Parameters

EETc 11, 12, 21 and 22

Assignment

Table 4: Assignment

Parameter name

Code

Default

value

Min.

Max.

Description

Assignment

ASi

Sensor Type

NTC10K NTC5K

NTC10K Sensor type (all sensors must be of same type)

NTC5K - NTC 5000 Ohm at 25 °C (Beta value=3980 @ 25/100 °C)

NTC10K - NTC 10000 Ohm at 25 °C (Beta Value 3980 @ 25/100 °C)

S2 Configuration

S2C

EuA

nC

dES

Desired configuration for S2 port

nC - Not used/configured

Con - Condenser Sensor

EuA - Defrost/evaporator Sensor

doC - Door Sensor (Normally closed type)

doo - Door Sensor (Normally open type)

ESP - Eco Switch - Push button type

ESt - ECO Switch - Toggle type

dES - Defrost switch - Push Button type only

Relay 2 Configuration

(applicable only for EETc 2x series)

o2C

dEF

nC

Fan

Desired configuration for relay 2

nC - Not Connected

dEF - Configured for defrost heater or defrost valve

Fan - Configured for evaporator fan

Thermostat

Table 5: Thermostat

Parameter name

Code

Default

value

Min.

Max.

Description

Thermostat

THE

Lowest Temperature Limit (°C)

LSE

0

-100

120

Cut-out temperature at coldest position of the spindle (thermostat knob)

Highest Temperature Limit (°C)

HSE

10

-100

120

Cut-out temperature at warmest position of the spindle (thermostat knob)

Lowest Temperature Differential (K) Ldi

2

1

50

The difference between the cut-out and the cut-in at coldest position of the ther-

mostat.

Highest Temperature Differential (K) Hdi

2

1

50

The difference between the cut-out and the cut-in at warmest position of the ther-

mostat.

Initial pull down ON/OFF

IPE

OFF

OFF

ON

Initial Pull down

OFF - Disable

ON - Enable

Initial Pull Down (IPD) provides faster cooling when the cabinet is powered up with

warmer inside temperature. During IPD, defrost will be skipped until the cabinet air

temperature reaches the cut-out temperature or the IPD duration expires. IPD oper-

ates only during power-up and can be enabled/disabled using this parameter.

Initial Pull down duration (Hrs)

IPD

0

0

120

Maximum time initial pull down can run. Initial pull down will terminate as soon as

this time expires regardless of the cabinet air temperature

Initial pull down initiate tempera-

ture (°C)

Pit

50

-50

120

It indicates the temperature at which initial pull down will be initiated.

• At Power-up: If the cabinet air temp. > Pit for more than 5 minutes, this will trig-

ger the Initial pull down.

Compressor

Table 6: Compressor

Parameter name

Code

Default

value

Min.

Max.

Description

Compressor

COP

Min Run time (Sec.)

Crt

0

0

1800

To prevent the compressor from frequent cut-outs, it ensures that the compressor

runs for at least the specified time. It overrides the cut-out temperature. (Tip: Setting

it too high could lead to unneccessary deep temperatures)

Min Stop time (Sec.)

CSt

120

0

1800

To prevent the compressor from frequent cut-ins, the parameter ensures that the

compressor remains off for at least the specified time under this parameter. It over-

rides the cut-in temperatures. (Tip: Setting it too high could lead to unneccessary

warm temperatures)

© Danfoss | Climate Solutions | 2023.07

BC320944106159en-000301 | 17

Refrigeration controller, type EET series

Summary of Contents for EET Series

Page 1: ...User Guide Refrigeration controller Type EETc and EETa series Enhanced Electronic Thermostat...

Page 2: ...evaporator defrost applicable for EETa only 8 Dual compressor control applicable for EETa only 8 Anti Freeze function applicable for EETa only 9 Quick Test mode 9 Sensor Error handling 9 Potentiomete...

Page 3: ...at 22 Compressor 22 Alarm 22 Defrost 23 Fan 24 Light 24 ECO Strategy 24 Automatic Heater Control 25 System protection 25 Test Mode 26 Service 26 Troubleshooting and Alarms 28 Troubleshooting 28 Alarms...

Page 4: ...compressor refrigerators EETa only Anti freeze applications requiring auto heat control EETa only Applications requiring dual defrost control EETa only Key features Table 1 Key features Key features E...

Page 5: ...This feature protects the compressor from short ON OFF cycles The EET controller ensures that the compressor is switched ON and OFF for a minimum time specified under Minimum run time Crt and Minimum...

Page 6: ...e compressor can keep running and then a second level of condenser temperature beyond which the compressor is switched off until the temperature comes down to an acceptable limit This would help to im...

Page 7: ...r cooling by achieving the required cabinet temperature in the shortest period possible Automatic Pull down applicable for EETa only This feature helps to achieve faster and extra cooling when there i...

Page 8: ...mode Danfoss 80G414 Door Open Door Close Temperature Normal mode Eco delay Edd Holiday Length HoL Eto Hto Normal mode ECO mode Holiday mode Time Dual evaporator defrost applicable for EETa only The EE...

Page 9: ...e controller instantly when connected to an actual application in the OEM Production line or during field service The feature can be used when connected to KoolProg or by using MODBUS commands please...

Page 10: ...a 7 8 5 95 2 1 5 3 95 0 05 M10 x 0 75 83 5 mm 43 5 mm 48 mm 30 5 17 5 16 Danfoss 80G401 M10 x 0 75 is supplied loose Figure 14 Mounting plate dimensionfor EETc and EETa 11 2 Danfoss 80G402 16 mm Recom...

Page 11: ...t signal cables from the cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance Suitably fasten the output connection cables to avoid any unintentional contact...

Page 12: ...a 3W Danfoss 80G407 Evap Sensor Aux Inputs Cab air sensor Condensor Sensor Door Switch External input for pull down External input for ECO External input for defrost 1 2 S1 S2 3 N L 4 Compressor COM S...

Page 13: ...controller due to capillary action Accessories KoolKey KoolKey EKA 200 Acts as a gateway to connect PC tool KoolProg and also a programming key Figure 23 KoolKey EKA 200 as programming key Refer to th...

Page 14: ...structions Bluetooth Adapter EKA 202 EKA 203 Bluetooth Adapter EKA 202 EKA 203 only for EETa controllers External plug in type module that provides wireless connectivity with Danfoss mobile applicatio...

Page 15: ...tive 30k cycles Product dimension Length 79 mm Width 37 5 mm Height 30 5 mm Temperature control Potentiometer with Spindle Number of inputs 2 1 Analogue 1 Analogue Digital Supported sensor types NTC 5...

Page 16: ...30k cycles 2 FLA 12 LRA 30k cycles EN 60730 5 A Resistive 30k cycles Product dimension Length 83 5 mm Width 43 5 mm Height 30 5 mm Temperature control Potentiometer with Spindle Number of inputs 3 1 A...

Page 17: ...position of the ther mostat Initial pull down ON OFF IPE OFF OFF ON Initial Pull down OFF Disable ON Enable Initial Pull Down IPD provides faster cooling when the cabinet is powered up with warmer in...

Page 18: ...frost OFF cycle defrost EL electrical defrost Hgd hot gas defrost Minimum defrost Interval Mins dii 360 1 4320 Defines the minimum time period between the start of two defrost cycles If the evaporator...

Page 19: ...r is ON FPL fan cycling fan cycling during compressor off cycle Fan ON Delay Sec Fod 0 0 240 Time delay to start the fan after compressor cut in Fan Stop Delay Sec FSd 0 0 240 Time delay to stop the f...

Page 20: ...sensor error active only if EHd Set Zero Cross Config ZC Yes No Yes It enhances the relay life and avoids relay sparks during relay ON and OFF If Yes is selected the relays will be switched ON and OFF...

Page 21: ...C PTC PTC 990 S2 Configuration S2C EuA nC dES Desired configuration for S2 port nC Not used configured Con Condenser sensor EuA Defrost evaporator sensor doC Door sensor Normally closed type doo Door...

Page 22: ...prevent the compressor from frequent cut outs it ensures that the compressor runs for at least the specified time It overrides the cut out temperature Tip setting it too high could lead to unneccessar...

Page 23: ...must be terminated The controller will terminate the defrost based on the defrost terminate temperature dtt or Maximum defrost time dAt If no evaporator sensor is used defrost will be terminated base...

Page 24: ...n the evaporator sensor is configured Light Table 20 Light Parameter name Code Default value Min Max Description Light Lig Cabinet Light Control Normal mode CLC ON ON dor ON always ON this button is d...

Page 25: ...nimum Cut in Voltage uLi 100 70 230 The lowest voltage at which the compressor is allowed to cut in Minimum Cut out Voltage uL0 90 70 225 If the voltage goes below this value when the compressor is ru...

Page 26: ...erature C CTO 100 200 Thermostat cut out temperature at current spindle position Cabinet Air temperature C att 100 200 Temperature of Cabinet Air sensor Evaporator 1 temperature C Et1 100 200 Temperat...

Page 27: ...de 10 Energy mode delay Defrost status stages dES 1 4 1 Idle 2 Ice off 3 Drip off 4 Cooling Preperation Defrost interval counter Comp run time Mins InC 0 32767 Defrost interval counter based on accumu...

Page 28: ...nsor fault Check the S1 sensor and sensor alarm status Potentiometer fault Check the controller potentimeter function Frost is not fully melted during defrost Evaporator sensor position not proper Too...