0
0.0
0.0
0.0
0.0
0.0
-
-
Alarm
Table 23: Alarm
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Alarm
A--
Delay for temp alarm during normal conditions
A03
0
240
min
30
45
30
30
30
30
30
10
Delay for temp alarm during pull-down/start up/
defrost
A12
0
240
min
60
90
60
60
60
60
60
-
High temp. alarm limit
A13
-100.0
200.0
°C
8.0
10.0
8.0
-15.0
8.0
-15.0
8.0
80.0
Low temp. alarm limit
A14
-100.0
200.0
°C
-30.0
0.0
-2.0
-30
-2.0
-30.0
-30.0
20.0
DI1 delay (Time delay for selected DI1 function)
A27
0
240
min
30
30
30
30
30
30
30
30
DI2 delay (Time delay for selected DI2 function)
A28
0
240
min
30
30
30
30
30
30
30
30
Condenser High alarm limit
A37
0
200
°C
80
80
80
80
80
80
-
-
Condenser High block limit
A54
0
200
°C
85
85
85
85
85
85
-
-
Voltage protection enable
A72
no
YES
no
no
no
no
no
no
no
no
Minimum cut-in voltage
A73
0
270
V
0
0
0
0
0
0
0
0
Minimum cut-out voltage
A74
0
270
V
0
0
0
0
0
0
0
0
Maximum voltage
A75
0
270
V
270
270
270
270
270
270
270
270
Defrost
Table 24: Defrost
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Defrost
d--
Defrost Method (no=None, nAt=Natural, EL = Elec-
tric; gAS=Hot gas)
d01
no
gAS
EL
nAt
EL
EL
EL
EL
EL
-
Defrost stop temperature.
d02
0.0
50.0
°C
6.0
-
-
-
6.0
6.0
6.0
-
Defrost Interval
d03
0
240
hour
8
6
8
12
8
12
8
-
Max defrost Time
d04
0
480
min
30
45
15
15
30
30
30
-
Defrost delay at power up
d05
0
240
min
0
0
0
0
0
0
NA
-
Drip delay
d06
0
60
min
0
0
0
0
0
0
2
(1)
-
Fan delay after defrost
d07
0
60
min
0
0
0
0
0
0
-
Fan start temperature after defrost
d08
-50.0
50.0
°C
-5.0
50.0
-5.0
-5.0
-
-
© Danfoss | Climate Solutions | 2023.01
BC194286421698en-000901 | 25
Electronic refrigeration control, type ERC 21X