Contactors CI 32 - CI 50

 

Thermal overload relay TI 80 

TI 80

Conditional Short Circuit Rating - Suitable for use on 
circuits capable of delivering not more than 100 000 rms 
symmetrical amperes, 600 V maximum when protected 
by Class J fuses

IC.PI.C10.C2.00 | 520B7001 | 2

Before installing the contactor, make sure that the control voltage supply corresponds with the specified voltage.
Wrong control voltage across the terminals (A1 and A2) can cause contactor chattering or coil overheating and damage.

Control voltage must be applied within tolerances given below:

- Standard coil: from -15% to 10%
- Double frequency coil: ±10%