background image

11

VMIFI102

Electrical Installation

6.1 

Electrical connection

 

 

The electrical installation must only be carried out by 

an authorized electrician (and must follow applicable 
local and national regulations). The electrical instal-
lation must be carried out using permanently routed 
cables. It must be possible to isolate the power sup-
ply using an all-pole circuit breaker for the intended 
current. For information regarding maximum load 
for externally connected devices. see electrical instal-
lation instructions.

Electrical current!

 

 

The terminal blocks are live and can be highly dan-

gerous due to the risk of electric shock. The power 
supply must be isolated before electrical installation 
is started. The heat pump is internally connected 
at the factory. The electrical installation therefore 
mainly covers the following points:

Connection to the power supply

•  Remove the front cover from the heat pump.
•  Pull the power supply cable through the opening in the 

rear of the heat pump to the terminal blocks.

•  Connect the supply cable to the designated terminal 

block.

See separate manual for the control system.

 

 

Note that the power supply cable must only be con-

nected to the intended terminal block. No other ter-
minal blocks may be used!

Electrical cabinet layout

K1 

Contactor compressor

K2 

Contactor brine pump

F10  Over current relay compressor.
F11  Over current relay brine pump
F1 

Fuse brine pump

F2 

Control fuse regulation. overheating protection 

compressor

F3 

Control fuse condensation pump

F100  Fuse 24 VAC 1
F101  Fuse 24 VDC
F102  Fuse 24 VAC 2
X1 

Terminal blocks for incoming supply and tempera-

ture sensor as well as terminal blocks for external 
components

T1 

Transformer 24 VAC 2x50 VA

E1 

WM HPC

E2 

HPC RM

6.2 

Connecting pump hot gas

Connect the hot gas pump to the designated terminal 
block. The voltage is 230 VAC. The pump is designed to be 
placed outside the heat pump casing and must be con-
nected with flexible hoses. 
This pump runs in parallel with the compressor.

6.3 

Connecting sensor for outside temper-
ature

Position the outdoor sensor on the north or north west 
facing side of the house. away from direct sunlight. The 
outdoor sensor should not be placed on reflective panel 
walls. The sensor must be positioned at least 1 m from 
openings in the walls that emit hot air. 
If the sensor cable is connected through a pipe. the pipe 
must be sealed so that the sensor is not affected by out-
going indoor air. 

•  Remove the rear piece from the heat pump.
•  Route the outdoor sensor’s connecting cable through 

the opening in the rear of the heat pump up to the con-
necting block.

•  Connect the sensor to the designated terminal block.

 

See separate manual for the control system.

 

 

Note that the outdoor sensor is connected with 

extra low protection voltage.

Also follow the applicable installation instructions for out-

door sensors!

NOTE! The bridge is 

removed in the event 

of separate control 

circuit.

Bridged at delivery

Incoming cable

Incoming cable control circuit

T1

E1

E2

F1

F2

F3

F100

F101

F102

K2

K1

F11

F10

X1

Sensor outdoor

PT1000

Pump hot gas

Summary of Contents for DHP-R Eco

Page 1: ...VMIFI102 Installation instructions Danfoss heat pump DHP R Eco...

Page 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Page 3: ...ng hot water sensor 12 6 5 Connecting sensor for system supply temperature 12 6 6 Connecting external start brine pump passive cooling option 12 6 7 Connecting exchange valve for hot water 12 6 8 Conn...

Page 4: ......

Page 5: ...ion because of lack of oxy gen Spaces in which heavy vapour can collect below the level of the air must therefore be well ventilated Refrigerant exposed to a naked flame creates a poi sonous irritatin...

Page 6: ...al connection must be adhered to the inside of the door Electrical current The terminal blocks are live and can be highly dan gerous due to the risk of electric shock The power supply must be isolated...

Page 7: ...ead in for communication cable 8 Lead in for incoming supply and sensor 9 Supply pipe sensor 10 Condenser with draining for prim side 11 Return sensor 13 Compressor 14 Instrument panel 15 Electrical c...

Page 8: ...gas exchanger 4 Supply line hot gas exchanger 5 Heat supply supply line 6 Coolant in to HP 2 3 Required service space To facilitate installation and later tests and maintenance there must be sufficien...

Page 9: ...es 2 are centred in the insert pipes 1 so that the insulation is distributed equally on all sides Seal the insert pipes 1 with a suitable sealant foam 4 4 Unpacking and installation The heat pump is p...

Page 10: ...e must be routed in a continuous incline A continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point 5 2 Heating system supply pipe and return pipe Install...

Page 11: ...erheating protection compressor F3 Control fuse condensation pump F100 Fuse 24 VAC 1 F101 Fuse 24 VDC F102 Fuse 24 VAC 2 X1 Terminal blocks for incoming supply and tempera ture sensor as well as termi...

Page 12: ...liary modules The two separate 24 VAC circuits must never be con nected to each other or to protective ground The total power load on 24 VAC 1 respectively 24 VAC 2 must not exceed 50VA 6 9 Connecting...

Page 13: ...n vessel for the coolant is sized according to the manufacturer s instructions Max operating pressure heat source see manufacturer s plate Max 6 bar 7 2 Filling the coolant system WARNING Ethylene gly...

Page 14: ...ly done by setting switch S2 to manual There is an indicator lamp under the cover of the coolant pump connection terminal box which lights when the rotation direction is correct Check that all connect...

Page 15: ...ing carried out by As user please ensure that the installer fills in the following information to facilitate servicing PIPE INSTALLATION Date Company Name Tel No ELECTRICAL INSTALLATION Date Company N...

Page 16: ...refrigerant No refilling of drai ned medium Blocked or filled drying filter in the cooling circuit Measure the temperature difference of the filter max 2 C HIGH PRESS ERROR High pressure error The co...

Page 17: ...eat transfer fluid bar bar 6 6 6 6 6 6 6 6 Min max temperature5 Cooling circuit C 20 10 20 10 20 10 20 10 Heating circuit6 C 65 20 65 20 65 20 65 20 Pressure switches Low pressure Operating MPa MPa 0...

Page 18: ......

Page 19: ......

Page 20: ...umps AB Box 950 SE 671 29 Arvika www danfoss com If these instructions are not followed during installation operation and maintenance Danfoss Heat Pumps liability according to the applicable warranty...

Reviews: