Danfoss ERC 21 Series User Manual Download Page 20

Code

Parameter description

Min.

Max.

Unit

d06

Drip-off time

This parameter defines the time delay to start the compressor after defrost heater being switched OFF. This delay is generally

provided to ensure all water droplets on the evaporator drips off before starting the refrigeration cycle.

0

60

min

d07

Fan delay after defrost

Defines how long the delay is between the start of the compressor and the fan after defrost cycle. This would help to avoid

hot air circulation in the cabinet imedietely after defrost.

0

60

min

d08

Fan start temperature after defrost

This only applies if an evaporator temperature sensor is fitted. This parameter determines at what evaporator temperature

the fan will start after a defrost cycle is complete. If the time set in d07 occurs before the temperature set in d08, the fan will

start in line with d07. If the temperature set in d08 occurs first, then the fan will start in line with d08.

-50.0

50.0

°C

d09

Fan during defrost

This parameter is to define whether fan is to operate during defrost or not.

OFF

on

d10

Defrost Stop Sensor

This parameter is to define which sensor has to be used to exit / terminate the defrost

non = none, defrost is based on time

Air = Sair sensor

dEF = S5 defrost sensor

non

dEF

d18

Compressor accumulated runtime to start defrost

When the accumulated compressor runtime is equal to the value set in this Parameter, defrost will be triggered. If the accu-

mulated compressor runtime is less than the set value during the defined defrost interval (d03), defrost will be triggered

based on the defrost interval (d03). This feature is disabled when this parameter is set to zero.

0

96

hour

d19

Defrost on demand

The controller will record S5 temperature during each defrost interval when the evaporator is clean and continue to monitor

S5 temperature. Controller triggers defrost if the S5 temperature becomes less than recorded temperature by this value it will

initiate the defrost on demand. This feature is disabled when this parameter is set to 20. This function can only be used in 1:1

systems.

0.0

20.0

K

d30

Defrost delay after pull down

This parameter defines the time delay to start the defrost after pull down cycle. This has to ensure defrost doesnot happen

immedietely after pull down cycle.

0

960

min

Fan

Table 11: Fan

Code

Parameter description

Min.

Max.

Unit

F--

Fan

F01

Fan control during compressor off cycle

This parameter define the fan operation during compressor off cycle.

FAo=Fan always ON

FFC=Fan follow compressor (Fan is switched off during compressor off cycle)

FPL= Fan Cycling

FAo

FPL

F04

Fan stop evaporating temperature

This parameter defines the maximum evaporator temperature at which the Fan must switch OFF. If the defrost sensor regis-

ters a higher temperature than the one set here, the fans will be stopped to avoid the warm air circulation in the cabinet.

-50.0

50.0

°C

F07

Fan On cycle

This parameter is applicable only when the Fan at Compressor cut out (F01) is set to Fan cycling mode. The Fan ON time will

be as per the time set in this parameter.

0

180

min

F08

Fan OFF cycle

This parameter is applicable only when the Fan at Compressor cut out (F01) is set to Fan cycling mode. The Fan OFF time will

be as per the time set in this parameter.

0

180

min

Compressor

Table 12: Compressor

Code

Parameter description

Min.

Max.

Unit

c--

Compressor

C01

Compressor minimum ON time

This parameter determines the minimum number of minutes the compressor must run before a cut-out can take effect based

on temperature. This is to avoid sudden switching ON and OFF of the compressor. When used for Heating application, sug-

gest to set this value 0 to avoid any overheating.

0

30

min

C02

Compressor minimum OFF time

This parameter determines the minimum number of minutes the compressor must switched OFF before a cut-in can take

effect based on temperature. This is to avoid sudden switching OFF and ON of the compressor.

0

30

min

C04

Compressor OFF delay at door open

This parameter sets the delay to stop the compressor when the door is opened. If set to 900, the function is disabled.

0

900

sec

C70

Zero crossing selection

This feature will increase the relay life time, reduce the contact welding and switching noise by switching ON at Zero crossing.

Disable zero crossing when external relay is used.

no

YES

Electronic refrigeration control, type ERC 21X

© Danfoss | Climate Solutions | 2023.01

BC194286421698en-000901 | 20

Summary of Contents for ERC 21 Series

Page 1: ...User Guide Electronic refrigeration control Type ERC 21X series Smart multipurpose refrigeration controller...

Page 2: ...efrost on Demand 10 Applications 11 Pre defined applications 11 ERC 211 controller 11 ERC 213 controller 11 ERC 214 controller 12 Electrical connection diagram 12 Electric noise 13 Configuration 14 Me...

Page 3: ...t 25 Fan control 26 Compressor 26 Others 26 Polarity 27 Parameters ERC 214 27 Configuration 27 Reference 27 Alarm 28 Defrost 28 Fan control 28 Compressor 29 Others 29 Polarity 29 Alarm code 30 Product...

Page 4: ...ors 34 Certificates declarations and approvals 35 Certificates declarations and approvals 35 Online support 36 Electronic refrigeration control type ERC 21X Danfoss Climate Solutions 2023 01 BC1942864...

Page 5: ...y 16 A relay enable direct connection of heavy loads without use of intermediate relay up to 2 hp compressors depending on its power factor and motor efficiency power factor greater than 0 65 for 230...

Page 6: ...Outputs Relay 1 compressor solenoid valve control or heater in case of heating applications Relay 2 can be configured defrost control or external alarm or cabinet light Relay 3 fan control Inputs Inp...

Page 7: ...either cabinet light or external alarm Inputs Input 1 control sensor Sair Input 2 defrost sensor S5 Input 3 condenser sensor Sc or digital input that can be configured for various functions as metion...

Page 8: ...ime Temperature Danfoss 80G8375 Compressor protection against high condensing temperature If the condenser is blocking up with dirt and thereby reaches a too high condensing temperature the controller...

Page 9: ...rmal thermostat set point and the alarm limits by a predefined offset value Figure 7 Reference displacement Danfoss 80G8474 Cabinet temp Thermostat ref disp Thermostat ref disp Time Ref displacement d...

Page 10: ...goes below the recorded temperature by the value set in parameter d30 before the configured defrost interval it will trigger defrost immediately This function can only be used in 1 1 systems This func...

Page 11: ...ost 2 6 C Time Sair DI1 AP3 MT Natural defrost defrost stop by Sair 2 6 C Sair temp Sair DI1 AP4 Heating Thermostat 30 70 C NA Sair DI1 AP5 Fully configurable simplified application Cooling Heating 1...

Page 12: ...0 C NA Sair NC DI1 DI2 1 The digital inputs DI1 and DI2 can be configured for multiple functions refer Parameters o02 and o37 1 The digital inputs DI1 and DI2 can be configured for multiple functions...

Page 13: ...nu code o02 Digital input configurable to the functions listed under menu code o37 Electric noise Cables for sensors and DI inputs must be kept separate from other electric cables Use separate cable t...

Page 14: ...default value eg AP0 flashing Choose the application type by pressing UP DOWN and press SET to confirm The controller presets parameter values according to the selected application and does not hide r...

Page 15: ...rameter menu display will show cFg Enter CFg menu by pressing SET button diaplay will show first parameter r12 main switch Select r12 by pressing SET button again and set the main switch to oFF r12 0...

Page 16: ...s PULL DOWN button again for 3 seconds to stop the pull down Danfoss 80G8441 A A Temperature and alarm codes alternate flashes until the alarm is resolved The alarm bell is shown Open the o37 DI2 Conf...

Page 17: ...d is locked any button press shows LoC in the display Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard unl is displayed for 3 seconds Figure 15 Unloack keyboard Danfoss Cl...

Page 18: ...t in of compressor relay Compressor relay will cut in when the cabinet temperature reaches the set point differetial In case of heating application heater will cut in when the temperature reaches the...

Page 19: ...ed and compressor is stopped It is restricted to starting again until alarm is reset manually Manual reset of con denser block alarm can be performed by power cycling the controller either by main swi...

Page 20: ...down This parameter defines the time delay to start the defrost after pull down cycle This has to ensure defrost doesnot happen immedietely after pull down cycle 0 960 min Fan Table 11 Fan Code Parame...

Page 21: ...or action on doo o67 Save settings as factory This parameter when set to YES The current controller Parameter settings are stored as Factory default WARNING Original factory settings are overwritten n...

Page 22: ...number of cycles On reaching 999x100 cycles the counts stops and is reset to 0 0 999 o24 Relay 2 counter The number of cycles for the DO2 relay can be read in this menu The read value is multiplied by...

Page 23: ...mp alarm during pull down start up defrost A12 0 240 min 60 60 90 90 NA 60 High temp alarm limit A13 100 0 200 0 C 8 0 16 0 10 0 10 0 80 0 8 0 Low temp alarm limit A14 100 0 200 0 C 30 0 0 0 0 0 0 0 1...

Page 24: ...ing Heating rE Cooling Ht Heating o07 2 rE Ht rE rE 1 rE 1 rE 1 Ht 1 rE Display Resolution o15 0 1 1 0 0 1 0 1 0 1 0 1 0 1 0 1 1 Predefined applications o61 2 AP0 AP5 AP0 AP1 AP2 AP3 AP4 AP5 Save sett...

Page 25: ...down limit temperature r97 100 0 200 0 C 0 0 0 0 0 0 0 0 0 0 0 0 Alarm Table 23 Alarm Function Code Min Max Unit AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7 Alarm A Delay for temp alarm during normal conditions...

Page 26: ...pressor Heater minimum OFF time C02 0 30 min 2 2 2 2 2 2 2 2 Compressor OFF delay at open door C04 0 900 Sec 900 900 900 900 900 900 60 1 900 Zero crossing selection YES no C70 no YES YES YES YES YES...

Page 27: ...ion Code Min Max Unit AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7 Configuration cFg Main switch 1 Service 0 OFF 1 ON r12 1 1 1 1 1 1 1 1 1 1 Predefined applications o61 2 AP0 AP7 AP0 AP1 AP2 AP3 AP4 AP4 AP6 AP7 C...

Page 28: ...P6 AP7 Defrost d Defrost Method no None nAt Natural EL Elec tric gAS Hot gas d01 no gAS EL nAt EL EL EL EL EL Defrost stop temperature d02 0 0 50 0 C 6 0 6 0 6 0 6 0 Defrost Interval d03 0 240 hour 8...

Page 29: ...Alarm o36 2 Lig ALA Lig Lig Lig Lig Lig Lig Lig Lig DI2 configuration nC Not configured Sdc Status display output doo Door alarm with resumption doA Door alarm without resumption SCH Main switch nig...

Page 30: ...ature in cabinet is too low A99 High Volt alarm Supply voltage is too high compressor protection AA1 Low Volt alarm Supply voltage is too low compressor protection A61 Condenser alarm Condenser temp t...

Page 31: ...le length 1 5 m Accuracy Measuring range 40 105 C 40 221 F Controller accuracy 1 K below 35 C 0 5 K between 35 25 C 1 K above 25 C Type of action 1B relay Output DO1 Relay 1 16 A 16 16 A EN 60730 1 10...

Page 32: ...e panel Slide the clips towards mounting surface until controller is firmly fixed To remove the controller one needs to skillfully unlatch the snapping tab and pull the clips backwards Dimensions Figu...

Page 33: ...too low or too high Check A A72 Check A A73 Check A A75 Defrost does not start Controller in pull down mode Check r r96 Pull down does not start Pull down max duration is 0 Check r r96 Pull down limi...

Page 34: ...4B4404 Thermo plastic polyester 8x30 1 5 m 1 084N1220 Thermo plastic polyester 8x30 3 5 m 1 084N1221 EKS 221 NTC 10000 ohm 25 C Beta 3435 at 25 85 C Thermo plastic rubber 6x5x15 3 5 m 150 084N3206 The...

Page 35: ...status at danfoss com or contact your local Danfoss representative if you have any questions Certificates declarations and approvals R290 R600a end use applications employing in accordance with the I...

Page 36: ...ations manuals and guides 3D models and drawings case stories brochures and much more Start searching now at www danfoss com en service and support documentation Danfoss Learning Danfoss Learning is a...

Reviews: