Instructions
ECL Comfort 210 / 310, communication description
Table 6-7:
Setting
Value
Address (if DHW is circuit 2)
Day 0-127
12122
Start time
0-47
12123
Duration [m]
10-600
12124
Desired temperature [°C]
9-110
12125
The anti-bacteria function is not active if the frost
protection mode is active.
6.9
Holiday
The address range for holiday settings is from 10700 to 10839.
Table 6-8 shows how a schedule consists of a mode (mode
from Table 6-9 depending on application), a start time (day-
month-year) and an end time (day-month-year) as well as the
addresses to change them. Up to 20 schedules can be defined
but typically less will actually be used depending on the
application. See the application instructions for information
about which holiday schedules belong to the specific circuits.
Table 6-8: Addresses for holiday schedules
Mode Start
day Start
month
Start year
End day
End month
End year
Schedule
P1 10700 10701 10702 10703 10704 10705 10706
Schedule
P2 10707 10708 10709 10710 10711 10712 10713
Schedule
P3 10714 10715 10716 10717 10718 10719 10720
Schedule
P4 10721 10722 10723 10724 10725 10726 10727
…
… … … … … … …
Schedule
P20 10833 10834 10835 10836 10837 10838 10839
Maximum start or end year is 2050
.
Table 6-9: Modes for holiday schedules
Operating mode
Code
Display symbol
Scheduled operation (holiday off)
0
Constant comfort temperature
1
7 – 23h Comfort temperature
2
Constant setback temperature
3
Frost protection / standby
4
/