Instructions  RI8NG552  ©  Danfoss  10/2011 

   EKC 326A

Display

The values will be shown with three digits.
Temperature are to be shown in °C and pressure in bar.

Operation

Menu survey

The buttons

When you want to change a setting, the two buttons will give you 
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the 
menu. You obtain this by pushing the upper button for a couple 
of seconds - you will then enter the column with parameter codes. 
Find the parameter code you want to change and push the two 
buttons simultaneously. When you have changed the value, save 
the new value by once more pushing the two buttons simultane-
ously.

Gives access to the menu (or cutout an alarm)

Gives access to changes

Saves a change

Examples of operations

Set a menus

1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting

Control starts when the supply is connected

0 V  = valve closed
10 V = valve open

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage

Light-emitting diodes (LED) on front panel

The four LED’s will flash, if there is an error in the regulation.
In this situation you can upload the error code on the display and 
cancel the alarm by giving the uppermost button a brief push.

The controller can give the following messages:

E1

Error message

Fault in controller

E15

Cut-out Sgc2 sensor

E16

Short circuited Sgc2 sensor

E20

Fault on the signal from Pgc

E39

Fault on the signal from Prec

A43

Alarm message

Step motor error. Output or phase

A45

Regulation stopped. Main switch r12 = off

A82

The Pgc gas pressure measured is higher than the 
maximum limit for n69

A83

The Pgc gas pressure measured is lower than Pgc 
min (A65)

A84

The receiver pressure measured is lower than "n71" 
minus "n72"

A94

Pgc alarm limit "A66" is exceeded

A95

Prec alarm limit "A67" is exceeded

Function

Para-
meter

Min.

Max.

Factory 
setting

Normal display

Shows the current pressure after the gas cooler
Pushing both buttons briefly will display the 
reference
Pushing the bottom button briefly will display 
Prec.

-

bar

Start / stop

Start / stop of regulation

r12

OFF (0) On (1)

On (1)

Ramp for reference after heat recovery

r65

0.1

20

1

Displacement of the Pgc minimum reference 
(n89) during heat recovery. (Displacement value 
at 10 V)

r68

0 bar

100 bar 0

Alarm Settings

Alarm  limit for Pgc Min.

A65

0 bar

200 bar 40

Permitted Pgc reference variation
0 = no alarm function (recommended)

A66

0 bar

50 bar

0

Permitted Prec reference variation
0 = no alarm function (recommended)

A67

0 bar

50 bar

0

Delay time for 'A94' Pgc reference alarm

A68

5 min. 360 min 15

Delay time for 'A95' Prec reference alarm

A69

5 min. 360 min 15

Regulating parameters

Actuator type for receiver control
0=ETS12,5/25 / CCM10/20, 
1=ETS50 / CCM30, 2=ETS100 / CCM40, 
3=ETS250, 4=ETS400, 
5=User defined (set: n37 and n38)
6=CCMT2/4/8

n03

0

6

0

P: Amplification factor Kp

n04

0.5

20

2.0

I:  Integration time Tn

n05

10 s

600 s

75

Max. opening degree. of the valve

n32

0

100

100

Number of steps from 0-100% opening degree 
(x10) **

n37

0

500

262

Number of steps per second

n38

0

300

250

Max. permitted receiver pressure, Prec

n58

10 bar 200 bar 60

P-belt beyond PrecMax for valve to close

n59

0 bar

60 bar

0

P: Amplification factor Kp for receiver

n60

0.5

20

5

I:  Integration time Tn for receiver

n61

10

600

75

The gas cooler’s max. pressure
This is where you set the maximum pressure per-
mitted in the gas cooler. If the pressure reaches 
this value, the valve is fully open.

n69

7

200

90

P-band under n69, so the valve is fully open if 
the pressure is n69.

n70

0

60

5

Min. pressure in the receiver
This function is only used if the pressure trans-
mitter Prec is mounted.

n71

7

60

30

P-band to force open the valve if the receiver 
pressure is too low 

n72

0

60

3

Subcooling is required to be regulated accord-
ing to temperature
Set the desired subcooling in K.

n79

1 K

30 K

1

The gas cooler’s min. pressure

n81

7

200 bar 45

Min. permissible opening degree for ICMTS

n87

0

100%

0

Extra capacity when the contact is closed. 
(The Pgc reference is increased with this value)

n88

0 bar

200 bar 0

Minimum permitted Pgc reference during heat 
recovery (AI > 2 V). The value can be increased 
further using the r68 function.  

n89

7 bar

200 bar 7

Do you require receiver pressure control: Off=no, 
On=yes

n90

Off

On

On

Prec. reference for receiver pressure control

n91

7 bar

200 bar 35

Receiver pressure control. Maximum opening 
degree for ETS

n92

0%

100%

100

Receiver pressure control. Smallest opening 
degree for ETS

n93

0%

100%

0

Define the reference curve point at 100 bar.

n99

35°C

55°C

39

ENGLISH

Manual: See RS8FM

SW =2.0x

Summary of Contents for EKC 326A

Page 1: ...Princip Principle Montageprinzip Principe M l Dimensions Ma e Dimensions Instructions EKC 326A RI8NG552 10 2011 Identifikation Identification 084B7252...

Page 2: ...be mounted near the gas cooler outlet to produce a correct signal High pressure valve Vhp Gas bypass valve Vgbp 8 VA DANSK ENGLISH Tilslutninger Connections N dvendige tilslutninger Klemme 25 26 Fors...

Page 3: ...ement Se reporter au document sp cifique RC8AC Important Pour mettre un signal correct les capteurs PGC et SGC2 doivent tre mont s proximit imm diate de la sortie du refroidisseur gaz Ben tigte Anschl...

Page 4: ...per viser referencen Kort tryk p nederste knap viser Prec bar Start stop Start stop af reguleringen r12 OFF 0 On 1 On 1 Rampe for referencen efter varmegenvinding r65 0 1 20 1 Forskydning af Pgc min r...

Page 5: ...ssp ndingens frekvens o12 50Hz 0 60 Hz 1 0 Tryktransmitteromr de Pgc min o20 1 bar 5 bar 1 Tryktransmitteromr de Pgc max o21 6 bar 199 bar 159 Tryktransmitteromr de Prec min o47 1 bar 5 bar 1 Tryktran...

Page 6: ...y the reference Pushing the bottom button briefly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the...

Page 7: ...0 60 Hz 1 0 Pressure transmitter range Pgc min o20 1 bar 5 bar 1 Pressure transmitter range Pgc max o21 6 bar 199 bar 159 Pressure transmitter range Prec min o47 1 bar 5 bar 1 Pressure transmitter ran...

Page 8: ...n aktuellen Druck hinter dem Gask hler Kurze Bet tigung beider Tasten zeigt den Sollwert an Kurze Bet tigung der unteren Taste zeigt Prec an bar Start stop Start stop der Regelung r12 OFF 0 On 1 On 1...

Page 9: ...z 1 0 Druckmessumformer Bereich Pgc min o20 1 bar 5 bar 1 Druckmessumformer Bereich Pgc max o21 6 bar 199 bar 159 Druckmessumformer Bereich Prec min o47 1 bar 5 bar 1 Druckmessumformer Bereich Prec ma...

Page 10: ...marrage arr t D marrage Arr t de la r gulation r12 OFF 0 On 1 On 1 Rampe de r f rence apr s la r cup ration de chaleur r65 0 1 20 1 D placement de la r f rence minimale Pgc n89 au cours d une r cup r...

Page 11: ...rvice o04 Choisir la fr quence d alimentation o12 50Hz 0 60 Hz 1 0 Plage du transmetteur de pression Pgc min o20 1 bar 5 bar 1 Plage du transmetteur de pression Pgc max o21 6 bar 199 bar 159 Plage du...

Page 12: ...2011 EKC 326A The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic waste According to Lo...

Reviews: