background image

14

 VMIFI102

13  Stop both the pumps and immediately close valve 1 

and 2.

14  Open valve 3 and disconnect the filling hoses.
15  Open valve 6 and pressurise the system, and vent via 

valve 1. Pressurise to max 1.5 bar. 

16  Close valve 6.
17  Set switch S1 and S2 to Auto  

(compressor and brine pump).

18  Clean the strainers after filling. 

Start up

 

 

The installation may only start operation if the heat-

ing system, any hot water tanks and the coolant 
circuit are filled. Otherwise the pumps can be dam-
aged.

In addition, the following points must be checked before 
starting operations:

•  Check the rotation direction of the coolant pump. This is 

most easily done by setting switch S2 to manual. There 
is an indicator lamp, under the cover of the coolant 
pump connection terminal box, which lights when the 
rotation direction is correct. 

•  Check that all connections are sealed.
•  Check the compressor’s direction of rotation by start

-

ing the compressor and feel by hand if the pressure line 
(upper pipe) is warm and the suction line (lower pipe) is 
cold.

•  If this is not the case, two of the phases in the power 

supply must be switched (for example L1 and L3).

•  Adapt the factory settings to the customer require

-

ments.

8.1 

Installing the front cover

 

 

Take care not to damage the front cover!

Install the front cover as follows:

•  Align the upper section of the front cover (2) in both the 

side channels on the unit and slide it carefully down-
wards until it covers the entire front side.

•  Tighten the screws (1).

1

2

Summary of Contents for DHP-R Eco

Page 1: ...VMIFI102 Installation instructions Danfoss heat pump DHP R Eco...

Page 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Page 3: ...ng hot water sensor 12 6 5 Connecting sensor for system supply temperature 12 6 6 Connecting external start brine pump passive cooling option 12 6 7 Connecting exchange valve for hot water 12 6 8 Conn...

Page 4: ......

Page 5: ...ion because of lack of oxy gen Spaces in which heavy vapour can collect below the level of the air must therefore be well ventilated Refrigerant exposed to a naked flame creates a poi sonous irritatin...

Page 6: ...al connection must be adhered to the inside of the door Electrical current The terminal blocks are live and can be highly dan gerous due to the risk of electric shock The power supply must be isolated...

Page 7: ...ead in for communication cable 8 Lead in for incoming supply and sensor 9 Supply pipe sensor 10 Condenser with draining for prim side 11 Return sensor 13 Compressor 14 Instrument panel 15 Electrical c...

Page 8: ...gas exchanger 4 Supply line hot gas exchanger 5 Heat supply supply line 6 Coolant in to HP 2 3 Required service space To facilitate installation and later tests and maintenance there must be sufficien...

Page 9: ...es 2 are centred in the insert pipes 1 so that the insulation is distributed equally on all sides Seal the insert pipes 1 with a suitable sealant foam 4 4 Unpacking and installation The heat pump is p...

Page 10: ...e must be routed in a continuous incline A continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point 5 2 Heating system supply pipe and return pipe Install...

Page 11: ...erheating protection compressor F3 Control fuse condensation pump F100 Fuse 24 VAC 1 F101 Fuse 24 VDC F102 Fuse 24 VAC 2 X1 Terminal blocks for incoming supply and tempera ture sensor as well as termi...

Page 12: ...liary modules The two separate 24 VAC circuits must never be con nected to each other or to protective ground The total power load on 24 VAC 1 respectively 24 VAC 2 must not exceed 50VA 6 9 Connecting...

Page 13: ...n vessel for the coolant is sized according to the manufacturer s instructions Max operating pressure heat source see manufacturer s plate Max 6 bar 7 2 Filling the coolant system WARNING Ethylene gly...

Page 14: ...ly done by setting switch S2 to manual There is an indicator lamp under the cover of the coolant pump connection terminal box which lights when the rotation direction is correct Check that all connect...

Page 15: ...ing carried out by As user please ensure that the installer fills in the following information to facilitate servicing PIPE INSTALLATION Date Company Name Tel No ELECTRICAL INSTALLATION Date Company N...

Page 16: ...refrigerant No refilling of drai ned medium Blocked or filled drying filter in the cooling circuit Measure the temperature difference of the filter max 2 C HIGH PRESS ERROR High pressure error The co...

Page 17: ...eat transfer fluid bar bar 6 6 6 6 6 6 6 6 Min max temperature5 Cooling circuit C 20 10 20 10 20 10 20 10 Heating circuit6 C 65 20 65 20 65 20 65 20 Pressure switches Low pressure Operating MPa MPa 0...

Page 18: ......

Page 19: ......

Page 20: ...umps AB Box 950 SE 671 29 Arvika www danfoss com If these instructions are not followed during installation operation and maintenance Danfoss Heat Pumps liability according to the applicable warranty...

Reviews: