Service parameter(s) 12
12 Boost
Circuit
Setting range
Factory setting
(I) / (II)
0 ... 99%
(0) / (0)%
Shortens the heating-up period by increasing the desired flow
temperature by the percentage you set.
Set the percentage at which you want the desired
flow temperature increased temporarily.
In order to shorten the heating-up period after a setback
temperature period, the desired flow temperature can be
increased temporarily (max. 1 hour). At optimizing the boost
is active in the optimization period (line 14).
If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is
connected, the boost stops when the room temperature has
been reached.
The boost also stops at the end of an optimizing period.