User Guide  |  Liquid level controller, EKE 347 

© Danfoss | DCS (ADAP-KOOL®) | 2016-04

DKRCI.PD.RP0.A4.02 | 8

Data

Supply voltage

24 V a.c. +/-20% 50/60 Hz or 24 V d.c. +/-20%

(the supply voltage is galvanically separated from the input and output signals. 

Input/output are not individual galvanic isolated)

Power consumption

Controller

20 W coil for AKV or AKVA

15 VA / 10W

55 VA

Input signal 

* Ri =

0(4)-20mA: 33 ohm

0(2)-10  V: 100 kohm

Level signal *

4-20 mA or 0-10 V

ICM valve feedback signal *

From ICAD 0/4-20 mA

Contact function start/stop of regulation

Relay output

3 pcs. SPDT (Lower level alarm, Upper level alarm, 

Common alarm / NC Solenoid)

Normally Open: 
3 A GP*, 2.2 FLA / 13.2 LRA, 1/6 hp, PD 220 VA, 250 V a.c. 100 k
3 FLA / 18 LRA, 1/10 hp, PD 150 VA, 125 V a.c. 100 k
Normally Closed:
3 A GP*, 250 V a.c. 100 k 
(*GP = General purpose).

Max 240 V a.c. or 24 V a.c./d.c. can be used, but same voltage type must be 

used on DO3 and DO2

Current output

0-20 mA or 4-20 mA

Max. load: 500 ohm

Valve connection

ICM - via current output

AKV/A- via 24 a.c. Pulse-Width Modulating output

Data communication

MODBUS RTU: Communication to system controller,

MODBUS on RS485: galvanic isolation (500 V d.c.)

CAN: Communication to other EKE controllers

Supported Modbus 
Commands

Supported  commands with max of 50 ms re-
sponse time 

03 (0x03) Read Holding Registers
04 (0x04) Read Input Registers
06 (0x06) Write Single Register

Supported  commands without defined max re-
sponse time 

08 (0x08) Diagnostics
16 (0x10) Write Multiple Registers (up to 20 registers)
43 (0x2b) Read Device Identification

Environments

–20 - 55°C, during operation

–30 - 80°C, during storage
90% Rh, not condensed
No shock influence / vibrations

Enclosure

IP 20 /IP 40 for the front mounted into a panel

Weight

193 g

Mounting

DIN rail

Display

Graphical LCD display

Terminals

plugs 1.5 or 2.5 mm

2

 multicore

Approvals

EU Low Voltage Directive and EMC demands re CE-marking complied with.

LVD-tested acc. to EN 60730-1 and EN 60730-2-9

EMC-tested acc. to EN61000-6-3 and EN 61000-6-2

UL file E31024

Ordering

Type

Description

Code No.

EKE 347

Liquid level controller

080G5000

MMIGRS2

Remote display, Panel, S

080G0294      

-

Wire for display unit, L = 1.5 m, 1 pcs.

080G0075

-

Wire for display unit, L = 3 m, 1 pcs.

080G0076

-

EKE / EKC accessory for panel mounting

027F0309

Summary of Contents for EKE 347

Page 1: ...e the liquid flow to or from the reservoir Liquid level control Alarm if the set alarm limits are exceeded Relay outputs for upper and lower level lim its and for alarm level User friendly and easy se...

Page 2: ...ers to the EKE 347 Operation monitoring and data collection can then be performed via PLC from a SCADA system With the guided micro wave rod AKS 4100 4100U it is possible to set the refrigerant level...

Page 3: ...unctions in connection with the max permissible level Receiver condenser The control system s short reaction time makes it very suited for high pressure float systems with small refrigerant charges IC...

Page 4: ...alarm present and Upper level alarm off no alarm present Additional to the external connected alarm audio video sources a Bell symbol will flash in the upper right corner in case of an alarm To see m...

Page 5: ...wable parameters including password issuing and re run of Setup wizard Service level is for service personnel and has fewer rights than commissioning The lowest level is for Daily use and allows only...

Page 6: ...0 100 Display Language EN CN PT RU SP FR IT GER ARAB EN Output indication level OD Level Login timeout 1 120 min 10 min Backlight timeout 0 120 min 2 min Password daily 3 digit 0 999 100 Password serv...

Page 7: ...oller name Controller name Type in controller name Read Write Read only Alarm and error codes When detecting an alarm from external sources or the flashing bell in the display the alarm description ca...

Page 8: ...ing output Data communication MODBUS RTU Communication to system controller MODBUS on RS485 galvanic isolation 500 V d c CAN Communication to other EKE controllers Supported Modbus Commands Supported...

Page 9: ...Normally Closed 34 35 circuits The relay will switch according to the programmed setting 25 27 Relay for low level limit Installer can choose between Normally Open 26 27 or Normally Closed 25 26 circu...

Page 10: ...ay ModBUS 4 20 mA 24 V DC yellow blue orange ICAD 1st gen ICAD ICM feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 yellow gray orange ICAD 1st gen pre 2010 ICAD 2nd gen 2010 yellow green brown brown whit...

Page 11: ...AC 20 15 VA 24 V DC 20 10 W Common Normally Open or Normally Closed Low Level Alarm Normally Open or Normally Closed High Level Alarm Normally Open or Normally Closed 37 29 28 27 26 25 36 35 34 33 32...

Page 12: ...F Application Open Close solenoid valve with coil 24 V 230V NO 4 NC 3 C 3 NO 3 NC 2 C 2 NO 2 NO 1 C 1 NC 1 POWER SUPPLY Voltage 24 230 V a c Connection examples AKS 4100 AKS 4100U Danfoss M84H0075_1 A...

Page 13: ...these options 2 valves with same capacity 2 valves with different capacity 3 valves with same capacity 3 valves with different capacity Multivalve Additionally the master must be programmed in IO conf...

Page 14: ...0 CAN H CAN L GND 15 16 17 18 Jumper 15 16 Jumper 15 16 D02 D03 D01 NC 2 C 2 NO 2 NC 3 C 3 NO 3 NO 1 C 1 NC 1 When more controllers are connected via CAN bus each end of the bus must be terminated wit...

Page 15: ...splay s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until the Bios menu appears 2 Select the MCX selection menu Sele...

Page 16: ...ES 0 Low 1 High n04 P band 5 200 30 1 3016 NO YES n05 Integration time Tn 60 600 400 s 0 3017 NO YES n34 Neutral zone 0 25 2 1 3018 NO YES N06 Difference 0 5 25 2 1 3019 NO YES n13 Period time for AKV...

Page 17: ...tate 0 6 0 0 4001 YES NO 0 Powerup 1 Stop 2 Auto 3 Manual 4 Slave 5 IO 6 Safe u01 Actual level 0 100 0 1 4002 NO NO u02 Actual reference 0 100 0 1 4003 YES NO u24 Actual OD 0 100 0 1 4004 NO NO u33 Ac...

Page 18: ...material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being...

Reviews: