Installation Guide  

 

Self-limiting cables on drum

Introduction

In this installation guide, the phrase “heating cable” refers to 

self-limiting cables on drums

To get the full installation guide,  warranty registration, 

product  information, tips & tricks, addresses,  etc  

visit 

www.devi.com

Safety instructions

Heating cables must always be installed according to local 

building regulations and wiring rules as well as the guidelines 

in this installation manual

•  De-energize all power circuits before installation and service 

•  Residual current device (RCD) protection is required RCD trip 

rating is max 30 mA

•  The screen from each heating cable must be connected to 

earthing terminal in accordance with local electricity regulations 

•  Heating cables must be connected via a switch providing all 

pole disconnection 

•  The heating cable must be equipped with a correctly sized 

fuse or circuit breaker according to local regulations

•  Never exceed the maximum heat density (W/m or W/m²) for 

the actual application Refer to Application Guide

•  Heating cable must be used together with an appropriate 

thermostat to secure against overheating and reduce energy 

consumption

The presence of a heating cable must

•  Be made evident by affixing caution signs in the fuse box 

and in the distribution board or markings at the power 

connection fittings and/or frequently along the circuit line 

where clearly visible (tracing)

•  Be stated in any electrical documentation following the 

installation

For use with sprinkler systems 

•  The alarm output shall be connected to and monitored by 

the fire detection alarm system

•  Systems shall be permanently connected to the power supply

•  Minimum ambient temperature shall not be less than -5°C

•  If backup power is being provided for the building electrical 

systems, it shall also provide backup power supply for the 

trace heating system

•  Heating system for sprinkler systems should be indicated 

by "for supply piping and branch lines including sprinkler 

heads"

Installation guidelines

•  It is not recommended to install heating cables at tempera-

tures below -5°C

•  Heating cable bending diameter must be at least 10 times 

the cable diameter (to the inside of the cable)

•  Do not bend connections

•  Free end from cold lead and kit components must be 

protected by installer to avoid water from coming in

•  Ensure that the cable is sufficiently fixed and mounted 

according to the installation guide 

•  The heating cables must be temperature controlled 

•  Ensure controllers and sensors are connected according to the 

applicable installation guide and/or application guide

•  Measure, verify and record insulation resistance during 

installation

•  Persons involved in the installation and testing of electrical 

trace heating systems shall be suitably trained in all special 

techniques required Installations are intended to be carried 

out under the supervision of a qualified person

Application overview

Pipe tracing

Tank frost 

protection

Sprinkler 

systems

Domestic hot 

water

Roof and 

gutter

DEVIpipeguard™ LSZH (T)

DEVIpipeguard™ (B)

DEVIpipeguard™ Industry

DEVIhotwatt™ (B)

DEVIiceguard™ (T)

DEVIiceguard™ (B)

Heating cables can be customized for the specific project, depending, length of heating cable and length of cold leads  

DEVIiceguard™ heating cables should not be in direct contact with bitumen For more details contact your local DEVI sales company

Note:

 It is the full responsibility of the installer/designer to use proper cold lead dimensioned for the purpose and assembly 

sets that establish sufficient mechanical strength, flammability resistance, UV resistance and water proofing - and to design 

the heating unit with correct output for the specific application to avoid overheating of the cable or building materials

Regarding other types of applications please contact your local DEVI sales company.

More information about applications (maximum linear output, specific output, heating circuit length, voltage etc) can be found 

at 

www.devi.com

3

DEVI AN384935621519en-010101

Summary of Contents for DEVIpipeguard LSZHT

Page 1: ...Installation Guide Self limiting cables on drum Installation Guide Self limiting cables on drum Intelligent solutions with lasting effect Visit DEVI com EN ...

Page 2: ...llation guidelines 4 4 Application overview 4 5 Thermostats controllers 5 6 Accessories 6 6 1 Fixing elements 6 6 2 Connection kits 7 7 Typical installations 10 7 1 Typical pipe tracing installation 10 7 2 Typical roof protection installation 11 8 Standard compliance 12 9 Warranty 12 AN384935621519en 010101 DEVI 2 ...

Page 3: ... should be indicated by for supply piping and branch lines including sprinkler heads 3 Installation guidelines It is not recommended to install heating cables at tempera tures below 5 C Heating cable bending diameter must be at least 10 times the cable diameter to the inside of the cable Do not bend connections Free end from cold lead and kit components must be protected by installer to avoid wate...

Page 4: ...local electric regulations and connected to a residual current device RCD The DEVIreg thermostat must be commissioned as prescribed in the thermostat manual Recommended temperature setting is according to Application Guide or Installation Guide More information about thermostats and controllers can be found at www devi com Sensors Sensors can be live 230V components and must be treated according t...

Page 5: ... 1 Fixing elements DEVIclip Roof Hook For fixing cables to roofing screws UV protected DEVIclip Guard Hook For fixing cables to the snow guard and roof edge UV protected DEVIclip Relief For relieving cables hanging in downpipes Spaceclip For attaching cables and relieving from sharp edges DEVIfast Double For fixing cable loops in downpipes DEVI Aluminium Tape For ensuring efficient heat transfer 5...

Page 6: ...cting two heating cables DEVIconnecto B T Heating cable T branch as a T junction for three heating cables and 1 end terminal DEVIconnecto B TE2 Heating cable double connection with 1 5 m power cable and 2 end terminals DEVIconnecto B TE3 Heating cable T branch with 1 5 m power cable and 3 end terminals DEVIconnecto B X Heating cable X branch for 4 heating cables incl 2 end terminals DEVIconnecto B...

Page 7: ...pply assembly view heating cable DEVI EasyConnect EC 2 Power supply connection set for 2 cables ECS ECF ECM assembly view power supply heating cable DEVI EasyConnect EC 3 Power supply connection set for 3 cables heating cable end muff DEVI EasyConnect EC ETK End plug set ECF ECM assembly view end muff heating cable DEVI EasyConnect EC 1 ETK Power supply connection set with end plug 7 DEVI AN384935...

Page 8: ...Industry Picture Name Description Connection kit for DEVIpipeguard 30 60 Industry PT 30 60 heating cables With clamping block for the connection of cold lead and heating cable shrink end cap shrink tubes bitumen gaskets and ferrules Connection kit for DEVIpipeguard 30 60 Industry PT 30 60 heating cables For mounting in connection box with screw connections With cable gland M20x1 5 with locknut shr...

Page 9: ...es 5 Straight lines and sensor must be fitted as shown at Fig 2 Twisted lines are attached as shown for every approx 1 m pipe with aluminum tape 6 Apply aluminum tape below mandatory for plastic pipes and on top on the whole length of the cable Make sure that the cables do not cross sharp edges 7 Attach and cover the sensor and the tip on top of the pipe with aluminum tape Extend cold tails leads ...

Page 10: ...rs gutter valleys on the roof and or the cable 6 Install the cable s on the roof in gutters and downpipes Check once again and compare the insulation resistance 7 Install sensors and extend sensor cables cold tails terminate cables and place connec tions dry Seal all penetrations e g through roofs and walls 8 Check once again and compare the insula tion resistance The measured value shall be no le...

Page 11: ...ordance with the instructions the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided Please note that theWARRANTY CERTIFICATE must be filled in stamped and signed by the author ized installer performing the installation Installation date must be indicated After the installation is performed store and keep theWARRANTY CERTIFICATE and purchase doc...

Page 12: ...ts without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and all Danfoss logotypes are trademarks of Danfoss A S All rights reserved Danfoss A S DEVI devi com 45 7488 8500 E Mail EH danfoss...