User Guide
|
Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
12 | RS8KD102
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
4.5.2
Language
Language
English
Selection of the menu language (password
protected)
Symbol
Description
Default
Function
English
Language
English
English
USA English
German
French
Spanish
4.5.3
LCD Function Check
Function for testing the LCD function (password protected)
All LEDs light up for about two seconds. The backlight is
yellow. (Green and red are activated at the same time). All
points are displayed on the LCD
LCD Function
check ?
4.6
Measuring Point Parameters
Reading and changing of the parameters for each
measuring point.
MP Parameters
MP 1
Active
Selection of measuring point (1 – X)
Symbol
Description
Default
Function
0 sec.
Delay Alarm
0 sec
Gas concentration > alarm thr set time = Alarm ON
Gas concentration < alarm threshold – hysteresis = Alarm OFF
Warning limit
C 5000 ppm
4.6.1
Alarm limits
For each measuring point two alarm thresholds
are available for free definition. If the gas
concentration is higher than the set alarm
threshold, the associated alarm is activated. If the
gas concentration falls below the alarm threshold
inclusive hysteresis the alarm is reset again.
The hysteresis of both alarm is 5% of the default
alarm threshold (e.g. with 5000pmm this
corresponds to 250ppm)
Critical limit
C 5000 ppm
4.6.2
Alarm delay
Delay Alarm ON
0 s
For setting the alarm delay for Critical and
Warning alarms