Technical data, DHP-AL
Table 53.
Technical data
DHP-AL
6
8
10
12
Type
Air/water
Refrigerant
Type
R404A
Amount
kg
0,95
1,45
1,50
1,60
Test pressurisation
MPa
3,4
Design pressure
MPa
3,1
Compressor
Type
Scroll
Oil
POE
Electrical data
3-N ~50Hz
Mains power supply V
400
Rated output, com-
pressor
kW
3,0
3,2
4,2
5,0
Rated output,
circ.pumps/fan
kW
0,4
0,6
0,6
0,7
Auxiliary heater, 5
step
kW
3/6/9/12/15
Start current
16
A
12
10
18
17
Fuse
A
10
3
/16
4
/20
5
/20
6
/
25
7
/25
14
/30
15
16
3
/16
4
/20
5
/20
6
/
25
7
/25
14
/30
15
16
3
/16
4
/20
5
/20
6
/
25
7
/30
14
/35
15
16
3
/20
4
/25
5
/25
6
/
25
7
/30
14
/35
15
Electrical data
1-N ~50Hz
Mains power supply V
230
Rated output, com-
pressor
kW
3,2
3,6
4,5
5,5
Rated output,
circ.pumps/fan
kW
0,4
0,6
0,6
0,7
Auxiliary heater, 3
step
kW
1,5/3,0/4,5
Start current
16
A
11
21
26
28
Fuse
A
25
3
/32
4
/40
5
25
3
/32
4
/40
5
32
3
/40
4
/50
5
32
3
/40
4
/50
5
Performance
10
Heat factor
1
kW
5,00
7,02
8,20
9,84
COP
1
2,85
3,10
2,85
3,00
Heat factor
2
kW
5,90
7,96
9,85
11,3
COP
2
3,26
3,45
3,29
3,35
Incoming power
2
kW
1,8
2,3
3,0
3,4
Nominal flow
8
Cooling circuit
l/s
0,32
0,49
0,58
0,64
Heating circuit
l/s
0,14
0,20
0,24
0,28
External available
pressure
9
Cooling circuit
kPa
46
83
69
95
Heating circuit
kPa
45
43
40
51
Lowest outdoor
temperature for
compressor start
°C
-20
Max/Min tempera-
ture
Cooling circuit
°C
20/-25
Heating circuit
°C
55/20
Pressure switches
Low pressure
MPa
0,08
Operation
MPa
2,65/2,85
High pressure
Mpa
3,10
80 – Service instructions VMGFC302