Danfoss – 32
VUBMF102
6 .7
Cleaning the strainer for the brine circuit
⚠
⚠
⚠
The heat pump must be switched off at the main switch before cleaning can be started.
The brine circuit’s strainer must be cleaned twice a year after installation. The interval
⚠
⚠
can be extended if there is evidence that cleaning twice a year is not necessary.
Figure 16: Strainer in the filler cock .
To clean the strainer:
1 Switch off the heat pump.
2 Remove the insulation around the filler cock.
3 Turn both shut-off cocks to the closed position (see figure above).
4 Unscrew the cover and remove it.
5 Remove the strainer.
6 Rinse the strainer.
7 Reinstall the strainer.
8 Check that the o-ring on the cover is not damaged.
9 Screw the cover back into place.
10 Turn both shut-off cocks to the open position.
11 Reinstall the insulation around the filler cock.
12 Start the heat pump.
Shut-off valve
Shut-off valve
Strainer
O-ring
Cover
Summary of Contents for DHP-AL
Page 2: ......
Page 40: ...Danfoss 40 VUBMF102...
Page 41: ...Danfoss 41 VUBMF102...
Page 42: ...VUBMF102...