55
Installation Guide
CCR2
Heating Solutions
VI.D1.E2.1R
SMT/SI
ENGLISH
1. Product description
The CCR2 is a control used for optimising the
thermal disinfection process in hot water
systems with functions such as temperature
registration and monitoring circulation hot water
systems. The control is connected to thermo
2. Technical data
3. Installation
For easy access, the CCR2 control is installed in
the technical box on DIN rail 35 mm. Box with
DIN rail should be mounted onto the wall (sub -
station or boiler room) as close as possible to the
heat source. DIN rail and box are not included. It
4. Switching the control on
Before switching the control on for the first
time, disconnect all cables and connect a 24 VAC
source to the disconnected power plug. Use a
voltmeter to measure the voltage on the power
cable plug before it is connected to the control.
If the voltage is correct:
1. Read the instructions before you operate the
control
2. Disconnect all cables
3. Connect the power to the transformer (not
connected to CCR2)
4. Turn on the power to the transformer
5. Verified currency - 24 V
6. Connect the cable from the transformer to the
CCR2 input
The control should display its name and the
software version – CONTROLLER START MENU –
display according to point 5.
Before any plugs are connected to the control’s,
input and output connectors:
1. Set all parameters on the control
2. Make sure that there is no external voltage on
the temperature sensor plugs
3. Make sure that the voltage on the relay
contacts is not too high (max. 24 VAC)
is recommended to install the standard 24 VAC
transformer in the same box as CCR2 (not supply).
Do not install (and remove) SD card when the
CCR2 is connected to the current. It must be
switched off (risk of losing data).
Temperature sensor (S0, S1 … S16)
Pt1000, S0- type ESMC / ESM11, S1 … S16 – type ESMB
Temperature range (registration)
–20 °C … +120 °C
Measuring accuracy
± 0,1 K
Inputs: B1 and B2
Free contact (5 V 1 mA)
Number of control valves (risers)
16
Output signal to actuators (Triac type)
24 VAC max. 1 A
Alarm signal output (Triac type)
24 VAC max. 1 A
Relay output
0 … 24 VAC/DC max. 1 A
OC output (Transistor type)
0 … 20 V DC NPN Open collector max. 200 mA
Type of memory card (included)
SD (512 MB factory card, build in CCR2)
Maximum memory card
2 GB
Timer: Real time clock
Built-in battery - service life 10 years
Ambient temperature
0 … 50 °C
Transport temperature
–10 … +60 °C
IP rating
IP 20,
Power supply
24 VAC
Power consumption
6 VA
Weight
0,9 kg
Installation
DIN rail 35 mm
actuators type TWA - A and remote temperature
sensors PT1000, type ESMB, installed on each
thermostatic circulation valve, type MTCV
(Multifunctional Thermostatic Circulation Valve).