GENER
AL INFORMA
TION
SY
STEM DESIGN
INTEGR
ATION INT
O SY
STEM
ORDERING INFORMA
TION
PR
ODUC
T INFORMA
TION
Electrical data, connections and wiring
DSH240-295-381*-485*
*except code 3
DSH381 code 3
The terminal box is provided with 2 triple
knockouts and 1 single knockout for power
supply and 4 double knockouts for the safety
control circuit.
The 3 power supply knockouts accommodate the
following diameters:
• Ø 50.8mm (φ 2inch) (UL 1"1/2 conduit) &
Ø 43.7mm (φ 1.72inch) (UL 1"1/4 conduit) &
Ø 34.5mm (φ 1.36 inch) (UL 1" conduit)
• Ø 40.5mm (φ 1.59inch) (ISO40) &
Ø 32.2mm (φ 1.27inch) (ISO32) &
Ø 25.5 mm (φ 1 inch) (ISO25)
• Ø 25.5 mm (φ 1 inch) (ISO25)
The 4 others knockouts are as follows:
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2") &
Ø 16.5mm (φ 0.65inch) (ISO16) (x2)
• Ø 20.7mm (φ 0.81inch) (ISO20 or PG13.5) (x2)
The terminal box is provided with:
•
Ø 50.5mm (φ 1.98inch) (ISO 50 & UL1"1/2
conduit) hole with possible Ø 63.5mm (φ 2.5inch)
(ISO63 and UL 2"conduit) knockout for power
supply
•
2 x Ø 22.5mm (φ 0.89inch) (PG16 and UL ½"
conduit) knockouts for safety control circuit.
Power supply
Power supply
Black
Sump heater
Cover holding screws (x3) · Torque 2.2 Nm
Blue Brown
M1, M2
Control circuit
Terminal box
Black
Blue
Brown
Faston 1/4" tabs
Power supply
Sump heater
Module
power supply
M1-M2
Control circuit
M1-M2 control circuit
Power supply
Power supply
Power supply
The terminal box is provided with 2 triple
knockouts for power supply, 2 double knockouts
and 3 simple knockouts for the safety control
circuit.
The 2 power supply knockouts accommodate the
following diameters:
• Ø 63.5mm (φ 2.5inch) (ISO63 and UL 2"conduit)
& Ø 54.2mm (φ 2.13inch) (PG42)& 43.7mm (UL
1"1/4 conduit)
The 5 other knockouts are as follows:
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2") &
Ø 16.5mm (φ 0.65 inch) (ISO16)
• Ø 25.5mm (φ 1inch) (ISO25) &
20mm (φ 0.79inch) (ISO20 or PG13.5)
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2")
• Ø 25.5mm (φ 1inch) (ISO25) (x2)
DSH485 code 3
The motor protection modules come preinstalled
within the terminal box. Phase sequence
protection connections and thermistor
connections are pre-wired and should not be
removed. The module must be connected to a
power supply of the appropriate voltage. The
module terminals are 6.3mm (0.25inch) size
Faston type.
L N S1 S2 M1 M2
L1 L2 L3
Black Blue Brown
Phase sequence input
Internal control contact
Safety
circuit
Thermistor
connection
Module power
16
FRCC.PC.045.A7.02
Summary of Contents for DSH Series
Page 2: ......