Danfoss ECtemp Touch
7
Installation Guide
Do not place the thermostat in a way that it will be
exposed to direct sunlight.
Note:
A floor sensor enables a more accurate
temperature control and is recommended in all floor
heating applications and
mandatory
under wooden
floors to reduce the risk of over-heating the floor.
• Place the floor sensor in a conduit in an appropriate place
where it is not exposed to sunlight or draft from door
openings.
• Equally distant and >2cm from two heating cables.
• The conduit should be flush with the floor surface -
countersink the conduit if necessary.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min 50mm.