The grey
side of the
ECL Card
Ex
tended ser
vic
e
32l
Service parameter(s) 141
141 Override input selection
Circuit
Setting range
Factory setting
(I) / (II)
OFF / 1 ... 6
(OFF) / (OFF)
Choose an unused temperature sensor input for overriding the
schedule for circuit I and / or circuit II.
The override can be activated for comfort or setback mode.
For override the controller's mode must be in 'scheduled
operation'!
OFF:
The controller's schedule is not overridden.
1 ... 6:
Select an unused sensor input S1 ... S6 for
the override of the circuit in question.
Connection example
If the override switch has gold-plated contacts, you can
choose one of the following solutions:
Closed switch:
Comfort temperature
Closed switch:
Setback temperature
Changeover switch:
Setback or comfort temperature
Connection example with ECA 9010
(used if the override switch does not have gold-plated
contacts).
16 - Brown
15 - Red
Green (S1 ... S6)
The ECA 9010 module is powered by the system device bus, which
means that the bus must be active. The bus is activated by setting
the controller address to 15 (line 199).
Summary of Contents for ECL Comfort C25
Page 4: ......
Page 9: ...Installation 11b...
Page 15: ...Installation...
Page 28: ...The grey side of the ECL Card Basic set up...
Page 53: ...The grey side of the ECL Card Extended service...