background image

Cause

Troubleshooting

Remedy

6. The compressor runs

backwards.The incoming

phases have the incorrect

sequence (only applies to 3-

phase heat pumps).

If the compressor runs back-

wards, it will not cope with

compressing the refrigerant

and therefore does not pro-

duce the correct power,

which leads to the control

system requesting auxiliary

heating.

If the text ERR PHASE SEQ. appears in the display

when the heat pump is powered, (only appears in the

first 10 minutes) this means that the phases have the

incorrect sequence.

When the compressor is running, check the pressure

pipe temperature by feeling the pressure pipe. If the

phases are correctly sequenced it should be hot (not

just warm) even a distance from the compressor.

When the compressor runs with the phases incorrect-

ly sequenced a strange noise may be heard (loud, rat-

tling) when the compressor runs backwards.

If the phases are in the incorrect order,

switch two incoming phases at the main

terminal block and recheck according to

the troubleshooting window.

7. Changed conditions Have

you increased your heating

and/or hot water demand?

If the heat pump has been dimensioned for a certain

demand and this demand is increased, the heat pump

might not be able to maintain the desired room tem-

perature.

If hot water consumption increases, a larger propor-

tion of time is used to produce hot water, which

means less time for heat production.

If the heat pump cannot cope with the de-

mand, replace it with one with a higher

output or supplement it with a higher out-

put auxiliary heater.

Problem – The auxiliary heater is in operation but not the compressor

Cause

Troubleshooting

Remedy

1. Operating mode AUX.

HEATER is selected.

If this operating mode is selected, the auxiliary heater is

used for heating and hot water production, not the com-

pressor.

If AUX. HEATER mode is selected and you

no longer want it, change to AUTO, the

heat pump then controls both the com-

pressor and auxiliary heater.

2. Peak heat operation (anti-

legionella function) is run-

ning.

Check if the heat pump runs peak heat.

Peak heat operation occurs in connection

with hot water production with the set in-

terval. The compressor should then start to

produce hot water and 2 minutes later the

auxiliary heater starts. The compressor

must then stop and the stop temperature

be reached with only the auxiliary heater

connected. Take no corrective action, this is

normal.

3. The compressor cannot

run due to an alarm.

Check the alarm that is indicated in the display.

Rectify the problem and rest the alarm.

4. The heat pump has stop-

ped on high return.

Check what the MAX value is set at in the heat pump’s

control computer. It must be adjusted to the unit’s

maximum supply temperature and the system’s delta

temperature so that it does not cut at too high a re-

turn temperature when the highest supply tempera-

ture is transmitted.

Check what the return line sensor shows. Is it a plausi-

ble/actual value? If not, take a resistance reading from

the sensors and check against the ohm table in Meas-

urement points .

If the MAX RETURN value is not adjus-

ted for the system according to the

troubleshooting window, adjust it.

If the sensor is defective, replace it.

Service Instructions

DHP-AQ

Danfoss Heating Solutions

VMGFJ202

29

Summary of Contents for DHP-AQ Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Service Instructions DHP AQ www heating danfoss com...

Page 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Page 3: ...mation Safety regulation 6 2 1 General safety precautions 6 2 2 Refrigerant 7 2 3 Electrical connection 8 2 4 Water quality 8 2 5 Commissioning 9 3 Troubleshooting 10 3 1 Alarm 10 3 2 Components 11 3...

Page 4: ...lation Supplied with the heat pump on delivery The Service instructions and Wiring diagrams are available for download here www documentation heatpump danfoss com 1 2 Symbols in documents The instruct...

Page 5: ...alve 304 Circulation pump 363 Exchange valve hot water 365 Supply line sensor 366 Return line sensor 406 or 62 Room sensor 408 EVU 417 Defrost sensor Explanation Component ordinary delivery according...

Page 6: ...om a safety qualified person Caution The heat pump must be located in a frost free environment Caution The heat pump must be placed in an area with a floor drain Caution The heat pump must be located...

Page 7: ...ied engineer Although the heat pump cooling system refrigerant circuit is filled with a chlorine free and environmentally approved refrigerant that will not affect the ozone layer work on this system...

Page 8: ...by an authorized electrician and must follow applicable local and national regulations Caution The electrical installation must be carried out using permanently routed cables It must be possible to is...

Page 9: ...culation pumps can be damaged Caution If the installation is only to be driven by the immersion heater during the installation ensure that the heating system is filled and the brine pump and compresso...

Page 10: ...PPLY LINE SENSOR Sensor fault alternatively cable fault System supply line sensor RETURN LINE SENSOR Sensor fault alternatively cable fault Return line sensor HIGH RETURN LINE TEMP Return line tempera...

Page 11: ...condarily with the auxiliary heater Hot water will stop to indicate that something noteworthy has occurred 3 2 Components 3 2 1 Outdoor unit 11 10 12 13 14 16 15 17 1 2 3 4 5 6 7 8 9 19 18 Fig 1 Compo...

Page 12: ...5 DHP AQ Maxi 1 Control module transparent in image 2 Immersion heater 3 Reversing valve 4 Circulation pump 5 Water heater 3 3 Measurement points Caution When reading the resistance of the sensors the...

Page 13: ...50 1194 8 5 55 7 1 60 1232 6 0 65 5 0 70 1271 4 2 75 3 7 80 3 1 85 2 7 3 3 1 Measurement checking sensors during fault tracing 1 Disconnect the relevant sensor from I O card terminal block 2 Measure t...

Page 14: ...orth 7 SUPPLY LINE SENSOR 8 HOT WATER TOP 9 HOT WATER SENSOR RETURN LINE SENSOR Located on return pipe that runs to heat pump See sys tem solution in the Installation instructions 3 4 Check points Tem...

Page 15: ...ist the most probable and common causes of the problem first When troubleshooting the cause of a problem start with the first cause and go down the list There may be more than one way of troubleshooti...

Page 16: ...that the circulation pump is active in the control system s manual test menu Check if there is voltage to the circulation pump if there is and it does not run the circulation pump is jammed If this i...

Page 17: ...be adjusted according to the system solution for large pressure drop 12 Blocked condenser on the water side If there is no strainer in the heating system there is a risk of dirt sticking in the conden...

Page 18: ...place it If incorrectly set adjust to the correct value 6 Defective compressor Measurement check the voltage on the phase s each to zero at the compressor There must not be any large devi ation betwee...

Page 19: ...5 No or insufficient circula tion in the heating system Check That the circulation pump spins That the shut off valves are open That the strainer is not blocked That there is no air in the heating sy...

Page 20: ...e of the dis charge pipe 140 C 4 Lack of refrigerant not enough refrigerant in the system Using manometer apparatus and thermometer check that the unit s overheating is correct for the specific refrig...

Page 21: ...e instruc tions Install flexible hoses according to the in structions 3 Installing suspending pipes Check if vibrations are transmitted via one of the pipe mountings in the installation Remove or move...

Page 22: ...s Replace the compressor if the valve opens at too low pressure or when the compres sor is stationary Problem Noise miscellaneous Cause Troubleshooting Remedy 1 Vibrating protective sleeves on the pre...

Page 23: ...n the service output Schrader valve 9 Insufficient exchange sur face to transfer the heat pump s output to the heat er Only applies to heat pumps with a separate heat er Is the exchange surface too sm...

Page 24: ...electric heating element Use a buzzer and check if all coils in the electric heating el ement are intact If the electric heating element is defective replace it 6 The heat pump has stop ped on HIGH RE...

Page 25: ...valves 11 The total output of the heat pump and auxiliary heater is too low in relation to the building s power de mand What is the building s power demand What is the output of the heat pump What is...

Page 26: ...ve mo tor The motor should set the valve to the relevant posi tion depending on operat ing conditions If it does not hot water from the water heater will mix with the radi ator water Check the functio...

Page 27: ...ess of the outdoor tempera ture CURVE5 0 5 The supply temperature can be adjusted up or down 5 C at these out door temperatures HEAT STOP Stops all production of heat when the outdoor temperature is t...

Page 28: ...If AUX HEATER mode is selected and you no longer want it change to AUTO the heat pump then controls both the com pressor and auxiliary heater 2 The compressor cannot run due to an alarm Check the ala...

Page 29: ...put auxiliary heater Problem The auxiliary heater is in operation but not the compressor Cause Troubleshooting Remedy 1 Operating mode AUX HEATER is selected If this operating mode is selected the au...

Page 30: ...e temperature by feeling the pressure pipe If the phases are correctly sequenced it should be hot not just warm even a distance from the compressor When the compressor runs with the phases incorrect l...

Page 31: ...he phases are in the incorrect order switch two incoming phases at the main terminal block and recheck according to the troubleshooting window 8 The compressor has been stopped by the operating pressu...

Page 32: ...the heat pump cannot cope with the de mand replace it with one with a higher output or supplement it with a higher out put auxiliary heater 3 Lack of refrigerant not enough refrigerant in the system U...

Page 33: ...d that it is correctly calibrated Calibrate if necessary Problem Build up of ice under and around the outdoor unit Cause Troubleshooting Remedy Insufficient drainage Does a lot of ice accumulate under...

Page 34: ...Service Instructions DHP AQ VMGFJ202 Danfoss Heating Solutions 34...

Page 35: ...Service Instructions DHP AQ Danfoss Heating Solutions VMGFJ202 35...

Page 36: ...rves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifica...

Reviews: