Installation Guide
Ready-made self-limiting cable ECpipeheat 10 V3
08091499 / AN40004190359601-010101
6 | © Danfoss | 2022.01
Product specification
Type
Value
Nominal voltage
230 V~
Nominal output (tolerance)
10 W/m @ 10 °C (7,5-13,5 W/m @ 10 °C )
Max. permissible use temperature, powered
65 °C
Max. permissible use temperature, unpowered
65 °C
Minimum installation temperature
- 5 °C
Max. water temperature (inside water pipe installation)
23 °C
Max. water pressure (inside water pipe installation)
10 bar
Heating cable dimensions
8,75 × 5,15 mm
Outer sheath
HDPE + blue PVDF
Minimum Screen Coverage
100% aluminium foil
Maximum resistance of protective aluminum foil and drain wire
36 Ω/Km
Bending Ø, min.
50 mm (to the inside of the cable)
Cold lead with plug
2 m, 3 х 0,75 mm²
IP Class for ready made unit
IP Class for heating part and end termination
IP67
IP68
Specific heating cable length can be chosen from product range and used for different suitable projects. For more details
contact your local Danfoss sales company.
Note:
In case of cold lead extension it is the full responsibility of the installer/designer to use proper cold lead
dimensioned for the purpose and assembly sets that establish sufficient mechanical strength, flammability resistance
and water proofing - and to design the heating unit with correct output for the specific application to avoid
overheating of the cable or building materials.
Regarding other types of applications please contact your local Danfoss sales company.
More information about applications (maximum linear output, specific output, heating circuit length, voltage etc.) can be
found at
www.danfoss.com