Controller application setting parameters

Quick Guide

1

) The compressor relay closes when the room temperature exceeds the setting value and differential.

2

) Alarm is released and sensor failure is indicated, if the room temperature reaches 5°C or more outside the setting range

–60° to +50°C.

3)

The frequency is measured after approx. three days and nights operation after start of the plant (72 cyclings) otherwise:
ON-time = c03 x 20: 100 minutes
OFF-time interval 20 minus ON-time per minute

4

) Function possibilities with SPST contact, connected to the terminals 3 and 4 are the following:

Door alarm

: If  SPST is cut out, alarm signalling starts and the fan is stopped, cf. A04 or F03.

Defrost:

 If SPST is cut in, defrost starts.

(However, if  d03 is not OFF, defrost will during contact break down start with the programmed time intervalles).

Bus

: With installed communication card, the position of the SPST contacts will be registered in the BUS system.

Operating the two pushbuttons

Display

readout

What the controller does automatically

Resulting

controller

setup

Normal

operation

Room

 temp. 2

Normal

operation

(or alarm)

Known

codes

and settings

All parameter

settings

= factory

settings

Normal

operation

Normal

operation

Normal

operation

Alarm relay

not

 activated

Alarm

Room

temp.

Room

temp.

Set

value

Change

Change

Change

Set

value

Room

temp.

Room

temp.

Power off

Power

on

Room

temp.

Room

temp.

Room

temp.

Room

temp.

Room

temp.

Alarm code/

Fault code

Alarm code/

Fault code

Room temp.

Room temp.

Defrost operation

Defrost sensor temp.

What

to do

Initial

controller

setup

Read

or

change

 room

temp.

setting

Read

or change

parameter

codes

and

settings

Re-establish

all factory

settings

Read

defrost

sensor

temp.

Manually

start of

a defrost

operation

Manually

stop of

a defrost

operation

Reset

alarm

relay

Read codes

cause of

alarm mode

Normal

operation

Room

temp. 1

Normal

operation

(or alarm)

Unknown

codes

and settings

Unknown

settings

Normal

operation

or alarm

Normal

operation

Defrost

operation

Alarm

relay

activated

Alarm relay

not

activated

Room

temp.

Room

temp.

Code

Room

temp.

Room

temp.

Room

temp.

Room

temp.

Room

temp.

Room

temp.

Para-

Controller

Min.

Max.

Factory

Actual

Setting and read-off parameters

meter

application no.

value

value

setting

setting

codes

1

2

3

4

Temperature controller, Temperature

-60

o

C

50

o

C

3

o

C

Thermostat

Differential

1

)

r01

0.1 K

20 K

2 K

Max. limitation of set temperature

r02

-59

o

C

50

o

C

50

o

C

Min. limitation of set temperature

r03

-60

o

C

49

o

C

-60

o

C

Adjustment of temperature indication

r04

20 K

20 K

0.0 K

Temperature unit (°C/°F)

r05

o

C

Alarm

Upper deviation  (above temp. s differential 

2

)

A01

0 K

50 K

10 K

Lower deviation  (below temp. setting 

2

)

A02

50 K

0 K

10 K

Temperature alarm delay

A03

0 min

90 min

30 min

Door alarm delay

A04

0 min

90 min

60 min

Compressor

Min. ON-time

c01

0 min

15 min

0 min

Min. OFF-time

c02

0 min

15 min

0 min

Cut-in frequency on sensor fault 

3

)

c03

0 %

100 %

0 %

Compressor stop at open door (yes/no)

c04

no

Defrost

Defrost method (EL/GAS)

d01

EL

Defrost stop temperature

d02

0

o

C

25

o

C

6

o

C

Interval between defrost starts

d03

OFF

48 hour

8 hour

Max. defrost duration

d04

0 min

180 min

45 min

Defrost time delay (after power up)

d05

0 min

60 min

0 min

Drip-off time

d06

0 min

20 min

0 min

Fan start delay after defrost

d07

0 min

20 min

1 min

Fan start temperature

d08

-15

o

C

0

o

C

-5

o

C

Fan cut-in during defrost (yes/no)

d09

no

Defrost sensor (yes/no)

d10

yes

Temperature alarm delay after defrost

d11

0 min

199 min

90 min

Delay of display view after defrost stop

d12

0 min

15 min

1 min

Fan

Fan stop on compressor cut-out (yes/no)

F01

no

Fan stop delay

F02

0 min

30 min

0 min

Fan stop at open door (yes/no)

F03

yes

Miscellaneous

Delay of output signal after start-up

o01

0 s

600 s

5 s

Digital input signals 

4

)

(0 = not used, 1 = door alarm, 2 = defrost, 3 = bus)

o02

0

Access code

o05

OFF

100

OFF

Used sensor type (Pt / PTC)

o06

Pt/PTC

Real time clock (if fitted)

Six start times for defrost

All can be cut out by setting on OFF

t01

 t06

0

23

OFF

Hour setting

t07

0 hour

23 hour

0 hour

Minute setting

t08

0 min

59 min

0 min

Fault code display

Alarm code display

Status code display

E 1

Fault in controller

A 1

High temperature alarm

S 2

ON-time

E 2

Disconnected room sensor

A 2

Low temperature alarm

S 3

OFF-time

E 3

Short-circuited room sensor

A 4

Door alarm

S 4

Drip-off time

E 4

Disconnected defrost sensor

E 5

Short-circuited defrost sensor

E 6

Change battery