108
Controller application setting parameters
Quick Guide
1
) The compressor relay closes when the room temperature exceeds the setting value and differential.
2
) Alarm is released and sensor failure is indicated, if the room temperature reaches 5°C or more outside the setting range
–60° to +50°C.
3)
The frequency is measured after approx. three days and nights operation after start of the plant (72 cyclings) otherwise:
ON-time = c03 x 20: 100 minutes
OFF-time interval 20 minus ON-time per minute
4
) Function possibilities with SPST contact, connected to the terminals 3 and 4 are the following:
Door alarm
: If SPST is cut out, alarm signalling starts and the fan is stopped, cf. A04 or F03.
Defrost:
If SPST is cut in, defrost starts.
(However, if d03 is not OFF, defrost will during contact break down start with the programmed time intervalles).
Bus
: With installed communication card, the position of the SPST contacts will be registered in the BUS system.
Operating the two pushbuttons
Display
readout
What the controller does automatically
Resulting
controller
setup
Normal
operation
Room
temp. 2
Normal
operation
(or alarm)
Known
codes
and settings
All parameter
settings
= factory
settings
Normal
operation
Normal
operation
Normal
operation
Alarm relay
not
activated
Alarm
Room
temp.
Room
temp.
Set
value
Change
Change
Change
Set
value
Room
temp.
Room
temp.
Power off
Power
on
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Alarm code/
Fault code
Alarm code/
Fault code
Room temp.
Room temp.
Defrost operation
Defrost sensor temp.
What
to do
Initial
controller
setup
Read
or
change
room
temp.
setting
Read
or change
parameter
codes
and
settings
Re-establish
all factory
settings
Read
defrost
sensor
temp.
Manually
start of
a defrost
operation
Manually
stop of
a defrost
operation
Reset
alarm
relay
Read codes
cause of
alarm mode
Normal
operation
Room
temp. 1
Normal
operation
(or alarm)
Unknown
codes
and settings
Unknown
settings
Normal
operation
or alarm
Normal
operation
Defrost
operation
Alarm
relay
activated
Alarm relay
not
activated
Room
temp.
Room
temp.
Code
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Para-
Controller
Min.
Max.
Factory
Actual
Setting and read-off parameters
meter
application no.
value
value
setting
setting
codes
1
2
3
4
Temperature controller, Temperature
-60
o
C
50
o
C
3
o
C
Thermostat
Differential
1
)
r01
0.1 K
20 K
2 K
Max. limitation of set temperature
r02
-59
o
C
50
o
C
50
o
C
Min. limitation of set temperature
r03
-60
o
C
49
o
C
-60
o
C
Adjustment of temperature indication
r04
20 K
20 K
0.0 K
Temperature unit (°C/°F)
r05
o
C
Alarm
Upper deviation (above temp. s differential
2
)
A01
0 K
50 K
10 K
Lower deviation (below temp. setting
2
)
A02
50 K
0 K
10 K
Temperature alarm delay
A03
0 min
90 min
30 min
Door alarm delay
A04
0 min
90 min
60 min
Compressor
Min. ON-time
c01
0 min
15 min
0 min
Min. OFF-time
c02
0 min
15 min
0 min
Cut-in frequency on sensor fault
3
)
c03
0 %
100 %
0 %
Compressor stop at open door (yes/no)
c04
no
Defrost
Defrost method (EL/GAS)
d01
EL
Defrost stop temperature
d02
0
o
C
25
o
C
6
o
C
Interval between defrost starts
d03
OFF
48 hour
8 hour
Max. defrost duration
d04
0 min
180 min
45 min
Defrost time delay (after power up)
d05
0 min
60 min
0 min
Drip-off time
d06
0 min
20 min
0 min
Fan start delay after defrost
d07
0 min
20 min
1 min
Fan start temperature
d08
-15
o
C
0
o
C
-5
o
C
Fan cut-in during defrost (yes/no)
d09
no
Defrost sensor (yes/no)
d10
yes
Temperature alarm delay after defrost
d11
0 min
199 min
90 min
Delay of display view after defrost stop
d12
0 min
15 min
1 min
Fan
Fan stop on compressor cut-out (yes/no)
F01
no
Fan stop delay
F02
0 min
30 min
0 min
Fan stop at open door (yes/no)
F03
yes
Miscellaneous
Delay of output signal after start-up
o01
0 s
600 s
5 s
Digital input signals
4
)
(0 = not used, 1 = door alarm, 2 = defrost, 3 = bus)
o02
0
Access code
o05
OFF
100
OFF
Used sensor type (Pt / PTC)
o06
Pt/PTC
Real time clock (if fitted)
Six start times for defrost
All can be cut out by setting on OFF
t01
→
t06
0
23
OFF
Hour setting
t07
0 hour
23 hour
0 hour
Minute setting
t08
0 min
59 min
0 min
Fault code display
Alarm code display
Status code display
E 1
Fault in controller
A 1
High temperature alarm
S 2
ON-time
E 2
Disconnected room sensor
A 2
Low temperature alarm
S 3
OFF-time
E 3
Short-circuited room sensor
A 4
Door alarm
S 4
Drip-off time
E 4
Disconnected defrost sensor
E 5
Short-circuited defrost sensor
E 6
Change battery