Light-emitting diodes (LED) on front panel

All 4 light-emitting diodes will flash when there is an error in the 
regulation.

In this situation you can upload the error code on the display and 

cancel the alarm by giving the uppermost button a brief push.

The controller can give the following messages:

E1

Error message

Fault in controller

E15

Cut-out S2 sensor

E16

Short circuited S2 sensor

E17

Cut-out  S3 sensor

E18

Short circuited S3 sensor

E20

Fault on signal from Pc

E39

Fault on signal from P0

A11

Alarm message

No refrigerant has been selected

A43

Step motor fault. Output or phase

A45

Regulation stopped. Main switch r12 = off

Display

The values will be shown with three digits. 

Temperature are shown in °C  and pressure in bar.

Operation

Menu survey

The buttons

When you want to change a setting, the two buttons will give you 

a higher or lower value depending on the button you are push-

ing. But before you change the value, you must have access to the 

menu. You obtain this by pushing the upper button for a couple 

of seconds - you will then enter the column with parameter codes. 

Find the parameter code you want to change and push the two 

buttons simultaneously. When you have changed the value, save 

the new value by once more pushing the two buttons simultane-

ously.

 

Gives access to the menu (or cutout an alarm)

 

Gives access to changes

 

Saves a change

Examples of operations

Set of a menu

1. Push the upper button until a parameter is shown

2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value

5. Push both buttons again to conclude the setting

Function

Para-

meter Min.

Max.

Fac.set-

ting

Normal display
Displays either the valve's current opening degree or the current superheat value.

(Can be set in o17)

Briefly pushing the bottom button will display one of the two readings.

Briefly pushing both buttons will display the superheat reference (u22).
Start / stop
Start / stop af regulation

r12

OFF (0) On (1)

On (1)

Regulating parameters
Select valve type:

0=ETS 12,5 & 25 / CCM10 & CCM20

1=ETS 50 / CCM30, 2=ETS 100 / CCM40

3=ETS 250, 4=ETS 400, 

5=User defined (set : n37 and n38)

6=0-10 V's output must control ICAD actuator

7=0-10 V's output must on/off control a solid 

state relay.

n03

0

7

0

I: Integration time Tn 

n05

5 s

600 s

90

D: Differentiation time Td

n06

0 s

60 s

0

Max. value of superheat reference

n09

3 K

60 K

40

Min. value of superheat reference

n10

3 K

40 K

10

MOP (max. = Off)

n11

0 bar

60 bar

60

Signal reliability during start-up. Time for safety. 
Should only be changed by trained staff

n15

0 s

240 s

0

Signal reliability during start-up – Opening 
degree’s start value. Should only be changed by 
trained staff.

n17

0%

100%

0

Kp amplification just around reference value
Changes should only be made by trained staff

n19

0

30

3

Amplification factor for superheat. (KpT0) 
Changes should only be made by trained staff

n20

0

30

5

Max. opening degree of valve

n32

0%

100%

100

Number of steps from 0-100% opening degree 
(x10) **

n37

0

500

263

Number of steps per second

n38

0

300

250

Max. Kp factor for PID-regulation (Kp max)

n95

0

30

5

Calculation factor for superheat SH
Changes should only be made by trained staff

n96

10

100

50

Filter constant for SH reference
Changes should only be made by trained staff

n97

5 s

600 s

60

Lower limit value for the condensing pressure

n98

-30°C

10°C

-5

Miscellaneous
Controller’s address (0 = off)

o03*

0

119

0

ON/OFF switch (service-pin message)

o04*

-

-

-

Set supply voltage frequency

o12

50Hz (0) 60 Hz (1) 0

Select display view for the "normal display"

1: Opening degree of the valve

2: Superheat

o17

1

2

1

Manual control of outputs: 

0: Normal regulation

1: Overriding. Manual control permitted

o18

0

1

0

Pressure transmitter selection

1: AKS 32R / AKS 2050

2: Pressure  transmitter with 0-10 V

3: Pressure transmitter with 1-5 V

o10

1

3

1

Working range for pressure transmitter  Pc - min. o20

-1 bar 5 bar

-1

Working range for pressure transmitter  Pc - max. o21

6 bar

199 bar 59

Refrigerant setting for P0 circuit
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  
6=R13.  7=R13b1.  8=R23.  9=R500.  10=R503.  
11=R114.  12=R142b. 13=User defined. 
14=R32. 15=R227.  16=R401A.  17=R507. 
18=R402A.  19=R404A. 20=R407C.  21=R407A.  
22=R407B.  23=R410A.  24=R170.  25=R290.  
26=R600.  27=R600a.  28=R744.  29=R1270.

30=R417A. 31=R422A. 32=R413A. 33=R422D. 

34=R427A. 35=R438A

o30

0

35

0

Relay application: 0=Alarm relay. 1=EVR valve i 

liquid line

o36

0

1

0

Forced control of the valves opening degree. 

(Only if o18 is set to manual)

o45

0

100%

0

Working range for pressure transmitter P0 - min. o47

-1 bar 5 bar

-1

SW =2.0x

*) This setting will only be possible if a data communication module has been installed in the 
controller.

**) The display on the controller can show 3 digits only, but  the setting value has 4 digits. Only the 

3 most important will be shown. It means fx. 250 will give a setting of 2500.

Summary of Contents for EKC 313

Page 1: ...Controller for cascade systems with CO2 EKC 313 User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...e temperature exceeds 100 C Functions Output signal The controller has a voltage output on 0 10 V The signal can be used for Indicating the valve s opening degree when using an ETS valve Controlling t...

Page 3: ...if the condensing pressure is low Optimised superheat regulation is used when the condensing pressure is above the set value If the condensing pressure falls below the set value the opti mised superhe...

Page 4: ...result in a reduced opening degree When there is a drop out on the low pressure thermostat during start up the value must be raised a bit If there is pendling during start up the value must be reduced...

Page 5: ...r second Must only be set when n03 is set to 5 Automatically set when n03 is set to 0 1 2 3 or 4 n38 Steps sec Miscellaneous Miscellaneous Address If the controller is built into a network with data c...

Page 6: ...eating U19 SH Close Reading the condensation pressure calculated for temperature U20 Cond Temp Tc Reading the condensation pressure pressure at Pc U21 Cond Press Pc Reading the evaporating pressure pr...

Page 7: ...ings Alarm destinations E1 Fault in controller Controller fault E15 Cut out S2 sensor S2 o c E16 Short circuited S2 sensor S2 s c E17 Cut out S3 sensor S3 o c E18 Short circuited S3 sensor S3 s c E20...

Page 8: ...y n03 0 7 0 I Integration time Tn n05 5 s 600 s 90 D Differentiation time Td n06 0 s 60 s 0 Max value of superheat reference n09 3 K 60 K 40 Min value of superheat reference n10 3 K 40 K 10 MOP max Of...

Page 9: ...verted to temperature u26 C Read calculated SH closing value U19 K Read Pc converted to temperature U20 C Read pressure at pressure transmitter Pc U21 bar Working range for pressure transmitter P0 max...

Page 10: ...nnects when regulation requires a low valve open ing degree Alarm relay 12 and 13 are connected in case of alarm 21 22 23 24 Connecting an ETS valve Terminals 21 through 24 should not be used when usi...

Page 11: ...3 A inductive Actuator ETS CCM CCMT Step motor ICAD mounted on ICMTS Voltage signal 0 10 V Output signal Voltage signal 0 10 V to either ICAD control or to signal for valves opening degree Data commun...

Page 12: ...tions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to prevent this However a wrong installati...

Reviews: