Installation Guide
Ready-made self-limiting cable DEVIpipeheat™ 10 V3
5
Thermostats/controllers
Pipe frost protection
Tank frost protection
DEVIreg™ 330
DEVIreg™ 610
DEVIreg™ Multi
The DEVIreg™ thermostat/controller must be commissioned as prescribed in the installation instruction for the actual controller
and adjusted where local conditions vary in relation to factory settings Before every heating season or at least once per year,
check for faults in the switchboard, thermostat and sensors
Each heating cable screen must be earthed in accordance with local electric regulations and connected to a residual current
device (RCD)
The heating cables must be temperature controlled and not operate at ambient temperature higher than 5 °C
More information about thermostats and controllers can be found at
www.devi.com.
Sensors:
• Sensors can be live (230 V) components and must be treated according to specific Installation Guide and local standards
• Sensors can be extended using cable with the same cable construction and cross sections (up to 50 m)
• See section 7 for specific installations
1
2
3
4
5
1 - Controller; 2 - DIN-rail; 3 - Electric cabinet; 4 - Cold lead connection; 5 - Sensor connection
7