9.5
Default settings
The default DHW temperature is set to 50°C.
The following table shows the other default settings in the control system:
Menu Description
Default value
Range
00
Auto heating curve (value 43 relates to the number of the curve and
has no units of measure, A indicates that it is in automatic mode only)
A43
A24—50
01
Initial (desired) room temperature
20 °C
15—25 °C
02
House heating mode
1
1=Auto
0=Manual
03
Defrosting cycle
40 min
30—90 min
04
Coil temperature threshold for starting defrosting
-6 °C
From -20 °C to +5 °C
05
Coil temperature threshold for stopping defrosting
13 °C
1—30 °C
06
Maximum defrosting period
12 min
1—12 min
07
Domestic hot water hysteresis setting (i.e. number of degrees below
set point where the DHW will start again)
5 °C
1—20 °C
08
Heating hysteresis setting (i.e number of degrees below set point
where the heating will start again)
2 °C
1—20 °C
09
Overheating of electronic expansion valve in heating mode
2 °C
From -20 °C to +20 °C
10
Overheating of electronic expansion valve in cooling mode
3 °C
From -20 °C to + 20 °C
11
Time delay for compressor start-up after power-up (for example, after
a power cut-off)
1 min*
1—10 min
12
Circulation pump operation mode
1
1=Switched off when heating temper-
ature has been reached.
0=Continuous operation
13
Internal electrical heater operation during defrosting
1
1= Turned on
0=Turned off
14
Automatic legionella protection function
1
1=Activated
0=Deactivated
15
Internal electrical heater start option
0
0=Auto
1=Air-temperature condition set in
menu 16
2=Water temperature condition set in
menu 17
3= Conditions 1 and 2 must be met
16
Air temperature restriction for when internal electrical heater can
manually be started, that is, must be lower than this value.
-5 °C
From -15 °C to +7 °C
17
Additional hysteresis in relation to menu 08 for when internal electri-
cal heater can manually be started.
2 °C
0—13 °C
18
Additional temperature hysteresis for hot water tank electrical heater
in relation to menu 07 for when the electrical heater will start.
5 °C
0—20 °C
19
Hot water tank electrical heater startup delay
30 min
30—90 min
20
Return water temperature
Measured value From -30 °C to +99 °C
21
Supply water temperature
Measured value From -30 °C to +99 °C
22
Coil temperature in heating mode (T7)
Measured value From -30 °C to +99 °C
23
Coil temperature in cooling mode (T8)
Measured value From -30 °C to +99 °C
24
Air temperature (T1)
Measured value From -30 °C to +99 °C
25
Hot water tank temperature (T3)
Measured value From -30 °C to +99 °C
26
Buffer tank temperature (T2)
Measured value From -30 °C to +99 °C
27
Return gas temperature of compressor (T5)
Measured value From -30 °C to +99 °C
28
Exhaust gas temperature of compressor (T4)
Measured value From -30 °C to +99 °C
29
Shows the number of the operation steps for the expansion valve
Measured value 100—480 steps
Installation Guide
DHP-AT
Danfoss Heating Solutions
VMGFI302
29
Summary of Contents for DHP-AT
Page 37: ...12 Circuit diagram Installation Guide DHP AT Danfoss Heating Solutions VMGFI302 37...
Page 38: ...Installation Guide DHP AT VMGFI302 Danfoss Heating Solutions 38...
Page 39: ...Installation Guide DHP AT Danfoss Heating Solutions VMGFI302 39...
Page 40: ...13 Connection diagram Installation Guide DHP AT VMGFI302 Danfoss Heating Solutions 40...
Page 41: ...Installation Guide DHP AT Danfoss Heating Solutions VMGFI302 41...
Page 42: ...Installation Guide DHP AT VMGFI302 Danfoss Heating Solutions 42...
Page 43: ...Installation Guide DHP AT Danfoss Heating Solutions VMGFI302 43...